SiEBE12-625D-Series / E-SeriesSer viceManual[Applied Models]zInverter Multi : Cooling OnlyzInverter Multi : Heat Pump

Strona 2 - D-Series / E-Series

Introduction SiEBE12-625ix1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is

Strona 3

Control Specification SiEBE12-62590 Function and Control3.13 Malfunctions3.13.1 Sensor Malfunction DetectionSensor malfunction may occur either in the

Strona 4 - Table of Contents iii

SiEBE12-625 Control SpecificationFunction and Control 91Detail Judgment by Input CurrentWhen an output frequency is exceeds 55 Hz and the input curren

Strona 5

Control Specification SiEBE12-62592 Function and Control3.15 Wiring-Error CheckOutline The convenient Wiring Error Check function is designed for the

Strona 6 - Table of Contents v

SiEBE12-625 Control SpecificationFunction and Control 93Checking the current setting data on the microcomputer memoryThose data can be checked by look

Strona 7 - 1. Introduction

Control Specification SiEBE12-62594 Function and Control3.16 Additional Function3.16.1 Connection Pipe Condensation Preventing FunctionThis control is

Strona 8

SiEBE12-625 Control SpecificationFunction and Control 953.16.5 Cooling / Heating Mode LockUse the S15 connector to set the unit to only cool or heat.S

Strona 9 - 1.1.3 Inspection after Repair

Control Specification SiEBE12-62596 Function and Control

Strona 10 - 1.1.5 Using Icons List

SiEBE12-625System Configuration 97Part 5System Configuration1. System Configuration...

Strona 11 - List of Functions

System Configuration SiEBE12-62598 List of Functions1. System Configuration1.1 Operation InstructionsAfter the installation and test operation of the

Strona 12 - 1. List of Functions

SiEBE12-625 InstructionList of Functions 992.Instruction2.1 Manual Contents and Reference PageH: Illustrations are for wall mounted type FTXS20-50D as

Strona 13 - List of Functions 3

SiBE12-625List of Functions 1Part 1List of Functions1. List of Functions...

Strona 14 - 4 List of Functions

Instruction SiEBE12-625100 List of Functions2.2 Safety Precautions• Keep this manual where the operator can easily find them.• Read this manual attent

Strona 15 - List of Functions 5

SiEBE12-625 InstructionList of Functions 101Installation siteTo install the air conditioner in the following types of environments, consult the deale

Strona 16 - 6 List of Functions

Instruction SiEBE12-625102 List of Functions2.3Names of PartsFTK(X)S 20/25/35/50 DIndoor UnitON/OFF16 141315121 3 45791011862

Strona 17 - 1.2 Heat Pump Models

SiEBE12-625 InstructionList of Functions 103Outdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fi

Strona 18 - 8 List of Functions

Instruction SiEBE12-625104 List of FunctionsRemote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 19 - List of Functions 9

SiEBE12-625 InstructionList of Functions 105FTK(X)S 20/25/35 CIndoor UnitOFFON

Strona 20 - 10 List of Functions

Instruction SiEBE12-625106 List of FunctionsOudoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fil

Strona 21 - List of Functions 11

SiEBE12-625 InstructionList of Functions 107Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 22 - 12 List of Functions

Instruction SiEBE12-625108 List of FunctionsCDK(X)S 50/60/71 EIndoor UnitMain unit control panel71411121343129108651615

Strona 23 - Specifications

SiEBE12-625 InstructionList of Functions 109Outdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fi

Strona 24 - 1. Specifications

List of Functions SiEBE12-6252 List of Functions1. List of Functions1.1 Cooling Only ModelsCategory FunctionsFTKS20-35D3VMW(L)FTKS50D2V1W(L)FTKS20-35C

Strona 25 - Specifications 15

Instruction SiEBE12-625110 List of FunctionsRemote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 26 - 16 Specifications

SiEBE12-625 InstructionList of Functions 111FLK(X)S 71 BIndoor UnitThis illustration shows a 50-class unitMain unit control panel7141112134315129108

Strona 27 - Specifications 17

Instruction SiEBE12-625112 List of FunctionsOudoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fil

Strona 28 - Duct Connected Type

SiEBE12-625 InstructionList of Functions 113Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 29 - Specifications 19

Instruction SiEBE12-625114 List of FunctionsFTXG 25/35 E, CTXG 50 EIndoor Unit1514181213171 3 4 62111657 8 910(With the panel closed)

Strona 30 - 20 Specifications

SiEBE12-625 InstructionList of Functions 115Outdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fi

Strona 31 - Floor Standing Type

Instruction SiEBE12-625116 List of FunctionsRemote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 32 - 22 Specifications

SiEBE12-625 InstructionList of Functions 117FDK(X)S 25/35/50/60 C, FDK(X)S 25/35 EIndoor Unit36891071452

Strona 33 - 1.3 Indoor Units - Heat Pump

Instruction SiEBE12-625118 List of FunctionsOutdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Air fi

Strona 34 - 24 Specifications

SiEBE12-625 InstructionList of Functions 119Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 35 - Specifications 25

SiEBE12-625 List of FunctionsList of Functions 3Category FunctionsFTKS50-71EV1BFTKS71BAVMBCategory FunctionsFTKS50-71EV1BFTKS71BAVMBBasic FunctionInve

Strona 36 - 26 Specifications

Instruction SiEBE12-625120 List of FunctionsFLK(X)S 25/35/50/60 BIndoor UnitThe indoor unit can be installed either to the ceiling or to a wall. The

Strona 37 - Specifications 27

SiEBE12-625 InstructionList of Functions 121Outdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Louver

Strona 38 - 28 Specifications

Instruction SiEBE12-625122 List of FunctionsRemote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 39 - Specifications 29

SiEBE12-625 InstructionList of Functions 123FVK(X)S 25/35/50 BIndoor UnitOpening the front panelHow to open the front panelCAUTIONAir outlet selecti

Strona 40 - 30 Specifications

Instruction SiEBE12-625124 List of FunctionsOutdoor UnitIndoor UnitOutdoor UnitAppearance of the outdoor unit may differ from some models.1. Photoc

Strona 41 - Specifications 31

SiEBE12-625 InstructionList of Functions 125Remote control1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It displays the cu

Strona 42 - Floor Standing Type 50Hz 230V

Instruction SiEBE12-625126 List of Functions2.4Preparation before OperationTo set the batteries1. Slide the front cover to take it off.2. Set two dry

Strona 43 - 1.4 Outdoor Units - Heat Pump

SiEBE12-625 InstructionList of Functions 127To operate the remote control• To use the remote control, aim the transmitter at the indoor unit. If ther

Strona 44 - 34 Specifications

Instruction SiEBE12-625128 List of FunctionsìNOTETo set the clock1. Press “CLOCK button”.0:00 is displayed.blinks.2. Press “TIMER setting button” to

Strona 45 - Connector Wiring Diagram

SiEBE12-625 InstructionList of Functions 1292.5 AUTO · DRY · COOL · HEAT · FAN OperationThe air conditioner operates with the operation mode of your

Strona 46 - 1.1 Wall Mounted Type

List of Functions SiEBE12-6254 List of FunctionsCategory FunctionsFDKS25/35CAVMBFDKS50/60CVMBFDKS25/35EAVMBCategory FunctionsFDKS25/35CAVMBFDKS50/60CV

Strona 47 - PCB(1): Control PCB

Instruction SiEBE12-625130 List of FunctionsTo change the air flow rate setting5. Press “FAN setting button”.• Indoor unit quiet operationWhen the ai

Strona 48 - 1.1.2 FTK(X)S20~35C

SiEBE12-625 InstructionList of Functions 1312.6 Adjusting the Air Flow DirectionFTK(X)E 20/25/35/50 DYou can adjust the air flow direction to increase

