• Indoor Unit • Ceiling suspended unit • FHQ-C
1
2
• Split - Sky Air • Indoor Unit4
2 Specifications
Standard Accessories : Screw for wiring fixture;
Standard Accessories : Wiring fixture;
Standard Accessories : Resin bushing;
Standard Accessories : Sealing material;
Standard Accessories : Joint insulating material;
Standard Accessories : Installation pattern;
Standard Accessories : Clamps;
Standard Accessories : Washer for hanger bracket;
Standard Accessories : Clamp metal;
Standard Accessories : Drain hose;
Standard Accessories : Declaration of conformity;
Standard Accessories : Operation manual;
Standard Accessories : Installation manual;
Sound pressure level Cooling High/Nom./Low dBA 36/34/31 37/35/32 37/35/33 38/36/34 42/38/34 44/41/37 46/42/38
Heating Super high/High/
Nom./Low
dBA -/36/34/31 -/37/35/32 -/37/35/33 -/38/36/34 -/42/38/34 -/44/41/37 -/46/42/38
Re fr igeran t Typ e R-410A
Piping connections Sound absorbing insulation Not needed
Liquid Type/OD mm C1220T (Flare connection)/6.35 C1220T (Flare connection)/9.52
Gas Type/OD mm C1220T
(Flare
connection)/
9.5
C1220T (Flare connection)/
12.7
C1220T (Flare connection)/15.9
Drain VP20
Heat insulation Needed
Air direction control Up and downwards
Air filter Type Resin net with mold resistance
Quantity pc 2
Safety devices Item 01 Fuse (F, 5A, 250V) -
2-2 Electrical Specifications FHQ35C FHQ50C FHQ60C FHQ71C FHQ100C FHQ125C FHQ140C
Power supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Current - 50Hz Maximum running current A 0.6 0.8 1.3 1.5 1.8
Current - 60Hz Nominal running current A -
2-1 Technical Specifications FHQ35C FHQ50C FHQ60C FHQ71C FHQ100C FHQ125C FHQ140C
Komentarze do niniejszej Instrukcji