Service ManualInverter Multi for 2 RoomsG-SeriesSiBE12-816_D[Applied Models]● Inverter Multi : Cooling Only● Inverter Multi : Heat Pump

Strona 2 - G-Series

Introduction SiBE12-816_DixCheck to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet securely.If th

Strona 3 - Table of Contents ii

Control Specification SiBE12-816_D89 Function and Control4.7 Heating Peak-cut ControlOutline During heating operation, the indoor heat exchanger tempe

Strona 4

SiBE12-816_D Control SpecificationFunction and Control 904.9 Liquid Compression Protection FunctionOutline In order to obtain the dependability of the

Strona 5 - Table of Contents iv

Control Specification SiBE12-816_D91 Function and Control4.11 Electronic Expansion Valve ControlOutline The following items are included in the electr

Strona 6

SiBE12-816_D Control SpecificationFunction and Control 92Detail The followings are the examples of control which function in each mode by the electron

Strona 7 - 1. Introduction

Control Specification SiBE12-816_D93 Function and Control4.11.1 Fully Closing with Power onThe electronic expansion valve is initialized when the powe

Strona 8

SiBE12-816_D Control SpecificationFunction and Control 944.11.8 Target Discharge Pipe Temperature ControlThe target discharge pipe temperature is obta

Strona 9

Control Specification SiBE12-816_D95 Function and Control4.11.10 Disconnection of the Discharge Pipe ThermistorOutline The disconnection of the discha

Strona 10

SiBE12-816_D Control SpecificationFunction and Control 964.12.3 Refrigerant Shortage ControlOutline I Detecting by power consumptionIf the power consu

Strona 11 - 1.2 Used Icons

Control Specification SiBE12-816_D97 Function and Control4.12.4 Anti-icing ControlDuring cooling, if the indoor heat exchanger temperature in the oper

Strona 12 - List of Functions

SiBE12-816_DOperation Manual 98Part 5Operation Manual1. System Configuration...

Strona 13 - 1. Functions

SiBE12-816_D Introductionx1.2 Used IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is des

Strona 14 - — : No Functions

System Configuration SiBE12-816_D99 Operation Manual1. System ConfigurationAfter the installation and test operation of the room air conditioner have

Strona 15 - List of Functions 4

SiBE12-816_D RA Indoor UnitOperation Manual 1002. RA Indoor Unit2.1 FTXG-J, CTXG-J Series - ARC466A12.1.1 Name of PartsDisplayName of Parts• Appearanc

Strona 16 - 1.2 Heat Pump

RA Indoor Unit SiBE12-816_D101 Operation Manual6• Appearance of the outdoor unit may differ from some models. Open the front panelAir filterEarth ter

Strona 17 - List of Functions 6

SiBE12-816_D RA Indoor UnitOperation Manual 1027Name of PartsRemote ControllerSignal transmitterReceiver FAN setting button• It selects the airflow ra

Strona 18 - 7 List of Functions

RA Indoor Unit SiBE12-816_D103 Operation Manual8 Open the front coverECONO button• ECONO operation. Page 20SWING button• Adjusting the airflow direc

Strona 19 - List of Functions 8

SiBE12-816_D RA Indoor UnitOperation Manual 1042.1.2 AUTO · DRY · COOL · HEAT · FAN Operation11The air conditioner operates with the operation mode of

Strona 20 - 9 List of Functions

RA Indoor Unit SiBE12-816_D105 Operation Manual12 To change the temperature settingPress .COOL operation HEAT operation AUTO operation DRY or FAN

Strona 21 - Specifications

SiBE12-816_D RA Indoor UnitOperation Manual 1062.1.3 Adjusting the Airflow Direction and Rate13You can adjust the airflow direction to increase your c

Strona 22 - 1. Specifications

RA Indoor Unit SiBE12-816_D107 Operation Manual14 To adjust the airflow rate settingPress .• Each pressing of advances the airflow rate s

Strona 23 - 50 Hz, 220 - 230 - 240 V

SiBE12-816_D RA Indoor UnitOperation Manual 1082.1.4 COMFORT AIRFLOW Operation15COMFORT AIRFLOW Operation To start COMFORT AIRFLOW operationPress

Strona 24

SiBE12-816_D1 List of FunctionsPart 1List of Functions1. Functions...

Strona 25 - Floor Standing Type

RA Indoor Unit SiBE12-816_D109 Operation Manual2.1.5 INTELLIGENT EYE Operation16 To start INTELLIGENT EYE operationPress .Display To cance

Strona 26

SiBE12-816_D RA Indoor UnitOperation Manual 11017INTELLIGENT EYE OperationNOTE Notes on INTELLIGENT EYE operation• Application range is as follows.90

Strona 27 - 50 Hz, 230 V

RA Indoor Unit SiBE12-816_D111 Operation Manual2.1.6 POWERFUL Operation18POWERFUL Operation To start POWERFUL operationPress during operation. To

Strona 28 - Ceiling Mounted Cassette Type

SiBE12-816_D RA Indoor UnitOperation Manual 1122.1.7 OUTDOOR UNIT QUIET Operation19 To start OUTDOOR UNIT QUIET operationPress . • “ ”

Strona 29 - 50 Hz, 220 - 240 V

RA Indoor Unit SiBE12-816_D113 Operation Manual2.1.8 ECONO Operation20ECONO Operation To start ECONO operationPress during operation.• “

Strona 30

SiBE12-816_D RA Indoor UnitOperation Manual 1142.1.9 OFF TIMER Operation21OFF TIMER Operation To use OFF TIMER operation• Check that the clock is cor

Strona 31 - 1.3 Heat Pump - Indoor Unit

RA Indoor Unit SiBE12-816_D115 Operation Manual2.1.10 ON TIMER Operation22ON TIMER Operation To use ON TIMER operation1. Press ..3. Press

Strona 32

SiBE12-816_D RA Indoor UnitOperation Manual 1162.1.11 WEEKLY TIMER OperationUse the copy mode to make settings for Tuesday to Friday, because these se

Strona 33

RA Indoor Unit SiBE12-816_D117 Operation Manual• Pressing changes “ON” or “OFF” setting in sequence. Pressing alternates the following i

Strona 34

SiBE12-816_D RA Indoor UnitOperation Manual 11825WEEKLY TIMER OperationNOTE Notes on WEEKLY TIMER operation6. Press to select the desired time.

Strona 35

SiBE12-816_D FunctionsList of Functions 21. Functions1.1 Cooling OnlyCategory FunctionsFTXS20/25/35/42/50G2V1BFTXS20/25/35/42/50J2V1BFVXS25/35/50FV1BC

Strona 36

RA Indoor Unit SiBE12-816_D119 Operation Manual26Copy mode6:00 8:30 17:30 22:0025˚C 27˚C6:00 8:30 17:30 22:0025˚C 27˚CCOPYCOPYCOPYProgram 1 Program 2

Strona 37

SiBE12-816_D RA Indoor UnitOperation Manual 120• The “ ”will disappear from the LCD.• The TIMER lamp goes off.• To reactivate the WEEKLY

Strona 38

RA Indoor Unit SiBE12-816_D121 Operation Manual28 To delete reservationsThe individual reservation1. Press .• The day of the week and the rese

Strona 39

SiBE12-816_D RA Indoor UnitOperation Manual 1222.2 FTXS, FVXS Series - ARC452A1, A32.2.1 Manual Contents and Reference Page★: Illustrations are for FT

Strona 40 - 1.4 Heat Pump - Outdoor Unit

RA Indoor Unit SiBE12-816_D123 Operation Manual2.2.2 Names of PartsFTXS20/25/35/42/50G2V1B, FTXS20/25/35/42/50J2V1BNames of parts Indoor Unit 16 141

Strona 41

SiBE12-816_D RA Indoor UnitOperation Manual 124 Indoor Unit1. Air filter3. Air inlet4. Front panel5. Panel tab6. Room temperature sensor:•

Strona 42 - Connector Wiring Diagram

RA Indoor Unit SiBE12-816_D125 Operation Manual Remote Controller 156234<ARC452A3>7813141517<Open the front cover>10911121618• It displ

Strona 43 - 1. Indoor Unit

SiBE12-816_D RA Indoor UnitOperation Manual 126FVXS25/35/50FV1BNames of parts Indoor Unit CAUTION 12652478391210111314Air outlet selection switch•

Strona 44 - PCB (2): Signal Receiver PCB

RA Indoor Unit SiBE12-816_D127 Operation Manual22˚C25˚CIndoor Unit1. Titanium Apatite Photocatalytic Air-Purifying Filter:2. Air outlet3. Display4

Strona 45 - SiBE12-816_D Indoor Unit

SiBE12-816_D RA Indoor UnitOperation Manual 128 Remote Controller 156234<ARC452A1>7811121315<Open the lid>91014161. Signal transmitter:•