Strona 49

Instruction SiEBE12-625132 List of FunctionsTo start COMFORT AIRFLOW operation3. Press “COMFORT AIRFLOW button”.• The flap position will change, prev

Strona 50 - PCB(2): Signal Receiver PCB

SiEBE12-625 InstructionList of Functions 133FTK(X)S 20/25/35 CYou can adjust the air flow direction to increase your comfort.To adjust the horizontal

Strona 51 - Connectors

Instruction SiEBE12-625134 List of FunctionsTo adjust the vertical blades (louvers)Hold the knob and move the louvers.(You will find a knob on the le

Strona 52

SiEBE12-625 InstructionList of Functions 135FLK(X) 25/35/50/60 AYou can adjust the air flow direction to increase your comfort.To adjust the horizont

Strona 53 - 1.1.4 FTXG25~35E, CTXG50E

Instruction SiEBE12-625136 List of FunctionsTo 3-D Airflow1.3 Press the “SWING button ” and the “SWING button ”:The “ ” and “ ” display will light

Strona 54

SiEBE12-625 InstructionList of Functions 137FTXG 25/35 E, CTXG 50 ETo 3-D Airflow1.3 Press the “SWING button ” and the “SWING button ”:The “ ” and

Strona 55 - 1.2 Duct Connected Type

Instruction SiEBE12-625138 List of FunctionsTo start COMFORT AIRFLOW operation5. Press the “COMFORT AIRFLOW button”.• The flap orientation will chang

Strona 56 - PCB (2): Display PCB

SiEBE12-625 InstructionList of Functions 139FTXS 25/35/50/60 BYou can adjust the air flow direction to increase your comfort.To adjust the horizontal

Strona 57

SiEBE12-625 List of FunctionsList of Functions 5Category FunctionsFLKS25-60BAVMBFVKS25-50BAVMBCategory FunctionsFLKS25-60BAVMBFVKS25-50BAVMBBasic Func

Strona 58 - PCB (4): Signal Receiver PCB

Instruction SiEBE12-625140 List of FunctionsNotes on flap and louvers angles.To adjust the vertical blades (louvers)• When adjusting the louver, use

Strona 59 - 1.4 Floor Standing Type

SiEBE12-625 InstructionList of Functions 141FTXS 25/35/50/60 BTo adjust the vertical blades (louvers)Hold the knob and move the louver.(You will find

Strona 60 - (25, 35 class)

Instruction SiEBE12-625142 List of FunctionsAir flow selection• make air flow selection acoording to what suits you.When setting the air flow selecti

Strona 61 - PCB (2): Control PCB

SiEBE12-625 InstructionList of Functions 1432.7POWERFUL OperationNOTEPowerful operation quickly maximizes the cooling (heating) effect in any operatio

Strona 62 - 1.5 Outdoor Units

Instruction SiEBE12-625144 List of Functions2.8OUTDOOR UNIT SILENT OperationNOTEOUTDOOR UNIT SILENT operation lowers the noise level of the outdoor un

Strona 63 - PCB Detail

SiEBE12-625 InstructionList of Functions 1452.9ECONO OperationNOTEECONO operation is a function which enables efficient operation by lowering the maxi

Strona 64 - Inverter PCB (MID2)

Instruction SiEBE12-625146 List of Functions2.10HOME LEAVE OperationBefore using HOME LEAVE operation.HOME LEAVE operation is a function which allows

Strona 65 - Function and Control

SiEBE12-625 InstructionList of Functions 147What’s the HOME LEAVE operationIs there a set temperature and air flow rate which is most comfortable, a

Strona 66 - 1. Main Functions

Instruction SiEBE12-625148 List of Functions2.11INTELLIGENT EYE OperationFTK(X)E 25/35 B“INTELLIGENT EYE” is the infrared sensor which detects the hum

Strona 67 - Heating Operation

SiEBE12-625 InstructionList of Functions 149“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTIONEnergy saving operation• Ch

Strona 68 - Auto-Swing

List of Functions SiEBE12-6256 List of FunctionsCategory Functions4MKS75E2(3)V1B4MKS90DAVMBCategory Functions4MKS75E2(3)V1B4MKS90DAVMBBasic FunctionIn

Strona 69 - FTK(X)S20-50D

Instruction SiEBE12-625150 List of FunctionsFTK(X)D 50/60/71 B“INTELLIGENT EYE” is the infrared sensor which detects the human movement.To start INTE

Strona 70 - Timing Chart

SiEBE12-625 InstructionList of Functions 151To adjust the angle of the INTELLIGENT EYE sensor“INTELLIGENT EYE” is useful for Energy SavingNotes on “I

Strona 71

Instruction SiEBE12-625152 List of FunctionsFTK(X)S 50/60/71 E, FTK(X)S 71 B“INTELLIGENT EYE” is the infrared sensor which detects the human movement.

Strona 72 - 1.5 Programme Dry Function

SiEBE12-625 InstructionList of Functions 153“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTIONEnergy saving operation• Ch

Strona 73 - 1.6 Automatic Operation

Instruction SiEBE12-625154 List of FunctionsFTK(X)S 50/60/71 E, FTK(X)S 71 B“INTELLIGENT EYE” is the infrared sensor which detects the human movement.

Strona 74 - 1.7 Thermostat Control

SiEBE12-625 InstructionList of Functions 155“INTELLIGENT EYE” is useful for Energy SavingNotes on “INTELLIGENT EYE”CAUTIONEnergy saving operation• Ch

Strona 75 - 1.8 Night Set Mode

Instruction SiEBE12-625156 List of Functions2.12TIMER OperationNotesTimer functions are useful for automatically switching the air conditioner on or o

Strona 76 - 1.9 ECONO Mode

SiEBE12-625 InstructionList of Functions 157ATTENTIONTo use ON TIMER operation• Check that the clock is correct. If not, set the clock to the present

Strona 77 - Function and Control 67

Instruction SiEBE12-625158 List of Functions2.13Note for Multi System<< What is a “Multi System”? >>This system has one outdoor unit conne

Strona 78 - 68 Function and Control

SiEBE12-625 InstructionList of Functions 159Priority Room SettingThe Priority Room Setting requires initial programming during installation. Please c

Strona 79 - Scene <Heating>

SiEBE12-625 List of FunctionsList of Functions 71.2 Heat Pump ModelsCategory FunctionsFTXG25/35EV1BW(S)CTXG50EV1BW(S)Category FunctionsFTXG25/35EV1BW(

Strona 80 - Details of the

Instruction SiEBE12-625160 List of Functions2.14Care and CleaningFTK(X)E 20/25/35/50 DCAUTION Before cleaning, be sure to stop the operation and turn

Strona 81 - ON/OFF button

SiEBE12-625 InstructionList of Functions 1611. Open the front panel.2. Pull out the air filters.• Push a little upwards the tab at the center of each

Strona 82 - 72 Function and Control

Instruction SiEBE12-625162 List of FunctionsNOTECheckBefore a long idle period1. Operate the “fan only” for several hours on a fine day to dry out th

Strona 83 - 2.1 Main Structural Parts

SiEBE12-625 InstructionList of Functions 163FTK(X)D 50/60/71 BCAUTION Before cleaning, be sure to stop the operation and turn the breaker OFF.Indoor

Strona 84 - 2.2 Function of Thermistor

Instruction SiEBE12-625164 List of Functions1. Open the front panel.2. Pull out the air filters.• Push a little upwards the tab at the center of each

Strona 85 - E Liquid Pipe

SiEBE12-625 InstructionList of Functions 165CheckBefore a long idle period1. Operate the “fan only” for several hours on a fine day to dry out the in

