•VRV
®
Systems • Indoor Unit
9
Indoor Unit • Large concealed ceiling unit • FXMQ-MA
6 Dimensional drawings
6 - 1 Dimensional Drawings
FXMQ200,250MA
3D038851
32 - ø 4.7 hole
(All around)
1,100 or more
(Service space)
650 or more
(Service space)
Discharge side
View
Suction side (Note. 2)
Inspection hole 600 or more
Approx
32 - ø 4.7 hole
(All around)
(All around)
View
(All around)
16 - ø 8 hole
Piping size (field supply)
Model Gas Liquid
FXMQ200MA ø 19.1 attached piping ø 9.5
FXMQ250MA ø 22.2 attached piping ø 9.5
NOTES
1 Location of unit’s name plate: switch box surface.
2 Mount the air filter at the suction side. (Select its colorimethod (gravity method) 50%
or more).
Nr Part name Description
1 Liquid pipe connection Flare connection
2 Gas pipe connection Attendant piping connection
3 Ground terminal M5 (Inside switch box)
4 Switch box
5 Power supply wiring connection
6 Transmission wiring connection
7 Hook M10
8 Discharge companion flange
9 Suction flange
10 Attached piping Brazing
11 Name plate
12 Drain piping connection PS1B Internal thread
VP25 (O.D. ø33.349, I.D. ø30.391)