Strona 46 - Indoor Unit SiBE12-816_D

Functions SiBE12-816_D3 List of FunctionsCategory FunctionsFLKS25/35/50BAVMBFDKS25/35EAVMBFDKS50CVMBCategory FunctionsFLKS25/35/50BAVMBFDKS25/35EAVMBF

Strona 47

RA Indoor Unit SiBE12-816_D129 Operation Manual2.2.3 AUTO · DRY · COOL · HEAT · FAN OperationAUTO · DRY · COOL · HEAT · FAN Operation To start opera

Strona 48

SiBE12-816_D RA Indoor UnitOperation Manual 130 To change the airflow rate setting5. Press “FAN setting button”.• Indoor unit quiet operationWhen

Strona 49

RA Indoor Unit SiBE12-816_D131 Operation Manual2.2.4 Adjusting the Airflow DirectionFTXS20/25/35/42/50G2V1B, FTXS20/25/35/42/50J2V1BAdjusting the Airf

Strona 50 - 3EB86013-1

SiBE12-816_D RA Indoor UnitOperation Manual 132 To start 3-D Airflow To cancel 3-D Airflow2. 4. Press either the “SWING button ” or the “SWI

Strona 51 - 1.2 Floor Standing Type

RA Indoor Unit SiBE12-816_D133 Operation ManualFVXS25/35/50FV1B2. When the flap has reached the desired position, press “SWING button ” once more.

Strona 52 - PCB (2): Control PCB

SiBE12-816_D RA Indoor UnitOperation Manual 134Airflow Airflow selectionCAUTION Operating mode• Make airflow selection according to what suits you.•

Strona 53 - 1.3.1 FLK(X)S25/35/50BAVMB

RA Indoor Unit SiBE12-816_D135 Operation Manual2.2.5 COMFORT AIRFLOW and INTELLIGENT EYE Operation To start operation To cancel operation• Press

Strona 54 - PCB (2): Power Supply PCB

SiBE12-816_D RA Indoor UnitOperation Manual 136Notes on “COMFORT AIRFLOW Operation” Notes on “INTELLIGENT EYE Operation” • The INTELLIGENT EYE sensor

Strona 55 - 1.4 Duct Connected Type

RA Indoor Unit SiBE12-816_D137 Operation ManualNotes on “INTELLIGENT EYE Operation” “INTELLIGENT EYE” is useful for Energy Saving CAUTION COMFORT AIRF

Strona 56 - PCB (2): Display PCB

SiBE12-816_D RA Indoor UnitOperation Manual 1382.2.6 POWERFUL OperationPOWERFUL Operation1. Press “POWERFUL button”.NOTE 1, 2POWERFUL operation quick

Strona 57 - 1.5.1 FFQ25/35/50/60B8V1B

SiBE12-816_D FunctionsList of Functions 4Category FunctionsFFQ25/35/50B8V1B2MKS40/50GV1B2MKS40/50G2V1BCategory FunctionsFFQ25/35/50B8V1B2MKS40/50GV1B2

Strona 58 - PCB Detail [A1P]: Control PCB

RA Indoor Unit SiBE12-816_D139 Operation Manual2.2.7 OUTDOOR UNIT QUIET OperationOUTDOOR UNIT QUIET Operation1. Press “QUIET button”.2. Press “QUIET

Strona 59 - 2P113638-2

SiBE12-816_D RA Indoor UnitOperation Manual 1402.2.8 ECONO OperationECONO Operation1. Press “ECONO button”.• “ ” is displayed on the LCD.2. Pres

Strona 60 - 2.2.1 BRC7E530W/531W

RA Indoor Unit SiBE12-816_D141 Operation Manual2.2.9 TIMER OperationTIMER Operation•• Check that the clock is correct.If not, set the clock to the p

Strona 61 - 3. Outdoor Unit

SiBE12-816_D RA Indoor UnitOperation Manual 142 To use ON TIMER operation 1. Press “ON TIMER button”.is displayed.blinks.2.3.4. Press “CANCEL button

Strona 62 - 50 class

RA Indoor Unit SiBE12-816_D143 Operation Manual2.2.10 WEEKLY TIMER OperationWEEKLY TIMER Operation Using in these cases of WEEKLY TIMERAn example of

Strona 63 - Function and Control

SiBE12-816_D RA Indoor UnitOperation Manual 144To use WEEKLY TIMER operation 1. Press “ button”. 2.3. Press “NEXT button”.4.Press “SELECT bu

Strona 64 - (R12321)

RA Indoor Unit SiBE12-816_D145 Operation ManualWEEKLY TIMER Operation8.9. Press “NEXT button”.10.NOTE Notes on WEEKLY TIMER operation1098Press “SELEC

Strona 65

SiBE12-816_D RA Indoor UnitOperation Manual 1461. Press “ button”.2.3.4.5. Press “COPY button”.6. Press “ button” to complete the se

Strona 66 - 55 Function and Control

RA Indoor Unit SiBE12-816_D147 Operation ManualWEEKLY TIMER Operation Confirming a reservation • The reservation can be confirmed.1.Press “

Strona 67 - 1.4 Airflow Direction Control

SiBE12-816_D RA Indoor UnitOperation Manual 1482.2.11 Note for Multi SystemNote for Multi System〈〈 What is a “Multi System”? 〉〉This system has one out

Strona 68 - (R13554)

Functions SiBE12-816_D5 List of Functions1.2 Heat PumpCategory FunctionsFTXG25/35EV1BW(S)CTXG50EV1BW(S)Category FunctionsFTXG25/35EV1BW(S)CTXG50EV1BW(

Strona 69

RA Indoor Unit SiBE12-816_D149 Operation Manual2.3 FTXG-E, CTXG-E, FLK(X)S, FDK(X)S Series - ARC433B41, B67, B68, B69, B762.3.1 Manual Contents and Re

Strona 70 - (R11581)

SiBE12-816_D RA Indoor UnitOperation Manual 1502.3.2 Remote ControllerFTXG25/35EV1BW(S), CTXG50EV1BW(S)1. Signal transmitter:• It sends signals to the

Strona 71 - 1.7 Automatic Operation

RA Indoor Unit SiBE12-816_D151 Operation ManualFLK(X)S25/35/50BAVMB1. Signal transmitter:• It sends signals to the indoor unit.2. Display:• It display

Strona 72 - (R12391)

SiBE12-816_D RA Indoor UnitOperation Manual 152FDK(X)S25/35EAVMB, FDK(X)S50CVMB1. Signal transmitter:• It sends signals to the indoor unit.2. Display:

Strona 73 - (R12392)

RA Indoor Unit SiBE12-816_D153 Operation Manual2.3.3 AUTO · DRY · COOL · HEAT · FAN OperationAUTO · DRY · COOL · HEAT · FAN Operation To start operat

Strona 74 - 1.9 NIGHT SET Mode

SiBE12-816_D RA Indoor UnitOperation Manual 154 To change the air flow rate setting5. Press “FAN setting button”.NOTEDRY mode AUTO or COOL or HEAT

Strona 75 - 1.10 ECONO Operation

RA Indoor Unit SiBE12-816_D155 Operation Manual2.3.4 Adjusting the Airflow DirectionFTXG25/35EV1BW(S), CTXG50EV1BW(S)Adjusting the Air Flow DirectionY

Strona 76 - 1.11 HOME LEAVE Operation

SiBE12-816_D RA Indoor UnitOperation Manual 156 To start COMFORT AIRFLOW operation5. Press “COMFORT AIRFLOW button”.• The flap orientation will chang

Strona 77 - (R12276)

RA Indoor Unit SiBE12-816_D157 Operation ManualFLK(X)S25/35/50BAVMBAdjusting the Airflow DirectionYou can adjust the air flow direction to increase yo

Strona 78 - (R12183)

SiBE12-816_D RA Indoor UnitOperation Manual 158 To adjust the vertical blades (louvers)• When adjusting the louver, use a robust and stable stool and

Strona 79 - Function and Control 68

SiBE12-816_D FunctionsList of Functions 6Category FunctionsFTXG25/35JV1BW(S)CTXG50JV1BW(S)Category FunctionsFTXG25/35JV1BW(S)CTXG50JV1BW(S)Basic Funct

Strona 80

RA Indoor Unit SiBE12-816_D159 Operation Manual2.3.5 POWERFUL OperationPOWERFUL Operation1. Press “POWERFUL button”.• “ ” disappears from the L

Strona 81 - Function and Control 70

SiBE12-816_D RA Indoor UnitOperation Manual 1602.3.6 OUTDOOR UNIT QUIET OperationOUTDOOR UNIT QUIET Operation1. Press “QUIET button”.• “ ” is d