Strona 86 - 2.2.2 Cooling Only Model

Instruction SiEBE12-625166 List of FunctionsCDK(X)D 25/35/50/60 CCAUTION Before cleaning, be sure to stop the operation and turn the breaker OFF.Indo

Strona 87

SiEBE12-625 InstructionList of Functions 1671. Open the front panel.2. Pull out the air filters.• Push a little upwards the tab at the center of each

Strona 88 - 3. Control Specification

Instruction SiEBE12-625168 List of FunctionsCheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the in

Strona 89 - 3.2 Frequency Control

SiEBE12-625 InstructionList of Functions 169FTK(X)S 71BCAUTION Before cleaning, be sure to stop the operation and turn the breaker OFF.Indoor unit, O

Strona 90

List of Functions SiEBE12-6258 List of FunctionsCategory FunctionsFTXS20-35D3VMW(L)FTXS50D2V1W(L)FTXS20-35CAVMBCategory FunctionsFTXS20-35D3VMW(L)FTXS

Strona 91 - Frequency

Instruction SiEBE12-625170 List of Functions1. Open the front panel.2. Pull out the air filters.• Push a little upwards the tab at the center of each

Strona 92 - 3.5 Input Current Control

SiEBE12-625 InstructionList of Functions 171CheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the in

Strona 93 - 3.7 Heating Peak-cut Control

Instruction SiEBE12-625172 List of FunctionsFTK(X)S 71BCAUTION • Before cleaning, be sure to stop the operation and turn the breaker OFF.• Always shut

Strona 94 - 3.8 Fan Control

SiEBE12-625 InstructionList of Functions 1731. Open the front panel.• Open the front panel by placing a finger on the panel tab on either side of the

Strona 95 - 3.10 Defrost Control

Instruction SiEBE12-625174 List of FunctionsNOTECheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out th

Strona 96 - Detail Separate into Zones

SiEBE12-625 InstructionList of Functions 175CAUTION • Only a qualified service person is allowed to perform maintenance.• Before cleaning, be sure to

Strona 97 - Function and Control 87

Instruction SiEBE12-625176 List of FunctionsCleaning the drain pan• Clean the drain pan periodically, or drain piping may be clogged with dust and ma

Strona 98

SiEBE12-625 InstructionList of Functions 177FDK(X)S 50/60 C, FDK(X)S 25/35 ECAUTION • Only a qualified service person is allowed to perform maintenanc

Strona 99 - 3.12.10 Oil Recovery Function

Instruction SiEBE12-625178 List of FunctionsCleaning the drain pan• Clean the drain pan periodically, or drain piping may be clogged with dust and ma

Strona 100 - 3.13 Malfunctions

SiEBE12-625 InstructionList of Functions 179FLK(X)S 25/35/50/60 BCAUTION Before cleaning, be sure to stop the operation and turn the breaker OFF.Indo

Strona 101 - 3.14 Forced Operation Mode

SiEBE12-625 List of FunctionsList of Functions 9Category FunctionsFTXS50-71EV1BFTXS71BAVMBCategory FunctionsFTXS50-71EV1BFTXS71BAVMBBasic FunctionInve

Strona 102 - 3.15 Wiring-Error Check

Instruction SiEBE12-625180 List of Functions1. Open the front panel.2. Pull out the air filters..• Push a little upwards the tab at the center of each

Strona 103 - Function and Control 93

SiEBE12-625 InstructionList of Functions 181CheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the in

Strona 104 - When Inverter

Instruction SiEBE12-625182 List of FunctionsFVK(X)S 25/35/50 BCAUTION Before cleaning, be sure to stop the operation and turn the breaker OFF.Indoor

Strona 105 - COOL mode (C)

SiEBE12-625 InstructionList of Functions 1831. Open the front panel.2. Remove the air filter.• Press the claws on the right and left of the air filter

Strona 106 - 96 Function and Control

Instruction SiEBE12-625184 List of FunctionsCheckBefore a long idle period1. Operate the “FAN only” for several hours on a fine day to dry out the in

Strona 107 - System Configuration

SiEBE12-625 InstructionList of Functions 1852.15TroubleshootingThe following cases are not air conditioner troubles but have some reasons. You may jus

Strona 108 - 1. System Configuration

Instruction SiEBE12-625186 List of FunctionsPlease check again before calling a repair person.Check again.Case CheckThe air conditioner does not opera

Strona 109 - Instruction

SiEBE12-625 InstructionList of Functions 187WARNINGIf one of the following symptoms takes place, call the service shop immediately.Disposal requiremen

Strona 110 - 2.2 Safety Precautions

Instruction SiEBE12-625188 List of FunctionsFAULT DIAGNOSIS BY REMOTE CONTROLIn the ARC433A series, the temperature display sections on the main unit

Strona 111 - System relocation

SiEBE12-625 InstructionList of Functions 189LED ON OUTDOOR UNIT PCB 3MXS, 3MKS, 4MXS, 4MKS seriesNOTESGREEN REDMICROCOMPUTERNORMALMALFUNCTIONDETE

Strona 112 - Names of Parts

SiEBE12-625Table of Contents iSUPER MULTI NXD-Series / E-SerieszCooling OnlyIndoor UnitFTKS20D3VMW FTKS20CAVMB FDKS25CAVMB FLKS25BAVMBFTKS20D3VML FTKS

Strona 113 - Outdoor Unit

List of Functions SiEBE12-62510 List of FunctionsCategory FunctionsFDXS25/35CAVMBFDXS50/60CVMBFDXS25/35EAVMBCategory FunctionsFDXS25/35CAVMBFDXS50/60C

Strona 114 - Remote control

Instruction SiEBE12-625190 List of Functions

Strona 115 - Indoor Unit

SiEBE12-625Service Diagnosis 191Part 6Service Diagnosis1. Caution for Diagnosis...

Strona 116 - Oudoor Unit

Caution for Diagnosis SiEBE12-625192 Service Diagnosis1. Caution for Diagnosis1.1 Troubleshooting with Operation LampThe operation lamp flashes when a

Strona 117

SiEBE12-625 Caution for DiagnosisService Diagnosis 193In case ofFLK(X)S 25/35/50/60 B SeriesCaution: Operation stops suddenly. (Operation lamp blinks.

Strona 118 - Main unit control panel

Problem Symptoms and Measures SiEBE12-625194 Service Diagnosis2. Problem Symptoms and MeasuresProblem Symptom Check Item Details of Measure Page No.to

Strona 119

SiEBE12-625 Service Check FunctionService Diagnosis 1953. Service Check FunctionIn the ARC433A series remote controller, the temperature display secti

Strona 120

Service Check Function SiEBE12-625196 Service DiagnosisCheck Method 21. Enter the diagnosis mode.Press the 3 buttons (TEMPs,TEMPt, MODE) simultaneousl

Strona 121 - FLK(X)S 71 B

SiEBE12-625 Service Check FunctionService Diagnosis 1975. Press the TEMP button.Press TEMPs or TEMPt and change the digit until you hear the sound of

Strona 122

Code Indication on the Remote Controller SiEBE12-625198 Service Diagnosis4. Code Indication on the Remote Controller4.1 Error Codes and Description of

Strona 123

SiEBE12-625 TroubleshootingService Diagnosis 1995. Troubleshooting5.1 Indoor Units - : Not used for troubleshooting∗ : Varies depending on the cases.I

Strona 124 - FTXG 25/35 E, CTXG 50 E

SiEBE12-625 List of FunctionsList of Functions 11Category FunctionsFLXS25-60BAVMBFVXS25-50BAVMBCategory FunctionsFLXS25-60BAVMBFVXS25-50BAVMBBasic Fun

Strona 125

Troubleshooting SiEBE12-625200 Service Diagnosis5.2 Outdoor Units4: ON, 1: OFF, 5: BlinksGreen : Flashes when in normal conditionRed : OFF in normal c

