EDUS391100-F6AMERICASFXAQ-PVJUWall Mounted Type
EDUS391100-F6 Electric CharacteristicsFXAQ-PVJU 95. Electric Characteristics6. Safety Devices Setting4D075550C: 4D047085CFXAQ - PVJU250V / 3.15A
Capacity Tables EDUS391100-F610 FXAQ-PVJU7. Capacity Tables7.1 Cooling CapacityFXAQ-P [Cooling capacity]TC: Total capacity: MBhSHC: Sensible heat ca
EDUS391100-F6 Capacity TablesFXAQ-PVJU 117.2 Heating CapacityFXAQ-P [Heating capacity]TC: Total capacity: MBhRefer to outdoor unit capacity tables for
Air Velocity and Temperature Distributions (Reference Data) EDUS391100-F612 FXAQ-PVJU8. Air Velocity and Temperature Distributions (Reference Data)FXA
EDUS391100-F6 Air Velocity and Temperature Distributions (Reference Data)FXAQ-PVJU 13FXAQ09PVJU <Cooling mode> C: 3D053943FXAQ09PVJU <Heating
Air Velocity and Temperature Distributions (Reference Data) EDUS391100-F614 FXAQ-PVJUFXAQ12PVJU <Cooling mode> C: 3D052935FXAQ12PVJU <Heating
EDUS391100-F6 Air Velocity and Temperature Distributions (Reference Data)FXAQ-PVJU 15FXAQ18PVJU <Cooling mode> C: 3D052936FXAQ18PVJU <Heating
Air Velocity and Temperature Distributions (Reference Data) EDUS391100-F616 FXAQ-PVJUFXAQ24PVJU <Cooling mode> C: 3D052937FXAQ24PVJU <Heating
EDUS391100-F6 Sound Levels (Reference)FXAQ-PVJU 179. Sound Levels (Reference)9.1 Overall9.2 Octave Band Level208/230V, 60Hz Location of microphone No
Sound Levels (Reference) EDUS391100-F618 FXAQ-PVJUFXAQ12PVJU FXAQ18PVJUFXAQ24PVJU4D0755824D0755834D075584
EDUS391100-F6FXAQ-PVJU 1 FXAQ-PVJUWall Mounted Type1. Specifications ... 22. Dimensions.
EDUS391100-F6 InstallationFXAQ-PVJU 1910.Installation Safety ConsiderationsRead these SAFETY CONSIDERATIONS for Installation carefully before installi
Installation EDUS391100-F620 FXAQ-PVJU• Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.• Do not
EDUS391100-F6 InstallationFXAQ-PVJU 21 BEFORE INSTALLATION2. When moving the unit while removing it from the packing case, be sure to lift it by th
Installation EDUS391100-F622 FXAQ-PVJU10.1 AccessoriesCheck the following accessories are included with your unit.Name(1) Installation panel(2) Atta
EDUS391100-F6 InstallationFXAQ-PVJU 23FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.Items to
Installation EDUS391100-F624 FXAQ-PVJUWhere piping between indoor and outdoor units is possible within the allowable limit. •(Refer to the installatio
EDUS391100-F6 InstallationFXAQ-PVJU 2510.2 Indoor Unit InstallationUse only accessories and parts which are of the designated specifi cation when insta
Installation EDUS391100-F626 FXAQ-PVJUMaking sure not to catch the horizontal fl aps, remove the front grille by pulling in the direction of the (4)arr
EDUS391100-F6 InstallationFXAQ-PVJU 27Hook the indoor unit onto the installation panel. (Refer to Fig. 9)(6)Placing buffering material between the wal
Installation EDUS391100-F628 FXAQ-PVJUPush on both bottom edges of the indoor unit using both hands and hook the tab on the back of (9)the indoor unit
Specifications EDUS391100-F62 FXAQ-PVJU1. SpecificationsWall Mounted TypeNotes: 1 Nominal cooling capacities are based on the following conditions: R
EDUS391100-F6 InstallationFXAQ-PVJU 29The outdoor unit is charged with refrigerant. •Use copper alloy seamless pipes. •Be sure to use both a spanner a
Installation EDUS391100-F630 FXAQ-PVJUWhen brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution •(NOTE 1
EDUS391100-F6 InstallationFXAQ-PVJU 3110.3 Drain Piping WorkDRAIN PIPING WORK6. Install the drain piping. (Refer to Fig. 16)(1)The drain pipe should b
Installation EDUS391100-F632 FXAQ-PVJU10.4 Electrical Wiring WorkAll fi eld supplied parts and materials and electric works must conform to local codes
EDUS391100-F6 InstallationFXAQ-PVJU 33SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIREModelPower supply wiringRemote controller wiringTransmission wi
Installation EDUS391100-F634 FXAQ-PVJUTo avoid a short circuit in the control box, be sure to apply sealing material or putty (not included) to the •
EDUS391100-F6 InstallationFXAQ-PVJU 35WIRING EXAMPLE Fit the power supply wire of each unit with a switch and fuse as shown in the drawing. •COMPLETE
Installation EDUS391100-F636 FXAQ-PVJUFor group control or use with 2 remote controllers2. L1 L2L1 L2 L1 L2IN/D OUT/DF1 F2 F1 F2Control boxP1P2P1P2F1F
EDUS391100-F6 InstallationFXAQ-PVJU 37CONTROL BY 2 REMOTE CONTROLLERS (CONTROLLING 1 INDOOR UNIT BY 2 RE-MOTE CONTROLLERS)When using 2 remote controll
Installation EDUS391100-F638 FXAQ-PVJU10.5 Field Settings Make sure the control box covers are closed on the indoor and outdoor units.(1)Field setti
EDUS391100-F6 SpecificationsFXAQ-PVJU 3Wall Mounted TypeNotes: 1 Nominal cooling capacities are based on the following conditions: Return air tempera
EDUS391100-F6 Test RunFXAQ-PVJU 3911. Test RunMake sure the control box covers are closed on the indoor and outdoor units.Refer to the installation
Accessories EDUS391100-F640 FXAQ-PVJU12.Accessories12.1 Optional Accessories (For Controls)Refer to booklet of “Controls”.
EDUS391100-F6Printed in U.S.A. 02/12 FS.KSpecifications, designs and other content appearing in this brochure are current as of February 2012 but subj
Dimensions EDUS391100-F64 FXAQ-PVJU2. DimensionsFXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJUUnit (in.)3D075388A
EDUS391100-F6 DimensionsFXAQ-PVJU 5FXAQ18PVJUUnit (in.)3D075389A
Dimensions EDUS391100-F66 FXAQ-PVJUFXAQ24PVJUUnit (in.)3D075390A
EDUS391100-F6 Piping DiagramsFXAQ-PVJU 73. Piping DiagramsModel Gas LiquidFXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJU/FXAQ18PVJU1/2 1/4FXAQ24PVJU 5/8 3/8C: 4
Wiring Diagrams EDUS391100-F68 FXAQ-PVJU4. Wiring DiagramsFXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJU/FXAQ18PVJU/FXAQ24PVJU3D075354