Strona 82 - 1.15 Other Functions

RA Indoor Unit SiBE12-816_D161 Operation Manual2.3.7 HOME LEAVE OperationHOME LEAVE OperationHOME LEAVE operation is a function which allows you to re

Strona 83 - 1.15.8 WEEKLY TIMER Operation

SiBE12-816_D RA Indoor UnitOperation Manual 162 What’s the HOME LEAVE operation?Is there a set temperature and air flow rate which is most comfortabl

Strona 84 - 2.1 Drain Pump Control

RA Indoor Unit SiBE12-816_D163 Operation Manual2.3.8 INTELLIGENT EYE OperationINTELLIGENT EYE Operation“INTELLIGENT EYE” is the infrared sensor which

Strona 85 - Remote Controller:

SiBE12-816_D RA Indoor UnitOperation Manual 164“INTELLIGENT EYE” is useful for Energy Saving Energy saving operation• Change the temperature –2°C in

Strona 86 - (R12938)

RA Indoor Unit SiBE12-816_D165 Operation Manual2.3.9 TIMER OperationTIMER Operation1. Press “OFF TIMER button”.is displayed.blinks.3. Press “OFF TIM

Strona 87 - (R12939)

SiBE12-816_D RA Indoor UnitOperation Manual 166 To use ON TIMER operation1. Press “ON TIMER button”.is displayed.blinks.3. Press “ON TIMER button

Strona 88 - 2.3 Freeze Prevention Control

RA Indoor Unit SiBE12-816_D167 Operation Manual2.3.10 Note for Multi SystemNote for Multi System〈〈 What is a “Multi System”? 〉〉This system has one out

Strona 89 - (R12941)

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 1683. SA Indoor Unit - FFQ Series3.1 BRC1D5281129325221110373527261214173424520 211816 13 15

Strona 90 - 3. Function of Thermistor

Functions SiBE12-816_D7 List of FunctionsCategory FunctionsFTXS20/25/35/42/50G2V1BFVXS25/35/50FV1BCategory FunctionsFTXS20/25/35/42/50G2V1BFVXS25/35/5

Strona 91 - Function and Control 80

SA Indoor Unit - FFQ Series SiBE12-816_D169 Operation Manual2Start5s5s5s+5s5sEnd

Strona 92 - 4. Control Specification

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 170Operation manual1BRC1D528Remote controller4PW23717-1WARNINGContentspage1. Features and fun

Strona 93

SA Indoor Unit - FFQ Series SiBE12-816_D171 Operation ManualBRC1D528Remote controller4PW23717-1Operation manual256LEAVE HOME2.1 ON/OFF BUTTON Press th

Strona 94 - 4.2 Frequency Control

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 172Operation manual3BRC1D528Remote controller4PW23717-112 MAXTEMPERATURE IMUM SET 13 MINIMUM

Strona 95

SA Indoor Unit - FFQ Series SiBE12-816_D173 Operation ManualBRC1D528Remote controller4PW23717-1Operation manual430 SCHEDULE TIMER BUTTON This button e

Strona 96 - 85 Function and Control

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 174 Operation manual5BRC1D528Remote controller4PW23717-14. Description of the operation modes

Strona 97 - 4.3.4 3-Minute Standby

SA Indoor Unit - FFQ Series SiBE12-816_D175 Operation ManualBRC1D528Remote controller4PW23717-1Operation manual6User adjustable parameters:• Fan speed

Strona 98 - (R14062)

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 176Operation manual7BRC1D528Remote controller4PW23717-1ADDITIONAL FEATURES OF THE CONTROLLER1

Strona 99 - 4.5 Input Current Control

SA Indoor Unit - FFQ Series SiBE12-816_D177 Operation ManualBRC1D528Remote controller4PW23717-1Operation manual8What can the schedule timer do?,The sc

Strona 100 - 4.8 Outdoor Fan Control

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 178Operation manual9BRC1D528Remote controller4PW23717-1The process described above is now res

Strona 101 - (R12739)

SiBE12-816_D FunctionsList of Functions 8Category FunctionsFLXS25/35/50BAVMBFDXS25/35EAVMBFDXS50CVMBCategory FunctionsFLXS25/35/50BAVMBFDXS25/35EAVMBF

Strona 102 - 91 Function and Control

SA Indoor Unit - FFQ Series SiBE12-816_D179 Operation ManualBRC1D528Remote controller4PW23717-1Operation manual106. Programming the schedule timerWhat

Strona 103 - (R14236)

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 18011BRC1D528Remote controller4PW23717-11••••••••ProgrammingTHE SCHEDULE TIMER IS PROGRAMMED

Strona 104 - 93 Function and Control

SA Indoor Unit - FFQ Series SiBE12-816_D181 Operation ManualBRC1D528Remote controller4PW23717-11212If the action and the corresponding time are correc

Strona 105 - Function and Control 94

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 18213BRC1D528Remote controller4PW23717-13 47. MaintenanceThe remote controller does not need

Strona 106 - 4.12 Malfunctions

SA Indoor Unit - FFQ Series SiBE12-816_D183 Operation Manual3.2 BRC7E530W/531W[1]1-11-28101311121514161791346257124251-31 22120 22231918COOL/HEAT CHAN

Strona 107 - Function and Control 96

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 184English 42.123This display shows the set temperature.45Refer to page 9.6The display shows

Strona 108 - 4.12.4 Anti-icing Control

SA Indoor Unit - FFQ Series SiBE12-816_D185 Operation Manual5 English19RECEIVER20OPERATING INDICATOR LAMP (Red)21TIMER INDICATOR LAMP (Green)This lamp

Strona 109 - Operation Manual

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 186English 6How to put the dry batteries(1)(2)(3) Close the coverWhen to change batteriesSlid

Strona 110 - 1. System Configuration

SA Indoor Unit - FFQ Series SiBE12-816_D187 Operation Manual7 EnglishVRV System Refer to figure 1 on page [1] • • • Operate in the following order.• •

Strona 111 - Name of Parts

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 188English 8• (2)ON/OFFPress ON/OFF buttonNOTE• • • • 2• •TEMPERATURE SETTING In case of au

Strona 112 - Outdoor Unit

SiBE12-816_Di Table of ContentsInverter Multi for 2 RoomsG-SerieszCooling OnlyOutdoor Unit Indoor Unit2MKS40GV1B FTXS20G2V1B FVXS25FV1B2MKS40G2V1B FTX

Strona 113

Functions SiBE12-816_D9 List of FunctionsCategory FunctionsFFQ25/35/50B8V1B2MXS40/50GV1B2MXS40/50G2V1BCategory FunctionsFFQ25/35/50B8V1B2MXS40/50GV1B2

Strona 114 -  Open the front cover

SA Indoor Unit - FFQ Series SiBE12-816_D189 Operation Manual9 EnglishFAN SPEED CONTROLPress FAN SPEED CONTROL button.High or Low fan speed can be sele

Strona 115 - FAN Operation

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 190English 10The display flashes.PROGRAMMING TIMETIMER RESERVEPress the TIMER RESERVE button.

Strona 116 - Press

SA Indoor Unit - FFQ Series SiBE12-816_D191 Operation Manual11 English For Heat recovery system• Operate in the following order.Outdoor unitIndoor un

Strona 117 - Press

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 192English 12[STOP] Group control systemAll indoor units are equally set. Two remote contro

Strona 118 - Press

SA Indoor Unit - FFQ Series SiBE12-816_D193 Operation Manual13 EnglishNumber of beeps3 short beeps ...1 short beep ...1 long beep... Normal s

Strona 119 - COMFORT AIRFLOW Operation

SiBE12-816_D SA Indoor Unit - FFQ SeriesOperation Manual 194English 14II. IN CASE BESIDES EMERGENCY STOP1. The unit does not operate at all.• • • 2.•

Strona 120 - INTELLIGENT EYE Operation

SiBE12-816_D195 Service DiagnosisPart 6Service Diagnosis1. Troubleshooting with LED ...

Strona 121

SiBE12-816_DService Diagnosis 1967.11 Thermistor or Related Abnormality (Outdoor Unit)...2477.12 Electrical Box Temperatur

Strona 122 - POWERFUL Operation

Troubleshooting with LED SiBE12-816_D197 Service Diagnosis1. Troubleshooting with LED1.1 Indoor UnitOperation Lamp The operation lamp blinks when any

Strona 123 - Operation

SiBE12-816_D Troubleshooting with LEDService Diagnosis 198BRC7E530W/531WIn case of wireless remote controller, a signal receiver PCB and a display PCB

Strona 124 - ECONO Operation

SiBE12-816_DSpecifications 10Part 2Specifications1. Specifications ...