Strona 126

SiEBE12-625 TroubleshootingService Diagnosis 2015.3 Indoor Unit PCB AbnormalityRemoteControllerDisplayA1Method of Malfunction DetectionEvaluation of z

Strona 127

Troubleshooting SiEBE12-625202 Service Diagnosis5.4 Freeze-up Protection Control or High Pressure ControlRemoteControllerDisplayA5Method of Malfunctio

Strona 128

SiEBE12-625 TroubleshootingService Diagnosis 203TroubleshootingCheck No.06Refer to P.242Note: If the outside temperature is below –10°C in the cooling

Strona 129

Troubleshooting SiEBE12-625204 Service Diagnosis5.5 Fan Motor or Related Abnormality5.5.1 AC MotorRemoteControllerDisplayA6Method of Malfunction Detec

Strona 130 - How to open the front panel

SiEBE12-625 TroubleshootingService Diagnosis 2055.5.2 DC MotorRemoteControllerDisplayA6Method of Malfunction DetectionThe rotation speed detected by t

Strona 131

Troubleshooting SiEBE12-625206 Service DiagnosisTroubleshootingCheck No.01Refer to P.239Check No.02Refer to P.239Replace fan motor.Replace indoor unit

Strona 132

SiEBE12-625 TroubleshootingService Diagnosis 2075.6 Thermistor or Related Abnormality (Indoor Unit)RemoteControllerDisplayC4, C9 Method of Malfunction

Strona 133 - FVK(X)S 25/35/50 B

Troubleshooting SiEBE12-625208 Service Diagnosis5.7 Shutter Drive Motor / Shutter Limit Switch AbnormalityRemoteControllerDisplayC7Method of Malfuncti

Strona 134

SiEBE12-625 TroubleshootingService Diagnosis 2095.8 Front Panel Open / Close FaultRemoteControllerDisplayC7 Method of Malfunction DetectionMalfunction

Strona 135

List of Functions SiEBE12-62512 List of FunctionsCategory Functions4MXS68E2(3)V1B4MXS80DAVMBCategory Functions4MXS68E2(3)V1B4MXS80DAVMBBasic FunctionI

Strona 136 - Preparation before Operation

Troubleshooting SiEBE12-625210 Service Diagnosis5.9 Signal Transmission Error (between Indoor and Outdoor Units)RemoteControllerDisplayU4Method of Mal

Strona 137 - To remove, pull it upwards

SiEBE12-625 TroubleshootingService Diagnosis 2115.10 Unspecified Voltage (between Indoor and Outdoor Units)RemoteControllerDisplayUAMethod of Malfunct

Strona 138 - Turn the breaker ON

Troubleshooting SiEBE12-625212 Service Diagnosis5.11 Freeze-up Protection ControlRemoteControllerDisplayA5Outdoor Unit LED DisplayA 5 1 4 2 1 3

Strona 139 - List of Functions 129

SiEBE12-625 TroubleshootingService Diagnosis 213TroubleshootingCheck No.04Refer to P.240Check No.06Refer to P.242Check the wiring and piping. Check No

Strona 140 - 130 List of Functions

Troubleshooting SiEBE12-625214 Service Diagnosis5.12 OL Activation (Compressor Overload)RemoteControllerDisplayE5Outdoor Unit LED DisplayA 5 1 4 2

Strona 141 - FTK(X)E 20/25/35/50 D

SiEBE12-625 TroubleshootingService Diagnosis 2155.13 Compressor LockRemoteControllerDisplayE6Outdoor Unit LED DisplayA 5 1 1 2 4 3 4 4 1Method

Strona 142 - In FAN mode

Troubleshooting SiEBE12-625216 Service Diagnosis5.14 DC Fan LockRemoteControllerDisplayE7Outdoor Unit LED DisplayA 5 1 4 2 4 3 4 4 4Method of

Strona 143

SiEBE12-625 TroubleshootingService Diagnosis 2175.15 Input Over Current DetectionRemoteControllerDisplayE8Outdoor Unit LED DisplayA 5 1 1 2 4 3

Strona 144 - In HEAT or FAN mode

Troubleshooting SiEBE12-625218 Service DiagnosisTroubleshootingCheck No.07Refer to P.243Check No.08Refer to P.244Check No.14Refer to P.247Replace the

Strona 145 - FLK(X) 25/35/50/60 A

SiEBE12-625 TroubleshootingService Diagnosis 2195.16 Four Way Valve AbnormalityRemoteControllerDisplayEAOutdoor Unit LED DisplayA 5 1 4 2 1 3 1

Strona 146

SiEBE12-625Specifications 13Part 2Specifications1. Specifications...

Strona 147 - List of Functions 137

Troubleshooting SiEBE12-625220 Service DiagnosisTroubleshootingCheck No.05Refer to P.241Check No.06Refer to P.242Check No.11Refer to P.245Correct. Rec

Strona 148 - In COMFORT AIRFLOW mode

SiEBE12-625 TroubleshootingService Diagnosis 2215.17 Discharge Pipe Temperature ControlRemoteControllerDisplayF3Outdoor Unit LED DisplayA 5 1 4 2

Strona 149 - FTXS 25/35/50/60 B

Troubleshooting SiEBE12-625222 Service Diagnosis5.18 High Pressure Control in CoolingRemoteControllerDisplayF6Outdoor Unit LED DisplayA 5 1 4 2 1

Strona 150 - 140 List of Functions

SiEBE12-625 TroubleshootingService Diagnosis 223TroubleshootingCheck No.04Refer to P.240Check No.06Refer to P.242Check No.07Refer to P.243Check No.09R

Strona 151 - COOL/DRY

Troubleshooting SiEBE12-625224 Service Diagnosis5.19 Position Sensor AbnormalityRemoteControllerDisplayH6Outdoor Unit LED DisplayA 5 1 4 2 4 3 1

Strona 152 - Air flow selection

SiEBE12-625 TroubleshootingService Diagnosis 2255.20 CT or Related AbnormalityRemoteControllerDisplayH8Outdoor Unit LED DisplayA 5 1 4 2 4 3 1

Strona 153 - POWERFUL Operation

Troubleshooting SiEBE12-625226 Service DiagnosisTroubleshootingCheck No.12Refer to P.246Turn off the power and turn it on again.Check No. 12Check the

Strona 154 - OUTDOOR UNIT SILENT Operation

SiEBE12-625 TroubleshootingService Diagnosis 2275.21 Thermistor or Related Abnormality (Outdoor Unit)RemoteControllerDisplayP4, J3, J6, J8, J9, H9Outd

Strona 155 - ECONO Operation

Troubleshooting SiEBE12-625228 Service DiagnosisTroubleshootingCheck No.06Refer to P.242P4 : Radiation fin thermistorJ3 : Discharge pipe thermistorJ6

Strona 156 - HOME LEAVE Operation

SiEBE12-625 TroubleshootingService Diagnosis 2295.22 Electrical Box Temperature RiseRemoteControllerDisplayL3Outdoor Unit LED DisplayA 5 1 4 2 4

Strona 157 - Useful in these cases

Specifications SiEBE12-62514 Specifications1. Specifications1.1 Indoor Units - Cooling OnlyWall Mounted Type 50Hz 230VModel FTKS20D3VMW FTKS20D3VMLRat

Strona 158 - INTELLIGENT EYE Operation

Troubleshooting SiEBE12-625230 Service DiagnosisTroubleshootingCheck No.06Refer to P.242Check No.07Refer to P.243Check No.09Refer to P.244Turn off the

Strona 159 - Notes on “INTELLIGENT EYE”

SiEBE12-625 TroubleshootingService Diagnosis 2315.23 Radiation Fin Temperature RiseRemoteControllerDisplayL4Outdoor Unit LED DisplayA 5 1 1 2 1

