Functions SiBE01-503
16 Functions and Control
1.3 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Cooling
Thermostat OFF: Room temperature – setpoint
0
°
C
Thermostat ON : Room temperature – setpoint
1
°
C
Heating
Thermostat OFF: Room temperature – setpoint
2
°
C
Thermostat ON : Room temperature – setpoint
1
°
C
OFF
ON
Room temperature – setpoint
(R4725)
1˚C
0˚C
OFF
OFF
ON
ON
Room temperature – setpoint
(R4726)
2˚C
1˚C