Strona 125 - OFF TIMER Operation

Problem Symptoms and Measures SiBE12-816_D199 Service Diagnosis2. Problem Symptoms and MeasuresProblem Symptom Check Item Details of MeasureReference

Strona 126 - ON TIMER Operation

SiBE12-816_D Service Check FunctionService Diagnosis 2003. Service Check Function3.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series3.1.

Strona 127 - WEEKLY TIMER Operation

Service Check Function SiBE12-816_D201 Service DiagnosisCheck Method 21. Press the center of the Temp button and the Mode button at the same time.“5C”

Strona 128 - Setting mode

SiBE12-816_D Service Check FunctionService Diagnosis 2026. Press the Mode button.The figure of the one’s place blinks.7. Press the Temp ▲ or ▼ button

Strona 129

Service Check Function SiBE12-816_D203 Service Diagnosis3.1.2 ARC452 Series Remote ControllerCheck Method 1 1. When the timer cancel button is held do

Strona 130 - 25˚C 27˚C

SiBE12-816_D Service Check FunctionService Diagnosis 204Check Method 21. Press the 3 buttons (TEMP▲, TEMP▼, MODE) simultaneously to enter the diagnosi

Strona 131

Service Check Function SiBE12-816_D205 Service Diagnosis5. Press the TEMP▲ or ▼ button and change the figure until you hear the sound of “beep”.6. Dia

Strona 132 - 3P255639-1

SiBE12-816_D Service Check FunctionService Diagnosis 2063.1.3 ARC433 Series Remote ControllerCheck Method 1 1. When the timer cancel button is held do

Strona 133 - Operation Manual 122

Service Check Function SiBE12-816_D207 Service DiagnosisCheck Method 21. Press the center of the TEMP button and the MODE button simultaneously to ent

Strona 134 - Names of parts

SiBE12-816_D Service Check FunctionService Diagnosis 2085. Press the TEMP▲ or ▼ button and change the figure until you hear the sound of “beep”.6. Dia

Strona 135 - Indoor Unit

Specifications SiBE12-816_D11 Specifications1. Specifications1.1 Cooling Only - Indoor UnitWall Mounted Type50 Hz, 220 - 230 - 240 VModel FTXS20G2V1B

Strona 136 -  Remote Controller

Service Check Function SiBE12-816_D209 Service Diagnosis3.2 SA Indoor Unit - FFQ Series3.2.1 Relations between ModesThe following modes can be selecte

Strona 137

SiBE12-816_D Service Check FunctionService Diagnosis 2103.2.3 BRC7E530W/531WTo find the error code, proceed as follows:Step Action1 Press the [Inspect

Strona 138 - Indoor Unit

Service Check Function SiBE12-816_D211 Service Diagnosis3 Press the MODE button. The left “0” (upper digit) indication of the error code blinks.4 Pres

Strona 139 -  Remote Controller

SiBE12-816_D Service Check FunctionService Diagnosis 2125 Press the MODE button. The right “0” (lower digit) indication of the error code blinks.6 Pre

Strona 140 -  To stop operation

Code Indication on Remote Controller SiBE12-816_D213 Service Diagnosis4. Code Indication on Remote Controller4.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS,

Strona 141 - Operation Manual 130

SiBE12-816_D Code Indication on Remote ControllerService Diagnosis 2144.3 Outdoor Unit★: Displayed only when system-down occurs.Error Codes Descriptio

Strona 142 -  To adjust the vertical

Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series SiBE12-816_D215 Service Diagnosis5. Troubleshooting for RA Indoor Un

Strona 143 -  COMFORT AIRFLOW operation

SiBE12-816_D Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S SeriesService Diagnosis 2165.2 Freeze-up Protection Control or

Strona 144 -  To adjust the vertical

Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series SiBE12-816_D217 Service DiagnosisTroubleshootingCheck No.01Refer to

Strona 145 -  Airflow selection

SiBE12-816_D Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S SeriesService Diagnosis 2185.3 Fan Motor or Related Abnormalit

Strona 146 - COMFORT AIRFLOW and

SiBE12-816_D SpecificationsSpecifications 1250 Hz, 220 - 230 - 240 VModel FTXS50G2V1BRated Capacity 5.0 kW ClassFront Panel Color WhiteAirflow RatesHm

Strona 147 - Operation Manual 136

Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series SiBE12-816_D219 Service Diagnosis5.3.2 DC Motor (Wall Mounted Type,

Strona 148

SiBE12-816_D Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S SeriesService Diagnosis 220TroubleshootingCheck No.02Refer to

Strona 149

Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series SiBE12-816_D221 Service Diagnosis5.4 Thermistor or Related Abnormali

Strona 150 - OUTDOOR UNIT QUIET Operation

SiBE12-816_D Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S SeriesService Diagnosis 2225.5 Front Panel Open / Close Fault

Strona 151

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D223 Service Diagnosis6. Troubleshooting for SA Indoor Unit - FFQ Series6.1 Indoor Unit PCB

Strona 152 - TIMER Operation

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 2246.2 Drain Water Level System AbnormalityRemote Controller DisplayA3Me

Strona 153 -  To use ON TIMER

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D225 Service DiagnosisTroubleshootingNote: If "A3" is detected by the indoor unit

Strona 154

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 2266.3 Fan Motor or Related AbnormalityRemote Controller DisplayA6Method

Strona 155 - Setting Displays

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D227 Service Diagnosis6.4 Drain System AbnormalityRemote Controller DisplayAFMethod of Malf

Strona 156

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 2286.5 Thermistor or Related AbnormalityRemote Controller DisplayThe tab

Strona 157 - ON OFF ON OFF

Specifications SiBE12-816_D13 Specifications50 Hz, 220 - 230 - 240 VModel FTXS35J2V1B FTXS42J2V1BRated Capacity 3.5 kW Class 4.2 kW ClassFront Panel C

Strona 158

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D229 Service DiagnosisTroubleshootingIs it connected properly?Is it normal?Is the contact O

Strona 159 - Note for Multi System

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 2306.6 Remote Controller Thermistor AbnormalityRemote Controller Display

Strona 160 - 149 Operation Manual

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D231 Service Diagnosis6.7 Signal Transmission Error (between Indoor Unit and Remote Control

Strona 161

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 2326.8 Signal Transmission Error (between MAIN Remote Controller and SUB

Strona 162 - < ARC433B67, B68 >

Troubleshooting for SA Indoor Unit - FFQ Series SiBE12-816_D233 Service Diagnosis6.9 Field Setting AbnormalityRemote Controller DisplayUAMethod of Mal

Strona 163

SiBE12-816_D Troubleshooting for SA Indoor Unit - FFQ SeriesService Diagnosis 234TroubleshootingConnect them correctly.Replace the indoor unit PCB.Nor

Strona 164 -  To stop operation

Troubleshooting for Outdoor Unit SiBE12-816_D235 Service Diagnosis7. Troubleshooting for Outdoor Unit7.1 Anti-icing Control for Indoor UnitRemote Cont

Strona 165 - Operation Manual 154

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 236TroubleshootingCheck No.01Refer to P.261Check No.12Refer to P.263(R14407)CautionYESN

Strona 166

Troubleshooting for Outdoor Unit SiBE12-816_D237 Service Diagnosis7.2 OL Activation (Compressor Overload)Remote Controller DisplayE5Method of Malfunct

Strona 167

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2387.3 Compressor LockRemote Controller DisplayE6Method of Malfunction DetectionA compr

Strona 168 -  To adjust the horizontal

SiBE12-816_D SpecificationsSpecifications 14Floor Standing Type50 Hz, 220 - 230 - 240 VModel FVXS25FV1B FVXS35FV1BRated Capacity 2.5 kW Class 3.5 kW C

Strona 169 - (louvers)

Troubleshooting for Outdoor Unit SiBE12-816_D239 Service Diagnosis7.4 DC Fan LockRemote Controller DisplayE7Method of Malfunction DetectionAn error is

Strona 170

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2407.5 Input Overcurrent DetectionRemote Controller DisplayE8Method of Malfunction Dete

Strona 171

Troubleshooting for Outdoor Unit SiBE12-816_D241 Service Diagnosis7.6 Discharge Pipe Temperature ControlRemote Controller DisplayF3Method of Malfuncti

Strona 172 - HOME LEAVE Operation

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2427.7 High Pressure Control in CoolingRemote Controller DisplayF6Method of Malfunction

Strona 173 -  Useful in these cases

Troubleshooting for Outdoor Unit SiBE12-816_D243 Service Diagnosis7.8 Compressor Sensor System AbnormalityRemote Controller DisplayH0Method of Malfunc

Strona 174

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2447.9 Position Sensor AbnormalityRemote Controller DisplayH6Method of Malfunction Dete

Strona 175 - CAUTION

Troubleshooting for Outdoor Unit SiBE12-816_D245 Service DiagnosisTroubleshootingCheck No.15Refer to P.266Check No.18Refer to P.269Check No.20Refer to