Strona 160 - 150 List of Functions

Troubleshooting SiEBE12-625232 Service DiagnosisTroubleshootingCheck No.06Refer to P.242Check No.07Refer to P.243Check No.09Refer to P.244Turn off the

Strona 161

SiEBE12-625 TroubleshootingService Diagnosis 2335.24 Output Over Current DetectionRemoteControllerDisplayL5Outdoor Unit LED DisplayA 5 1 1 2 1 3

Strona 162 - 152 List of Functions

Troubleshooting SiEBE12-625234 Service DiagnosisTroubleshootingCheck No.07Refer to P.243Check No.08Refer to P.244Check No.13Refer to P.246Fully open t

Strona 163

SiEBE12-625 TroubleshootingService Diagnosis 2355.25 Insufficient GasRemoteControllerDisplayU0Outdoor Unit LED DisplayA 5 1 1 2 1 3 4 4 4Metho

Strona 164 - • 20 min. after, start

Troubleshooting SiEBE12-625236 Service DiagnosisTroubleshootingCheck No.04Refer to P.240Check No.06Refer to P.242Reconnect in position. Open the stop

Strona 165

SiEBE12-625 TroubleshootingService Diagnosis 2375.26 Low-voltage DetectionRemoteControllerDisplayU2Outdoor Unit LED DisplayA 5 1 4 2 1 3 1 4 4

Strona 166 - TIMER Operation

Troubleshooting SiEBE12-625238 Service Diagnosis5.27 Anti-icing Function in Other Rooms / Unspecified Voltage (between Indoor and Outdoor Units)Remote

Strona 167 - (Example)

SiEBE12-625 CheckService Diagnosis 2396. Check6.1 How to Check6.1.1 Fan Motor Connector Output CheckCheck No.01 1. Check connector connection.2. Check

Strona 168 - 158 List of Functions

SiEBE12-625 SpecificationsSpecifications 1550Hz 230VModel FTKS35D3VMW FTKS35D3VMLRated Capacity 3.5kW Class 3.5kW ClassFront Panel Color White Silver

Strona 169 - Priority Room Setting

Check SiEBE12-625240 Service Diagnosis6.1.3 Electronic Expansion Valve CheckCheck No.04 Conduct the followings to check the electronic expansion valve

Strona 170 - Fit the key

SiEBE12-625 CheckService Diagnosis 2416.1.4 Four Way Valve Performance CheckCheck No.05Turn off the power and turn it on again.Start the heating-mode

Strona 171 - List of Functions 161

Check SiEBE12-625242 Service Diagnosis6.1.5 Thermistor Resistance CheckCheck No.06 Remove the connectors of the thermistors on the PCB, and measure th

Strona 172 - Before a long idle period

SiEBE12-625 CheckService Diagnosis 2436.1.6 Installation Condition CheckCheck No.07Installation condition check Normal Change the position of the air

Strona 173

Check SiEBE12-625244 Service Diagnosis6.1.7 Discharge Pressure CheckCheck No.086.1.8 Outdoor Unit Fan System Check (With DC Motor)Check No.09Discharge

Strona 174 - Air filter

SiEBE12-625 CheckService Diagnosis 2456.1.9 Power Supply Waveforms CheckCheck No.10 Measure the power supply waveform between pins 1 and 3 on the term

Strona 175

Check SiEBE12-625246 Service Diagnosis6.1.11 Capacitor Voltage CheckCheck No.12 Before this checking, be sure to check the main circuit for short-circ

Strona 176 - 166 List of Functions

SiEBE12-625 CheckService Diagnosis 2476.1.13 Main Circuit Electrolytic Capacitor CheckCheck No.14  Checking the main circuit electrolytic capacitorz

Strona 177 - List of Functions 167

Check SiEBE12-625248 Service Diagnosis6.1.15 Hall IC CheckCheck No.16 1. Check the connector connection.2. With the power ON, operation OFF, and the c

Strona 178

SiEBE12-625Removal Procedure 249Part 7Removal Procedure1. Outdoor Unit (80 / 90 Class) ...

Strona 179 - List of Functions 169

Specifications SiEBE12-62516 Specifications50Hz 230VModel FTKS35CAVMB FTKS50D2V1WRated Capacity 3.5kW Class 5.0kW ClassFront Panel Color White WhiteAi

Strona 180 - 170 List of Functions

Outdoor Unit (80 / 90 Class) SiEBE12-625250 Removal Procedure1. Outdoor Unit (80 / 90 Class)1.1 Removal of Outer PanelsProcedure Warning Be sure to wa

Strona 181

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2513Unscrew 3 screws of the right panel, slide it downwards and release the tabs to remove.4

Strona 182 - 172 List of Functions

Outdoor Unit (80 / 90 Class) SiEBE12-625252 Removal Procedure6Unscrew 3 screws of the front panel to remove.7Remove 4 screws of the discharge outlet g

Strona 183 - List of Functions 173

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2531.2 Removal of Propeller FansProcedure Warning Be sure to wait 10 minutes or more after t

Strona 184 - FDK(X)S 25/35 C

Outdoor Unit (80 / 90 Class) SiEBE12-625254 Removal Procedure1.3 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after t

Strona 185 - Cleaning the air filter

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2553Remove the earth wire.4Remove 1 screw of the terminal board.5Release the tab on the top

Strona 186 - 176 List of Functions

Outdoor Unit (80 / 90 Class) SiEBE12-625256 Removal Procedure2. Remove each wire harness1Disconnect 4 connectors of the electronic expansion valve lea

Strona 187

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2574Remove the connector S92 for gas pipe thermistor.5Remove the connector S90 for thermisto

Strona 188 - 178 List of Functions

Outdoor Unit (80 / 90 Class) SiEBE12-625258 Removal Procedure8Remove the relay connector for compressor.9Remove the electrical box cover.10Disconnect

Strona 189 - List of Functions 179

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 25912Take off the thermistor presser spring, and remove the thermistor. Place the thermisto

Strona 190

SiEBE12-625 SpecificationsSpecifications 1750Hz 230VModel FTKS60EV1B FTKS71EV1BRated Capacity 6.0kW Class 7.1kW ClassFront Panel Color White WhiteAir

Strona 191

Outdoor Unit (80 / 90 Class) SiEBE12-625260 Removal Procedure3Remove the outdoor air thermistor lead wire from the groove.4Remove each wire harness, a

Strona 192 - Place front panel in grooves

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2611.4 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning off

Strona 193

Outdoor Unit (80 / 90 Class) SiEBE12-625262 Removal Procedure4Lift the PCB at the terminal board side.5Disconnect each wire harness connector linked t

Strona 194

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2636The figure shows the controller PCB.S20: Electronic expansion valve coil A portS21: Elec

Strona 195 - Troubleshooting

Outdoor Unit (80 / 90 Class) SiEBE12-625264 Removal Procedure1.5 Removal of Fan MotorProcedure Warning Be sure to wait 10 minutes or more after turnin

Strona 196 - Case Check

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2654Remove 4 screws of the fan motor. When reassembling, fix the lead wire to avoid contact

Strona 197 - Disposal requirements

Outdoor Unit (80 / 90 Class) SiEBE12-625266 Removal Procedure1.6 Removal of Electronic Expansion Valve and ThermistorProcedure Warning Be sure to wait

Strona 198 - Fault diagnosis

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2671.7 Removal of Sound Blanket and ReactorProcedure Warning Be sure to wait 10 minutes or m

Strona 199 - Diagnosis marked

Outdoor Unit (80 / 90 Class) SiEBE12-625268 Removal Procedure4Remove the sound blanket (top). Carefully remove the sound blanket, which is easily tor

Strona 200 - 190 List of Functions

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 2691.8 Removal of ShuntProcedure Warning Be sure to wait 10 minutes or more after turning of

Strona 201 - Service Diagnosis

Specifications SiEBE12-62518 SpecificationsDuct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the ext

Strona 202 - 1. Caution for Diagnosis

Outdoor Unit (80 / 90 Class) SiEBE12-625270 Removal Procedure1.9 Removal of Solenoid Valve and Four Way ValveProcedure Warning Be sure to wait 10 minu

Strona 203 - Service Diagnosis 193

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 271 Before taking this procedure, make sure there is no refrigerant gas left in the refrige

Strona 204

Outdoor Unit (80 / 90 Class) SiEBE12-625272 Removal Procedure1.10 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after turn

Strona 205 - 3. Service Check Function

SiEBE12-625 Outdoor Unit (80 / 90 Class)Removal Procedure 273 Make sure there is no refrigerant gas left inside the refrigerant pipes before starting

Strona 206 - → See 7.)

