INSTALLATION MANUALEnglishFrançaisEspañolSPLIT SYSTEM Air ConditionersMODELSCeiling mounted cassette type (Round flow model)FCQ18PAVJUFCQ24PAVJUFCQ30P
English 95. INDOOR UNIT INSTALLATIONInstalling optional accessories (except for the decoration panel) before installing the indoor unit is easier. How
10 English<Ceiling work>(1-3) Adjust the unit to the right position for installation.(Refer to “4. PREPARATIONS BEFORE INSTALLATION-(1)”.)• Usin
English 11CAUTION• Use a pipe cutter and flare suitable for the type of refrigerant.• Apply ester oil or ether oil around the flare section before con
12 EnglishNot recommendable but in case of emergencyYou must use a torque wrench but if you are obliged to install the unit without a torque wrench, y
English 13CAUTIONCAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING“Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copp
14 English• Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leak-age due to dew condensation.•
English 15WHEN ELECTRIC WIRING WORK IS FINISHED• Add approximately 1/4gal. of water slowly from the air outlet and check drainage flow.• Check drainag
16 EnglishCAUTIONDrain piping connectionsDo not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-age mi
English 178-2 Electrical characteristicsMCA: Minimum Circuit Ampacity (A) MOP: Maximum Overcurrent Protective Device (A)kW: Fan Motor Rated Output (kW
18 English[ PRECAUTIONS ]1. Use round crimp-style terminals for connecting wires to the power supply terminal block.If unavailable, observe the follow
English 1SPLIT SYSTEM Air Conditioners Installation manualCONTENTS1. SAFETY CONSIDERATIONS...
English 1910. Use a 90° elbow type of conduit with dimensions Fig. 27-1 to prevent it from hitting the swing motor hous-ing of decoration panel.Observ
20 EnglishCAUTION• When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the wiring connections and cl
English 211. When using 1 remote controller (Normal operation)2. When using 2 remote controllersFig. 29L1L2IN/D OUT/DF1F2F1F2P1P2P1P2F1F2T1T2Power sup
22 English[ PRECAUTIONS ]1. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones. Improper groundin
English 239-4 Computerized control (forced off and on/off operation)(1) Wire specifications and how to perform wiring• Connect the input from outside
24 English11. FIELD SETTINGCAUTIONWhen performing field setting or test run without attaching the decoration panel, do not touch the drain pump. This
English 2511-4 Setting of air filter sign•Remote controllers are equipped with liquid crystal display air filter signs to display the time to clean ai
3P161684-6K EM11A061(1110)1645 Wallace Drive, Suite 110Carrollton, TX 75006 [email protected]_CV_3P161684-6K.fm Page 2 Friday
2 English• Safely dispose all packing and transportation materials in accordance with federal/state/local laws or ordi-nances. Packing materials such
English 3• Refrigerant R410A in the system must be kept clean, dry, and tight.(a) Clean and Dry -- Foreign materials (including mineral oils such as S
4 English1. PRECAUTIONS• Be sure to read this manual before installing the indoor unit.• When selecting installation site, refer to the paper pattern.
English 53. OPTIONAL ACCESSORIES• The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)(However
6 EnglishPoints for explanation about operations4. NOTE TO THE INSTALLERBe sure to instruct customers how to properly operate the unit (especially cle
English 7CAUTION• The indoor and outdoor units and the power supply wiring and remote controller wire must be installed at least 40in. away from any t
8 English䡵 Installation is possible when ceiling opening dimensions is as follows• When installing the unit within the frame for fixing false ceiling.