Strona 176

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2467.10 DC Voltage / Current Sensor AbnormalityRemote Controller DisplayH8Method of Mal

Strona 177 - Combined

Troubleshooting for Outdoor Unit SiBE12-816_D247 Service Diagnosis7.11 Thermistor or Related Abnormality (Outdoor Unit)Remote Controller DisplayH9, J3

Strona 178 - Outdoor

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 248Troubleshooting In case of “H9” “J3” “J6” “J8” “J9”Check No.01Refer to P.261H9 : Out

Strona 179 - 3.1 BRC1D528

Specifications SiBE12-816_D15 SpecificationsFloor / Ceiling Suspended Dual Type50 Hz, 220 - 230 - 240 VModel FLKS25BAVMB FLKS35BAVMBRated Capacity 2.5

Strona 180 - 169 Operation Manual

Troubleshooting for Outdoor Unit SiBE12-816_D249 Service Diagnosis7.12 Electrical Box Temperature RiseRemote Controller DisplayL3Method of Malfunction

Strona 181 - 1. Features and functions

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2507.13 Radiation Fin Temperature RiseRemote Controller DisplayL4Method of Malfunction

Strona 182 - 171 Operation Manual

Troubleshooting for Outdoor Unit SiBE12-816_D251 Service DiagnosisTroubleshootingCheck No.17Refer to P.269Check No.19Refer to P.270Note: Refer to “App

Strona 183 - Operation Manual 172

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2527.14 Output Overcurrent DetectionRemote Controller DisplayL5Method of Malfunction De

Strona 184 - 3. Setting up the controller

Troubleshooting for Outdoor Unit SiBE12-816_D253 Service DiagnosisTroubleshootingCheck No.15Refer to P.266Check No.17Refer to P.269Check No.18Refer to

Strona 185 - Manual operation

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2547.15 Refrigerant ShortageRemote Controller DisplayU0Method of Malfunction DetectionR

Strona 186 - 175 Operation Manual

Troubleshooting for Outdoor Unit SiBE12-816_D255 Service DiagnosisTroubleshootingCheck No.01Refer to P.261Check No.12Refer to P.263(R14419)CautionYESN

Strona 187 - Schedule timer operation

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2567.16 Low-voltage Detection or Over-voltage DetectionRemote Controller DisplayU2Metho

Strona 188 - 177 Operation Manual

Troubleshooting for Outdoor Unit SiBE12-816_D257 Service Diagnosis7.17 Outdoor Unit PCB Abnormality or Signal Transmission ErrorRemote Controller Disp

Strona 189 - Operation Manual 178

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 258TroubleshootingYES(R14223)Check indoor unit also, because a communication circuit fa

Strona 190 - 179 Operation Manual

SiBE12-816_D SpecificationsSpecifications 16Duct Connected Type50 Hz, 230 VModel FDKS25EAVMB FDKS35EAVMBRated Capacity 2.5 kW Class 3.5 kW ClassFront

Strona 191 - Programming

Troubleshooting for Outdoor Unit SiBE12-816_D259 Service DiagnosisCheck No.11Refer to P.262NO(R14420)YESNOYESYESNONOYESCheck wrong wiring, insulation

Strona 192 - 181 Operation Manual

SiBE12-816_D Troubleshooting for Outdoor UnitService Diagnosis 2607.18 Unspecified Voltage (between Indoor Unit and Outdoor Unit) / Anti-icing control

Strona 193 - 4PW23717-1

Check SiBE12-816_D261 Service Diagnosis8. Check8.1 Thermistor Resistance CheckCheck No.01 Disconnect the connectors of the thermistors from the PCB, a

Strona 194 - 3.2 BRC7E530W/531W

SiBE12-816_D CheckService Diagnosis 2628.2 Fan Motor Connector Output CheckCheck No.02 1. Check the connection of connector.2. Check motor power suppl

Strona 195 - SECTION (Fig. 1, 2)

Check SiBE12-816_D263 Service Diagnosis8.5 Electronic Expansion Valve CheckCheck No.12 Conduct the followings to check the electronic expansion valve

Strona 196 - CONTROLLER

SiBE12-816_D CheckService Diagnosis 2648.6 Four Way Valve Performance CheckCheck No.13(R11903)NOYESYESNOTurn off the power and turn it on again.Discon

Strona 197 - 4. OPERATION RANGE

Check SiBE12-816_D265 Service Diagnosis8.7 Inverter Unit Refrigerant System CheckCheck No.14Refrigerant system checkCheck for refrigerant leakage. S

Strona 198 - 5. OPERATION PROCEDURE

SiBE12-816_D CheckService Diagnosis 2668.8 “Inverter Checker” CheckCheck No.15CharacteristicsIf abnormal stop occurs due to compressor startup failur

Strona 199 - Operation Manual 188

Check SiBE12-816_D267 Service DiagnosisFTXG-E, CTXG-E, FTXS, FVXS, FLK(X)S, FDK(X)S Series1) Turn the power on.2) Select FAN operation with the [MODE]

Strona 200 - 189 Operation Manual

SiBE12-816_D CheckService Diagnosis 2688.9 Rotating Pulse Input on the Outdoor Unit PCB CheckCheck No.16 <Outdoor fan motor>Make sure that the v

Strona 201 - Indoor unit

Specifications SiBE12-816_D17 SpecificationsCeiling Mounted Cassette Type50 Hz, 230 V★1 ( ) : dimension including control boxModel FFQ25B8V1B FFQ35

Strona 202 - 191 Operation Manual

Check SiBE12-816_D269 Service Diagnosis8.10 Installation Condition CheckCheck No.178.11 Discharge Pressure CheckCheck No.18Installation condition chec

Strona 203 - REMOTE CONTROLLER CONTROL

SiBE12-816_D CheckService Diagnosis 2708.12 Outdoor Unit Fan System CheckCheck No.19 DC motor8.13 Main Circuit Short CheckCheck No.20Note: Check to ma

Strona 204 - 193 Operation Manual

Check SiBE12-816_D271 Service Diagnosis8.14 Power Module CheckCheck No.22Note: Check to make sure that the voltage between (+) and (–) of the diode br

Strona 205 - 3P107422-1S

SiBE12-816_DRemoval Procedure 272Part 7Removal Procedure1. Outdoor Unit...

Strona 206 - Service Diagnosis

Outdoor Unit SiBE12-816_D273 Removal Procedure1. Outdoor UnitNote: The illustrations are for heat pump models as representative.1.1 Removal of Outer P

Strona 207 - Service Diagnosis 196

SiBE12-816_D Outdoor UnitRemoval Procedure 2744Remove the 4 screws and remove the discharge grille.When reassembling, make sure to fit the 4 hooks.5R

Strona 208 - Operation lamp (green)

Outdoor Unit SiBE12-816_D275 Removal Procedure1.2 Removal of Electrical BoxProcedure Warning Be sure to wait for 10 minutes or more after turning off

Strona 209 - (R14422)

SiBE12-816_D Outdoor UnitRemoval Procedure 2763Disconnect the connector for the fan motor [S70].4Release the fan motor lead wire.5Disconnect the conne

Strona 210

Outdoor Unit SiBE12-816_D277 Removal Procedure7Disconnect the connectors [S20], [S21], [S80].[S20]: electronic expansion valve coil for room A (white)

Strona 211 - Timer cancel button

SiBE12-816_D Outdoor UnitRemoval Procedure 27811Disconnect the connector for the thermistors [S90].[S90]: thermistors (outdoor temperature, outdoor he

Strona 212 - (R11671)

SiBE12-816_D SpecificationsSpecifications 181.2 Cooling Only - Outdoor Unit50 Hz, 220 - 240 V Note:1. The data are based on the conditions shown in th

Strona 213 - (R11673)

Outdoor Unit SiBE12-816_D279 Removal Procedure15Lift and remove the electrical box.StepProcedure Points(R12537)

Strona 214 - (R13820)

SiBE12-816_D Outdoor UnitRemoval Procedure 2801.3 Removal of PCBProcedure Warning Be sure to wait for 10 minutes or more after turning off all power s

Strona 215 - Service Diagnosis 204

Outdoor Unit SiBE12-816_D281 Removal Procedure4Release the earth wire from the hook.5Remove the 2 screws and detach the clip to remove the radiation s

Strona 216 - 205 Service Diagnosis

SiBE12-816_D Outdoor UnitRemoval Procedure 2826Cut the clamp and release the wire harnesses.7Remove the 7 screws in total to remove the PCB.8Lift up t

Strona 217 - (R14221)

Outdoor Unit SiBE12-816_D283 Removal Procedure9Release the lead wires from the hooks and remove the terminal boards.10Lift up the PCB.11Remove the PCB