Outdoor Unit (68 / 75 Class) SiEBE12-625274 Removal Procedure2. Outdoor Unit (68 / 75 Class)2.1 Removal of Outer PanelsProcedure Warning Be sure to wa

Strona 207 - → Refer to page 198.)

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2752.2 Removal of Electrical BOXProcedure Warning Be sure to wait 10 minutes or more after t

Strona 208

Outdoor Unit (68 / 75 Class) SiEBE12-625276 Removal Procedure3Pull out the terminal board to open. Glass tube fuse and varistor cannot be replaced in

Strona 209 - 5. Troubleshooting

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2774Disconnect the compressor relay connector.5Remove the reactor lead wire.3. Removing the

Strona 210 - 5.2 Outdoor Units

Outdoor Unit (68 / 75 Class) SiEBE12-625278 Removal Procedure2Remove 1 screw of the electrical box.3Remove the drip-proof cover.4Disconnect the fan mo

Strona 211

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2792.3 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning off

Strona 212 - 202 Service Diagnosis

SiEBE12-625 SpecificationsSpecifications 1950Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the external static pressu

Strona 213

Outdoor Unit (68 / 75 Class) SiEBE12-625280 Removal Procedure5Lift up the control PCB.6Disconnect each wire harness connector linked to the control PC

Strona 214 - 5.5.1 AC Motor

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2817The figure shows the control PCB. Glass tube fuse 3A2. Removing the service monitor PCB

Strona 215 - 5.5.2 DC Motor

Outdoor Unit (68 / 75 Class) SiEBE12-625282 Removal Procedure2.4 Removal of Fan MotorProcedure Warning Be sure to wait 10 minutes or more after turnin

Strona 216

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2832.5 Removal of Sound BlanketProcedure Warning Be sure to wait 10 minutes or more after tu

Strona 217 - Service Diagnosis 207

Outdoor Unit (68 / 75 Class) SiEBE12-625284 Removal Procedure2.6 Removal of Four Way Valve Coil, Solenoid Valve Coil, Electronic Expansion Valve Coil

Strona 218 - 208 Service Diagnosis

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2855Take off the putty, and remove each thermistor. Place the thermistor so that its end co

Strona 219 - Service Diagnosis 209

Outdoor Unit (68 / 75 Class) SiEBE12-625286 Removal Procedure2.7 Removal of Four Way Valve, Solenoid Valve and ShuntProcedure Warning Be sure to wait

Strona 220 - 210 Service Diagnosis

SiEBE12-625 Outdoor Unit (68 / 75 Class)Removal Procedure 2872.8 Removal of Solenoid Valve and ShuntProcedure Warning Be sure to wait 10 minutes or mo

Strona 221 - Service Diagnosis 211

Outdoor Unit (68 / 75 Class) SiEBE12-625288 Removal Procedure2.9 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after turni

Strona 222 - 5 1 4 2 1 3 4 4 4

SiEBE12-625Others 289Part 8Others1. Others ...2901.1 Tes

Strona 223

SiEBE12-625ii Table of Contents1. Introduction ...vi1.1 Safet

Strona 224 - 5 1 4 2 1 3 4 4 1

Specifications SiEBE12-62520 SpecificationsFloor / Ceiling Suspended Dual Type50Hz 230VModel FLKS25BAVMB FLKS35BAVMBRated Capacity 2.5kW Class 3.5kW C

Strona 225 - 5.13 Compressor Lock

Others SiEBE12-625290 Others1. Others1.1 Test Run from the Remote ControllerFor Heat pump In cooling mode, select the lowest programmable temperature;

Strona 226 - 5.14 DC Fan Lock

SiEBE12-625 OthersOthers 2911.2 Jumper Settings1.2.1 When Two Units are Installed in One RoomWhen two indoor units are installed in one room, the two

Strona 227 - 5 1 1 2 4 3 1 4 4

Others SiEBE12-625292 Others1.2.3 Adjusting the Angle of the Intelligent Eye SensorFTK(X)S20-35C Once installation of the indoor unit is complete, ad

Strona 228

SiEBE12-625Appendix 293Part 9Appendix1. Piping Diagrams...2941.1 Indoor

Strona 229 - 5 1 4 2 1 3 1 4 1

Piping Diagrams SiEBE12-625294 Appendix1. Piping Diagrams1.1 Indoor Units1.1.1 Wall Mounted TypeFTKS20/25/35D3VMW(L) FTXS20/25/35D3VMW(L)FTKS20/25/35C

Strona 230

SiEBE12-625 Piping DiagramsAppendix 295FTKS50D2V1W(L) FTXS50D2V1W(L)FTK(X)S50/60EV1B FTKS71EV1B, FTKS71BAV1BM4D051577INDOOR UNITThermistoron heat exch

Strona 231

Piping Diagrams SiEBE12-625296 AppendixCTXG50EV1BW(S)FTXS71EV1B, FTXS71BAVMB FTXG25/35EV1BW(S)M4D040082MINDOOR UNITCross flow fanFan motorField piping

Strona 232

SiEBE12-625 Piping DiagramsAppendix 2971.1.2 Duct Connected TypeFDK(X)S25/35EAVMB, FDK(X)S50/60CVMB, FDK(X)S25/35CAVMB1.1.3 Floor / Ceiling Suspended

Strona 233

Piping Diagrams SiEBE12-625298 Appendix1.1.4 Floor Standing TypeFLXS25/35BAVMB FLXS50/60BAVMBM4D048722AINDOOR UNITSirocco fanFan motorField pipingFiel

Strona 234 - 5 1 4 2 4 3 1 4 1

SiEBE12-625 Piping DiagramsAppendix 299FVKS50BAVMB FVXS50BAVMBMM4.8CuT4.8CuT7.0CuT7.0CuT7.0CuT7.0CuT4D050804INDOOR UNITHeat exchangerField pipingField

Strona 235

SiEBE12-625 SpecificationsSpecifications 21Floor Standing Type50Hz 230VModel FVKS25BAVMB FVKS35BAVMBRated Capacity 2.5kW Class 3.5kW ClassFront Panel

Strona 236

Piping Diagrams SiEBE12-625300 Appendix1.2 Outdoor Units1.2.1 Cooling Only4MKS75E2(3)V1B4MKS90DAVMB9.5CuTOUTDOOR UNIT7.9CuTPROPELLER FANDC FAN MOTORHE

Strona 237 - P4, J3, J6, J8, J9, H9

SiEBE12-625 Piping DiagramsAppendix 3011.2.2 Heat Pump4MXS68E2(3)V1B4MXS80DAVMBHEADEROUTDOOR UNIT12.7CuTPROPELLER FANDC FAN MOTORHEAT EXCHANGERCOMPRES