Strona 218 - 207 Service Diagnosis

SiBE12-816_D Outdoor UnitRemoval Procedure 28412Disconnect the connectors from the terminal board.★This illustration is for 40 class model as represen

Strona 219 - Service Diagnosis 208

Outdoor Unit SiBE12-816_D285 Removal Procedure1.4 Removal of Sound BlanketsProcedure Warning Be sure to wait for 10 minutes or more after turning off

Strona 220 - 3.2.2 BRC1D528

SiBE12-816_D Outdoor UnitRemoval Procedure 2863. Remove the sound blankets.1Release the strings, open the sound blanket (outer) and pull it out.2Remov

Strona 221 - (R14424)

Outdoor Unit SiBE12-816_D287 Removal Procedure1.5 Removal of Outdoor Fan / Fan MotorProcedure Warning Be sure to wait for 10 minutes or more after tur

Strona 222 - (R14395)

SiBE12-816_D Outdoor UnitRemoval Procedure 2882Release the fan motor lead wire.3Remove the screw of the fan motor fixing frame.4Remove the fan motor f

Strona 223 - (R14398)

SiBE12-816_DTable of Contents ii1. Introduction ... vi1.1 Saf

Strona 224 - FDK(X)S Series

Specifications SiBE12-816_D19 Specifications50 Hz, 220 - 240 V Note:1. The data are based on the conditions shown in the table below.Model 2MKS50GV1B

Strona 225 - 4.3 Outdoor Unit

Outdoor Unit SiBE12-816_D289 Removal Procedure5Turn the fan motor fixing frame backward and open the 2 hooks of the fan motor lead wire.6Release the f

Strona 226 - (R11930)

SiBE12-816_D Outdoor UnitRemoval Procedure 2901.6 Removal of ThermistorsProcedure Warning Be sure to wait for 10 minutes or more after turning off all

Strona 227 - Service Diagnosis 216

Outdoor Unit SiBE12-816_D291 Removal Procedure2Cut the clamp.3Peel the putty and remove the thermistors. [S91] : gas pipe thermistorroom A (black)room

Strona 228 - Refer to P.261

SiBE12-816_D Outdoor UnitRemoval Procedure 2921.7 Removal of Four Way Valve / Electronic Expansion ValvesProcedure Warning Be sure to wait for 10 minu

Strona 229 - Service Diagnosis 218

Outdoor Unit SiBE12-816_D293 Removal ProcedureBefore working, make sure that the refrigerant gas is empty in the circuit.Be sure to apply nitrogen r

Strona 230 - 219 Service Diagnosis

SiBE12-816_D Outdoor UnitRemoval Procedure 2944Heat up the brazed parts.Pull the pipe with pliers and disconnect.Note:Do not use a metal saw for cutt

Strona 231 - Refer to P.262

Outdoor Unit SiBE12-816_D295 Removal Procedure1.8 Removal of CompressorProcedure Warning Be sure to wait for 10 minutes or more after turning off all

Strona 232 - 221 Service Diagnosis

SiBE12-816_D Outdoor UnitRemoval Procedure 2964Remove the 2 nuts of the compressor. WarningBe careful not to get yourself burnt with the pipes and oth

Strona 233 - Service Diagnosis 222

SiBE12-816_D297 Trial Operation and Field SettingsPart 8Trial Operation andField Settings1. Pump Down Operation...

Strona 234 - 223 Service Diagnosis

SiBE12-816_D Pump Down OperationTrial Operation and Field Settings 2981. Pump Down OperationOutline In order to protect the environment, be sure to co

Strona 235 - Service Diagnosis 224

SiBE12-816_D SpecificationsSpecifications 201.3 Heat Pump - Indoor UnitWall Mounted Type50 Hz, 220 - 230 - 240 VModelFTXG25EV1BW FTXG25EV1BSCooling He

Strona 236 - Note: If "

Forced Cooling Operation SiBE12-816_D299 Trial Operation and Field Settings2. Forced Cooling Operationex. Wall mounted type FTXS SeriesItem Forced Coo

Strona 237 - Service Diagnosis 226

SiBE12-816_D Trial OperationTrial Operation and Field Settings 3003. Trial Operation3.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S SeriesO

Strona 238 - 6.4 Drain System Abnormality

Trial Operation SiBE12-816_D301 Trial Operation and Field SettingsARC452 Series(1) Press the ON/OFF button to turn on the system.(2) Press the both of

Strona 239 - Service Diagnosis 228

SiBE12-816_D Trial OperationTrial Operation and Field Settings 3023.2 SA Indoor Unit - FFQ Series3.2.1 CheckpointsTo carry out a trial operation, chec

Strona 240

Field Settings SiBE12-816_D303 Trial Operation and Field Settings4. Field Settings4.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S, FDK(X)S Series4.1

Strona 241 - CJ" displayed on

SiBE12-816_D Field SettingsTrial Operation and Field Settings 304FTXS-G, FTXS-J Series< Floor Standing Type>1) Remove the front grille.2) Lift t

Strona 242 - 231 Service Diagnosis

Field Settings SiBE12-816_D305 Trial Operation and Field Settings< Floor / Ceiling Suspended Dual Type >Cut the jumper JA on PCB.< Duct Conn

Strona 243 - Service Diagnosis 232

SiBE12-816_D Field SettingsTrial Operation and Field Settings 3064.1.3 Jumper and Switch Settings<Floor Standing Type><Floor / Ceiling Suspen

Strona 244 - 6.9 Field Setting Abnormality

Field Settings SiBE12-816_D307 Trial Operation and Field Settings4.2 SA Indoor Unit - FFQ Series4.2.1 How to Change the Field SettingsOutline If optio

Strona 245

SiBE12-816_D Field SettingsTrial Operation and Field Settings 308Wireless remote controllerTo set the field settings, you have to change:Mode No.Fir

Strona 246 - 235 Service Diagnosis

Specifications SiBE12-816_D21 Specifications50 Hz, 220 - 230 - 240 VModelCTXG50EV1BW CTXG50EV1BSCooling Heating Cooling HeatingRated Capacity 5.0 kW C

Strona 247 - Refer to P.263

Field Settings SiBE12-816_D309 Trial Operation and Field Settings4.2.2 Overview of the Field Settings: factory settingNote: Any function that is not a

Strona 248 - 237 Service Diagnosis

SiBE12-816_D Field SettingsTrial Operation and Field Settings 3104.2.3 MAIN / SUB Setting when Using 2 Wired Remote ControllersOutline The MAIN / SUB

Strona 249 - 7.3 Compressor Lock

Field Settings SiBE12-816_D311 Trial Operation and Field Settings4.2.4 Address and MAIN / SUB Setting for Wireless Remote ControllerOutline If several

Strona 250 - 7.4 DC Fan Lock

SiBE12-816_D Field SettingsTrial Operation and Field Settings 312Wireless Remote Controller (Factory Set is “1”) 1. Hold down the “ ” button and the “

Strona 251 - Service Diagnosis 240

Field Settings SiBE12-816_D313 Trial Operation and Field SettingsAfter Setting Stick the unit No. label at the decoration panel air discharge outlet a

Strona 252 - (R14412)

SiBE12-816_D Field SettingsTrial Operation and Field Settings 3144.3 Outdoor Unit4.3.1 Jumper SettingsLocation of the jumpersJumper (on outdoor unit P

Strona 253 - Service Diagnosis 242

Application of Silicon Grease to a Power Transistor and a Diode Bridge SiBE12-816_D315 Trial Operation and Field Settings5. Application of Silicon Gre

Strona 254 - 243 Service Diagnosis

SiBE12-816_DAppendix 316Part 9Appendix1. Piping Diagrams...3171.1 Indoo

Strona 255 - Service Diagnosis 244

Piping Diagrams SiBE12-816_D317 Appendix1. Piping Diagrams1.1 Indoor Unit1.1.1 Wall Mounted TypeFTXG25/35EV1BW(S) CTXG50EV1BW(S)FTXG25/35JV1BW(S) CTXG

Strona 256 - 245 Service Diagnosis

SiBE12-816_D Piping DiagramsAppendix 3181.1.2 Floor Standing TypeFTXS20/25/35/42G2V1BFTXS20/25/35/42J2V1BFTXS50G2V1BFTXS50J2V1BCROSS FLOW FAN9.5CuTREF

Strona 257 - Service Diagnosis 246

SiBE12-816_D SpecificationsSpecifications 2250 Hz, 220 - 230 - 240 VModelFTXG35JV1BW FTXG35JV1BSCooling Heating Cooling HeatingRated Capacity 3.5 kW C

Strona 258 - 247 Service Diagnosis

Piping Diagrams SiBE12-816_D319 Appendix1.1.3 Floor / Ceiling Suspended Dual TypeFLKS25/35BAVMB FLKS50BAVMBFLXS25/35BAVMB FLXS50BAVMBREFRIGERANT FLOWC