Strona 238

Wiring Diagrams SiEBE12-625302 Appendix2. Wiring Diagrams2.1 Indoor Units2.1.1 Wall Mounted TypeFTK(X)S20/25/35D3VMW(L)FTK(X)S20/25/35CAVMBR1T, R2T

Strona 239 - 5 1 4 2 4 3 1 4 4

SiEBE12-625 Wiring DiagramsAppendix 303FTK(X)S50D2V1W(L)FTK(X)S50/60/71EV1B, FTK(X)S71BAVMBPCB3PCB4LED2LED3H2P H3P LED1H1P S1WR1T t°S27S36S26PCB2S35S2

Strona 240

Wiring Diagrams SiEBE12-625304 AppendixFTXG25/35EV1BW(S), CTXG50EV1BW(S)2.1.2 Duct Connected TypeFDK(X)S25/35CAVMB, FDK(X)S50/60CVMB, FDK(X)S25/35EAVM

Strona 241 - 5 1 1 2 1 3 1 4 4

SiEBE12-625 Wiring DiagramsAppendix 3052.1.3 Floor / Ceiling Suspended Dual TypeFLK(X)S25/35/50/60BAVMB2.1.4 Floor Standing TypeFVK(X)S25/35/50BAVMBLE

Strona 242

Wiring Diagrams SiEBE12-625306 Appendix2.2 Outdoor Units2.2.1 Cooling only4MKS75E2(3)V1B, 4MKS90DAVMB2.2.2 Heat Pump4MXS68E2(3)V1B, 4MXS80DAVMBROOM A

Strona 243 - 5 1 1 2 1 3 4 4 1

SiEBE12-625Index iIndexNumerics3 minutes stand-by...81AA1...

Strona 244

SiEBE12-625ii IndexJ9...227L3...

Strona 245 - 5.25 Insufficient Gas

SiEBE12-625Index iiiMID1...53MID2...

Strona 246

Specifications SiEBE12-62522 Specifications1.2 Outdoor Units - Cooling Only50Hz 230VNote:1. The data are based on the conditions shown in the table be

Strona 247 - 5.26 Low-voltage Detection

SiEBE12-625iv IndexS92...52, 257, 263, 276, 285S93...52, 256, 263, 276,

Strona 248 - 5 1 1 2 1 3 1 4 1

SiEBE12-625Drawings & Flow Charts vDrawings & Flow ChartsAanti-icing function in other rooms ...238ARC433A ...

Strona 249 - 6. Check

SiEBE12-625vi Drawings & Flow ChartsFLKS50/60BAVMB ...297FLXS25/35BAVMB ...

Strona 250

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (

Strona 251 - Check No.05

SiEBE12-625 SpecificationsSpecifications 231.3 Indoor Units - Heat PumpWall Mounted Type 50Hz 230VModelFTXG25EV1BW FTXG25EV1BSCooling Heating Cooling

Strona 252 - Resistance range

Specifications SiEBE12-62524 Specifications50Hz 230VModelFTXS20D3VMW FTXS20D3VMLCooling Heating Cooling HeatingRated Capacity 2.0kW Class 2.0kW ClassF

Strona 253 - Check No.07

SiEBE12-625 SpecificationsSpecifications 2550Hz 230VModelFTXS35D3VMW FTXS35D3VMLCooling Heating Cooling HeatingRated Capacity 3.5kW Class 3.5kW ClassF

Strona 254 - Check No.09

Specifications SiEBE12-62526 Specifications50Hz 230VModelFTXS35CAVMBCooling HeatingRated Capacity 3.5kW ClassFront Panel Color WhiteAir Flow Ratesm³/m

Strona 255 - Check No.11

SiEBE12-625 SpecificationsSpecifications 2750Hz 230VModelFTXS50D2V1W FTXS50D2V1LCooling Heating Cooling HeatingRated Capacity 5.0kW Class 5.0kW ClassF

Strona 256 - 6.1.12 Power Transistor Check

Specifications SiEBE12-62528 Specifications50Hz 230VModelFTXS71EV1B FTXS71BAVMBCooling Heating Cooling HeatingRated Capacity 7.1kW Class 7.1kW ClassFr

Strona 257 - Service Diagnosis 247

SiEBE12-625 SpecificationsSpecifications 29Duct Connected Type50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the ext

Strona 258 - 6.1.15 Hall IC Check

SiEBE12-625Table of Contents iii3.8 Fan Control...843.9 Liqu

Strona 259 - Removal Procedure

Specifications SiEBE12-62530 Specifications50Hz 230VNote:1. The operating sound is based on the rear side suction inlet and the external static pressu

Strona 260 - Piping connection slot

SiEBE12-625 SpecificationsSpecifications 31Floor / Ceiling Suspended Dual Type50Hz 230VModelFLXS25BAVMB FLXS35BAVMBCooling Heating Cooling HeatingRate

Strona 261

Specifications SiEBE12-62532 SpecificationsFloor Standing Type 50Hz 230VModelFVXS25BAVMB FVXS35BAVMBCooling Heating Cooling HeatingRated Capacity 2.5k

Strona 262

SiEBE12-625 SpecificationsSpecifications 331.4 Outdoor Units - Heat Pump50Hz 230VNote:1. The data are based on the conditions shown in the table below

Strona 263 - Washer-fitted nut M8

Specifications SiEBE12-62534 Specifications

Strona 264 - 1.3 Removal of Electrical Box

SiEBE12-625Printed Circuit Board Connector Wiring Diagram 35Part 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wiri

Strona 265 - Varister

Printed Circuit Board Connector Wiring Diagram SiEBE12-62536 Printed Circuit Board Connector Wiring Diagram1. Printed Circuit Board Connector Wiring D

Strona 266

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 37PCB Detail PCB(1): Control PCBPCB(4): INTEL

Strona 267

Printed Circuit Board Connector Wiring Diagram SiEBE12-62538 Printed Circuit Board Connector Wiring Diagram1.1.2 FTK(X)S20~35CConnectorsNote: Other de

Strona 268 - Electrical box cover

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 39PCBJP21JBJAJC5VGND12V(R2413)SW7PCB(1) Contr

Strona 269 - Discharge pipe

SiEBE12-625iv Table of Contents5.13 Compressor Lock ...2155.14 DC Fan Lo

Strona 270 - Electrical box

Printed Circuit Board Connector Wiring Diagram SiEBE12-62540 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(1): Control PCBPCB(2): Signa

Strona 271 - Base bar

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 411.1.3 FTK(X)S50~71E, FTK(X)S71BConnectorsNo

Strona 272 - Procedure Points

Printed Circuit Board Connector Wiring Diagram SiEBE12-62542 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(1): Control PCB (indoor unit

Strona 273

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 431.1.4 FTXG25~35E, CTXG50EConnectors PCB(1)

Strona 274

Printed Circuit Board Connector Wiring Diagram SiEBE12-62544 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB(1): Control PCB (indoor unit

Strona 275

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 451.2 Duct Connected TypeConnectorsNote: Othe

Strona 276

Printed Circuit Board Connector Wiring Diagram SiEBE12-62546 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (2): Display PCBSW1LED1LED2

Strona 277 - Sound blanket

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 471.3 Floor / Ceiling Suspended Dual TypeConn

Strona 278

Printed Circuit Board Connector Wiring Diagram SiEBE12-62548 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (2): Power Supply PCBPCB (3)

Strona 279 - 1.8 Removal of Shunt

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 491.4 Floor Standing TypeConnectorsNote: Othe

Strona 280

SiEBE12-625Table of Contents vPart 9 Appendix... 2931. Piping Diagrams...