Strona 259 - Service Diagnosis 248

SiBE12-816_D Piping DiagramsAppendix 3201.1.4 Duct Connected TypeFDK(X)S25/35EAVMB, FDK(X)S50CVMB1.1.5 Ceiling Mounted Cassette TypeFFQ25/35/50B8V1BFI

Strona 260 - C ˚C and stops when it

Piping Diagrams SiBE12-816_D321 Appendix1.2 Outdoor Unit1.2.1 Cooling Only2MKS40GV1B, 2MKS40G2V1B2MKS50GV1B, 2MKS50G2V1BEVAM7.9CuT7.9CuT9.5CuTROOM A (

Strona 261

SiBE12-816_D Piping DiagramsAppendix 3221.2.2 Heat Pump2MXS40GV1B, 2MXS40G2V1B2MXS50GV1B, 2MXS50G2V1B7.9CuTEVA7.9CuTM9.5CuTMUFFLER9.5CuT9.5CuT7.0CuTHE

Strona 262 - 50 class 92.5

Wiring Diagrams SiBE12-816_D323 Appendix2. Wiring Diagrams2.1 Indoor Unit2.1.1 Wall Mounted TypeFTXG25/35EV1BW(S), CTXG50EV1BW(S)FTXG25/35JV1BW(S), CT

Strona 263 - Service Diagnosis 252

SiBE12-816_D Wiring DiagramsAppendix 324FTXS20/25/35/42/50G2V1B, FTXS20/25/35/42/50J2V1B2.1.2 Floor Standing TypeFVXS25/35/50FV1B1FU1X1MPCB1PCB3S46S49

Strona 264 - 253 Service Diagnosis

Wiring Diagrams SiBE12-816_D325 Appendix2.1.3 Floor / Ceiling Suspended Dual TypeFLK(X)S25/35/50BAVMB2.1.4 Duct Connected TypeFDK(X)S25/35EAVMB, FDK(X

Strona 265 - 7.15 Refrigerant Shortage

SiBE12-816_D Wiring DiagramsAppendix 3262.1.5 Ceiling Mounted Cassette TypeFFQ25/35/50B8V1BNOTES)TO OUTDOOR UNIT1. : TERMINALC1A3PA4PS1LX1M

Strona 266

Wiring Diagrams SiBE12-816_D327 Appendix2.2 Outdoor Unit2.2.1 Cooling Only2MKS40GV1B, 2MKS40G2V1B2MKS50GV1B, 2MKS50G2V1BDB1MRM10MRM20SA1V3DB24(ROOM-B)

Strona 267 - Service Diagnosis 256

SiBE12-816_D Wiring DiagramsAppendix 3282.2.2 Heat Pump2MXS40GV1B, 2MXS40G2V1B2MXS50GV1B, 2MXS50G2V1BV3SA1MRM10MRM20DB2DB1outdoorFIELD WIRINGL1(ROOM-B

Strona 268 - 257 Service Diagnosis

Specifications SiBE12-816_D23 Specifications50 Hz, 220 - 230 - 240 VModelFTXS20G2V1B FTXS25G2V1BCooling Heating Cooling HeatingRated Capacity 2.0 kW C

Strona 269

Revision HistoryMonth / Year Version Revised contents04/2008 SiBE12-816 –06/2010 SiBE12-816_A Addition of the wall mounted type FTXG-JV1BW(S), CTXG-JV

Strona 270 - Check No.11

Head Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 JapanTokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, To

Strona 271 - Service Diagnosis 260

SiBE12-816_D SpecificationsSpecifications 2450 Hz, 220 - 230 - 240 VModelFTXS50G2V1BCooling HeatingRated Capacity 5.0 kW ClassFront Panel Color WhiteA

Strona 272 - 8. Check

Specifications SiBE12-816_D25 SpecificationsFloor Standing Type50 Hz, 220 - 230 - 240 VModelFVXS25FV1B FVXS35FV1BCooling Heating Cooling HeatingRated

Strona 273 - 8.3 Hall IC Check

SiBE12-816_D SpecificationsSpecifications 26Floor / Ceiling Suspended Dual Type50 Hz, 220 - 230 - 240 VModelFLXS25BAVMB FLXS35BAVMBCooling Heating Coo

Strona 274 - (R14358)

Specifications SiBE12-816_D27 SpecificationsDuct Connected Type50 Hz, 230 VModelFDXS25EAVMB FDXS35EAVMBCooling Heating Cooling HeatingRated Capacity 2

Strona 275 - Check No.13

SiBE12-816_D SpecificationsSpecifications 28Ceiling Mounted Cassette Type50 Hz, 230 VNote:★1 ( ) : dimension including control boxModelFFQ25B8V1B F

Strona 276 - Check No.14

SiBE12-816_Diii Table of Contents2.3 Freeze Prevention Control ...772.4 Hot Start Co

Strona 277 - Compressor

Specifications SiBE12-816_D29 Specifications1.4 Heat Pump - Outdoor Unit50 Hz, 220 - 240 VNote:1. The data are based on the conditions shown in the ta

Strona 278

SiBE12-816_D SpecificationsSpecifications 3050 Hz, 220 - 240 VNote:1. The data are based on the conditions shown in the table below.Model2MXS50GV1B 2M

Strona 279 - Service Diagnosis 268

SiBE12-816_D31 Printed Circuit Board Connector Wiring DiagramPart 3Printed Circuit BoardConnector Wiring Diagram1. Indoor Unit...

Strona 280 - 8.11 Discharge Pressure Check

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 321. Indoor Unit1.1 Wall Mounted Type1.1.1 FTXG25/35EV1BW(S), CTXG50EV1BW(S)Con

Strona 281 - 8.13 Main Circuit Short Check

Indoor Unit SiBE12-816_D33 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Control PCBPCB (2): Signal Receiver PCBPCB (3): INTELLIGE

Strona 282 - 8.14 Power Module Check

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 341.1.2 FTXG25/35JV1BW(S), CTXG50JV1BW(S)Connectors and Other PartsPCB (1): Con

Strona 283 - Removal Procedure

Indoor Unit SiBE12-816_D35 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Control PCBS42S41S32JB JCS200H3H2FGS46S21S25LED AV1F1UH12

Strona 284 - 1. Outdoor Unit

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 36PCB (3): INTELLIGENT EYE Sensor PCBPCB (2): Signal Receiver / Display PCBS52

Strona 285 - Procedure Points

Indoor Unit SiBE12-816_D37 Printed Circuit Board Connector Wiring Diagram1.1.3 FTXS20/25/35/42/50G2V1B, FTXS20/25/35/42/50J2V1BConnectors and Other Pa

Strona 286 - 1.2 Removal of Electrical Box

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 38PCB Detail PCB (1): Control PCBV1FU1S1S41S21S47JBJAJCS46 S25LED AS32FGH1H2H32

Strona 287 - [S92] [S91]

SiBE12-816_DTable of Contents iv6. Troubleshooting for SA Indoor Unit - FFQ Series ...2236.1 Indoor Unit PCB Abnormality .

Strona 288 - Discharge pipe thermistor

Indoor Unit SiBE12-816_D39 Printed Circuit Board Connector Wiring DiagramPCB (2): Signal Receiver PCBPCB (3): Display PCBPCB (4): INTELLIGENT EYE Sens

Strona 289 - (R12536)

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 401.2 Floor Standing Type1.2.1 FVXS25/35/50FV1BConnectors and Other PartsPCB (1

Strona 290 - (R12537)

Indoor Unit SiBE12-816_D41 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Sensor PCBPCB (2): Control PCBPCB (3): Service PCB PCB (4

Strona 291 - 1.3 Removal of PCB

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 421.3 Floor / Ceiling Suspended Dual Type1.3.1 FLK(X)S25/35/50BAVMBConnectors a

Strona 292 - 281 Removal Procedure

Indoor Unit SiBE12-816_D43 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Control PCBPCB (2): Power Supply PCBPCB (3): Display PCB

Strona 293

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 441.4 Duct Connected Type1.4.1 FDK(X)S25/35EAVMB, FDK(X)S50CVMBConnectors and O

Strona 294 - Terminal board

Indoor Unit SiBE12-816_D45 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Control PCBPCB (2): Display PCBS1H2S7S26S32JCJBJAS212P13

Strona 295 - (R12566)

SiBE12-816_D Indoor UnitPrinted Circuit Board Connector Wiring Diagram 461.5 Ceiling Mounted Cassette Type1.5.1 FFQ25/35/50/60B8V1BConnectors and Othe