Strona 281

Printed Circuit Board Connector Wiring Diagram SiEBE12-62550 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Power Supply PCB (25, 3

Strona 282 - 1.10 Removal of Compressor

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 51PCB Detail PCB (2): Control PCBPCB (3): Dis

Strona 283

Printed Circuit Board Connector Wiring Diagram SiEBE12-62552 Printed Circuit Board Connector Wiring Diagram1.5 Outdoor UnitsConnectorsMID 1Inverter PC

Strona 284 - Piping cover

SiEBE12-625 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 53SPMPCB Detail PCB (1): Control PCBMID11) CN

Strona 285 - 2.2 Removal of Electrical BOX

Printed Circuit Board Connector Wiring Diagram SiEBE12-62554 Printed Circuit Board Connector Wiring DiagramInverter PCB (MID2)SPMW VUNS34S72S70FU201 (

Strona 286

SiEBE12-625Function and Control 55Part 4Function and Control1. Main Functions...

Strona 287 - Wiring fixture

Main Functions SiEBE12-62556 Function and Control1. Main FunctionsNote: See the list of functions for the functions applicable to different models.1.1

Strona 288 - Drip-proof cover

SiEBE12-625 Main FunctionsFunction and Control 57Inverter Features The inverter provides the following features: The regulating capacity can be chang

Strona 289

Main Functions SiEBE12-62558 Function and Control1.2 Power-Airflow Dual Flaps, Wide Angle Louvers and Auto-SwingPower-airflow Dual FlapsThe large flap

Strona 290 - ECN1 (green)

SiEBE12-625 Main FunctionsFunction and Control 59FTK(X)S20-50DThe vertical swing flap is controlled not to blow the air directly on the person in the

Strona 291

SiEBE12-625 Introductionvi1. Introduction1.1 Safety CautionsCautions and Warnings Be sure to read the following safety cautions before conducting rep

Strona 292 - Washer-fitted nut

Main Functions SiEBE12-62560 Function and Control1.3 Operation Starting ControlFTXG25-35E, CTXG50EThe system carries out the following control at the

Strona 293 - 2.5 Removal of Sound Blanket

SiEBE12-625 Main FunctionsFunction and Control 611.4 Fan Speed Control for Indoor UnitsControl Mode The airflow rate can be automatically controlled d

Strona 294

Main Functions SiEBE12-62562 Function and Control1.5 Programme Dry FunctionProgramme dry function removes humidity while preventing the room temperatu

Strona 295 - Thermistor

SiEBE12-625 Main FunctionsFunction and Control 631.6 Automatic OperationAutomatic Cooling / Heating Function (Heat Pump Only)When the AUTO mode is sel

Strona 296

Main Functions SiEBE12-62564 Function and Control1.7 Thermostat ControlThermostat control is based on the difference between the room temperature and

Strona 297 - Brazed part

SiEBE12-625 Main FunctionsFunction and Control 651.8 Night Set ModeWhen the OFF timer is set, the Night Set circuit automatically activates.The Night

Strona 298 - 2.9 Removal of Compressor

Main Functions SiEBE12-62566 Function and Control1.9 ECONO ModeOutline FTK(X)S20-50DThe "ECONO mode" reduces the maximum operating current a

Strona 299 - Others 289

SiEBE12-625 Main FunctionsFunction and Control 671.10 INTELLIGENT EYE (Wall Mounted Type Only)This is the function that detects existence of humans in

Strona 300 - 1. Others

Main Functions SiEBE12-62568 Function and Control Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes low and

Strona 301 - (R4417) (R4418)

SiEBE12-625 Main FunctionsFunction and Control 691.11 HOME LEAVE OperationOutline In order to respond to the customer's need for immediate heatin

Strona 302 - 292 Others

Introduction SiEBE12-625vii1.1.2 Cautions Regarding Products after RepairCautionDo not repair the electrical components with wet hands.Working on the

Strona 303 - Appendix

Main Functions SiEBE12-62570 Function and Control1.12 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full

Strona 304 - 1. Piping Diagrams

SiEBE12-625 Main FunctionsFunction and Control 711.13 Other Functions1.13.1 Hot Start FunctionHeat Pump OnlyIn order to prevent the cold air blast tha

Strona 305 - FTKS50D2V1W(L) FTXS50D2V1W(L)

Main Functions SiEBE12-62572 Function and Control1.13.5 Photocatalytic Deodorizing FilterPhotocatalytic Deodorizing Filter demonstrates powerful oxida

Strona 306 - CTXG50EV1BW(S)

SiEBE12-625 Function of Main Structural PartsFunction and Control 732. Function of Main Structural Parts2.1 Main Structural PartsHeat Pump ModelCoolin

Strona 307 - 1.1.2 Duct Connected Type

Function of Main Structural Parts SiEBE12-62574 Function and Control2.2 Function of Thermistor2.2.1 Heat Pump ModelA Outdoor Heat ExchangerThermisto

Strona 308 - 1.1.4 Floor Standing Type

SiEBE12-625 Function of Main Structural PartsFunction and Control 75D Indoor Heat ExchangerThermistor1. The indoor heat exchanger thermistors are us

Strona 309 - FVKS50BAVMB FVXS50BAVMB

Function of Main Structural Parts SiEBE12-62576 Function and Control2.2.2 Cooling Only ModelA Outdoor Heat ExchangerThermistor1. The outdoor heat ex

Strona 310 - 1.2 Outdoor Units

SiEBE12-625 Function of Main Structural PartsFunction and Control 77D Indoor Heat ExchangerThermistor1. The indoor heat exchanger thermistors are us

Strona 311 - 1.2.2 Heat Pump

Control Specification SiEBE12-62578 Function and Control3. Control Specification3.1 Mode HierarchyOutline There are two modes; the mode selected in us

Strona 312 - 2. Wiring Diagrams

SiEBE12-625 Control SpecificationFunction and Control 793.2 Frequency ControlOutline Frequency that corresponds to each room’s capacity will be determ

Strona 313 - FTK(X)S50D2V1W(L)

SiEBE12-625 Introductionviii1.1.3 Inspection after RepairBe sure to use an exclusive power circuit for the equipment, and follow the technical standar

Strona 314 - 2.1.2 Duct Connected Type

Control Specification SiEBE12-62580 Function and Control2. Determine upper limit frequency Set a minimum value as an upper limit frequency among the

Strona 315 - 2.1.4 Floor Standing Type

SiEBE12-625 Control SpecificationFunction and Control 813.3 Controls at Mode Changing / Start-up3.3.1 Preheating OperationOutline Operate the inverter

Strona 316 - 2.2 Outdoor Units

Control Specification SiEBE12-62582 Function and Control3.4 Discharge Pipe ControlOutline The discharge pipe temperature is used as the compressor&apo

Strona 317

SiEBE12-625 Control SpecificationFunction and Control 833.6 Freeze-up Protection ControlOutline During cooling operation, the signals being sent from

Strona 318

Control Specification SiEBE12-62584 Function and Control3.8 Fan ControlOutline Fan control is carried out with following functions.1. Fan ON control f

Strona 319 - Index iii

SiEBE12-625 Control SpecificationFunction and Control 853.10 Defrost ControlOutline Heat Pump OnlyDefrosting is carried out by the cooling cycle (reve

Strona 320

Control Specification SiEBE12-62586 Function and Control3.11 Low Hz High Pressure LimitOutline Heat Pump OnlySet the upper limit of high pressure in a

Strona 321 - Drawings & Flow Charts

SiEBE12-625 Control SpecificationFunction and Control 87Detail The followings are the examples of control which function in each mode by the electroni

Strona 322

Control Specification SiEBE12-62588 Function and Control3.12.1 Fully Closing with Power ONInitialize the electronic expansion valve when turning on th

Strona 323 - Prepared in Belgium by Lannoo

SiEBE12-625 Control SpecificationFunction and Control 893.12.7 Disconnection of the Discharge Pipe ThermistorOutline Detect a disconnected discharge p