Strona 296 - 1.4 Removal of Sound Blankets

Indoor Unit SiBE12-816_D47 Printed Circuit Board Connector Wiring DiagramPCB Detail [A1P]: Control PCBX25AX18AX61AX36AX40AX17AX15AHAPX5AX35AX24AX60AX1

Strona 297 - Sound blanket (bottom)

SiBE12-816_D Remote ControllerPrinted Circuit Board Connector Wiring Diagram 482. Remote Controller2.1 Wired Remote Controller2.1.1 BRC1D528Connectors

Strona 298 - (R12236)

SiBE12-816_Dv Table of Contents1.2 Removal of Electrical Box ...2751.3 Removal of PCB

Strona 299 - Fan motor

Remote Controller SiBE12-816_D49 Printed Circuit Board Connector Wiring Diagram2.2 Wireless Remote Controller2.2.1 BRC7E530W/531WConnectors and Other

Strona 300 - Lead wire Outdoor fan

SiBE12-816_D Outdoor UnitPrinted Circuit Board Connector Wiring Diagram 503. Outdoor Unit3.1 2MK(X)S40/50GV1B, 2MK(X)S40/50G2V1BConnectors and Other P

Strona 301 - 1.6 Removal of Thermistors

Outdoor Unit SiBE12-816_D51 Printed Circuit Board Connector Wiring DiagramPCB Detail 40 class50 classHN2HL1EFU3FU1 FU2HR1HR2U, V, WJ3 J4 J52P190760-2S

Strona 302

SiBE12-816_DFunction and Control 52Part 4Function and Control1. Function of Indoor Unit (RA Models)...

Strona 303 - Terminal cover

Function of Indoor Unit (RA Models) SiBE12-816_D53 Function and Control1. Function of Indoor Unit (RA Models)1.1 Temperature ControlDefinitions of Tem

Strona 304

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 54Drawing of InverterThe following drawing shows a schematic view of the inverter

Strona 305 - Removal Procedure 294

Function of Indoor Unit (RA Models) SiBE12-816_D55 Function and Control1.3 Operation Starting ControlWall Mounted Type: FTXG, CTXG SeriesThe system ca

Strona 306 - 1.8 Removal of Compressor

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 561.4 Airflow Direction ControlPower-Airflow Dual FlapsThe large flaps send a lar

Strona 307

Function of Indoor Unit (RA Models) SiBE12-816_D57 Function and ControlFloor / Ceiling Suspended Dual Type3-D Airflow Wall Mounted Type: FTXS SeriesAl

Strona 308 - Field Settings

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 581.5 Fan Speed Control for Indoor UnitsOutline Phase control and fan speed contr

Strona 309 - 1. Pump Down Operation

SiBE12-816_D Introductionvi1. Introduction1.1 Safety CautionsCautions and WarningsBe sure to read the following safety cautions before conducting rep

Strona 310 - (R14226)

Function of Indoor Unit (RA Models) SiBE12-816_D59 Function and ControlCOMFORT AIRFLOW OperationWall Mounted TypeThe fan speed is controlled automati

Strona 311 - (R11676)

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 601.7 Automatic OperationOutline Automatic Cooling / Heating FunctionWhen the AUT

Strona 312 - Trial Operation SiBE12-816_D

Function of Indoor Unit (RA Models) SiBE12-816_D61 Function and Control1.8 Thermostat ControlThermostat control is based on the difference between the

Strona 313 - 3.2.2 Trial operation

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 62HeatingWall Mounted Type: FTXG-J, CTXG-J SeriesWall Mounted Type: FTXG-E, CTX

Strona 314 - 4. Field Settings

Function of Indoor Unit (RA Models) SiBE12-816_D63 Function and Control1.9 NIGHT SET ModeOutline When the OFF timer is set, the NIGHT SET Mode is auto

Strona 315 - SiBE12-816_D Field Settings

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 641.10 ECONO OperationFTXG-J, CTXG-J, FTXS, FVXS SeriesThe "ECONO operation&

Strona 316 - Field Settings SiBE12-816_D

Function of Indoor Unit (RA Models) SiBE12-816_D65 Function and Control1.11 HOME LEAVE OperationOutline FLK(X)S, FDK(X)S SeriesHOME LEAVE operation is

Strona 317

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 661.12 2-Area INTELLIGENT EYE OperationOutline Wall Mounted Type: FTXS SeriesThe

Strona 318

Function of Indoor Unit (RA Models) SiBE12-816_D67 Function and Control2. Motions (for example: in cooling)When the microcomputer does not have a sig

Strona 319 - (R14426)

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 681.13 INTELLIGENT EYE OperationOutline Wall Mounted Type: FTXG, CTXG SeriesThis

Strona 320

Introduction SiBE12-816_DviiBe sure to wear a safety helmet, gloves, and a safety belt when working at a high place (more than 2 m). Insufficient safe

Strona 321 - (R11739)

Function of Indoor Unit (RA Models) SiBE12-816_D69 Function and Control1.14 Inverter POWERFUL OperationOutline In order to exploit the cooling and hea

Strona 322 - 1 2 3 M S

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 70Brightness SettingThe brightness of the multi-colored indicator lamp can be adj

Strona 323 - (R14401)

Function of Indoor Unit (RA Models) SiBE12-816_D71 Function and Control1.15 Other Functions1.15.1 Hot-Start FunctionIn order to prevent the cold air b

Strona 324 - Decoration

SiBE12-816_D Function of Indoor Unit (RA Models)Function and Control 721.15.7 Auto-restart FunctionEven if a power failure (including one for just a m

Strona 325

Function of Indoor Unit (SA Models) SiBE12-816_D73 Function and Control2. Function of Indoor Unit (SA Models)2.1 Drain Pump Control2.1.1 When the Floa

Strona 326 - Transistor and a Diode Bridge

SiBE12-816_D Function of Indoor Unit (SA Models)Function and Control 742.1.3 When the Float Switch is Tripped During Heating Operation:During heating

Strona 327 - Appendix

Function of Indoor Unit (SA Models) SiBE12-816_D75 Function and Control2.2 Thermostat Sensor in Remote ControllerTemperature is controlled by both the

Strona 328 - 1. Piping Diagrams

SiBE12-816_D Function of Indoor Unit (SA Models)Function and Control 76Heating When heating, the hot air rises to the top of the room, resulting in th

Strona 329 - 1.1.2 Floor Standing Type

Function of Indoor Unit (SA Models) SiBE12-816_D77 Function and Control2.3 Freeze Prevention ControlWhen the temperature detected by liquid pipe therm

Strona 330 - 319 Appendix

SiBE12-816_D Function of Indoor Unit (SA Models)Function and Control 782.4 Hot Start Control (In Heating Operation Only)Outline At startup with thermo

Strona 331 - C: 4D039335A

SiBE12-816_D Introductionviii1.1.2 Cautions Regarding Safety of UsersWarningBe sure to use parts listed in the service parts list of the applicable mo

Strona 332 - 1.2 Outdoor Unit

Function of Thermistor SiBE12-816_D79 Function and Control3. Function of ThermistorA Outdoor Heat Exchanger Thermistor1. The outdoor heat exchanger

Strona 333 - 1.2.2 Heat Pump

SiBE12-816_D Function of ThermistorFunction and Control 80D Indoor Heat Exchanger Thermistor1. The indoor heat exchanger thermistor is used for cont

Strona 334 - 2. Wiring Diagrams

Control Specification SiBE12-816_D81 Function and Control4. Control Specification4.1 Mode HierarchyOutline There are two modes; the one is the normal

Strona 335 - 2.1.2 Floor Standing Type

SiBE12-816_D Control SpecificationFunction and Control 82Determine Operation ModeThe system judges the operation mode command which is set by each roo

Strona 336 - 2.1.4 Duct Connected Type

Control Specification SiBE12-816_D83 Function and Control4.2 Frequency ControlOutline Frequency that corresponds to each room’s capacity is determined

Strona 337 - 3D038357B

SiBE12-816_D Control SpecificationFunction and Control 84For Heat Pump Model1. Determine command frequencyCommand frequency is determined in the foll

Strona 338 - 2.2 Outdoor Unit

Control Specification SiBE12-816_D85 Function and ControlPI Control (Determine Frequency Up / Down by ∆D Signal)1. P controlA total of the ∆D value is

Strona 339 - 2.2.2 Heat Pump

SiBE12-816_D Control SpecificationFunction and Control 864.3 Controls at Mode Changing / Start-up4.3.1 Preheating OperationOutline The inverter operat

Strona 340 - Revision History

Control Specification SiBE12-816_D87 Function and Control4.3.5 Compressor Protection FunctionWhen turning the compressor from OFF to ON, the upper lim

Strona 341 - JQA-1452

SiBE12-816_D Control SpecificationFunction and Control 884.5 Input Current ControlOutline An input current is detected by the CT during the compressor