EnglishFrançaisEspañolINSTALLATION MANUAL SYSTEM Inverter Air ConditionersMODELSAir Handling UnitFXTQ12PAVJUFXTQ18PAVJUFXTQ24PAVJUFXTQ30PAVJUFXTQ36PAV
9 EnglishNOTES If the wiring is in a place where people it can be easily 1. touched by people, install a ground-fault circuit interrupter to prevent
English 10in Fig. 10.Then secure them in place with the included clamp • material (1) as shown in Fig. 10 to protect them from external force from ou
11 EnglishOutside the air conditioners, separate the low voltage wiring •(remote controller and transmission wiring) and high voltage wiring (ground
English 12Wiring Method (See ‘‘8. ELECTRIC WIRING WORK’’)Remove the electric component box cover.(3) Add remote controller 2 (SUB) to the terminal bl
13 EnglishREMOTE CONTROL SETTING10-2 Forced off and ON/OFF operation should be selected by • selecting the SECOND CODE NO. as shown in Table 4.Table
English 14Turn off power supply to all indoor and outdoor units.(1) Remove the front panel (upper) and the electric heater (2) slot cover.Electric he
15 EnglishPass the power supply wiring and the ground wire (8) through the conduit (conduit should be fi eld sup-plied). The hole for running wires th
English 16Electric heater operating mode setting(12) -2 〈When electric heater is used in “Heat Pump lockout mode”〉Check the heater capacity. (Select
17 English〈When using a wireless remote controller〉A wireless remote controller address needs to be set when • using a wireless remote controller. Se
3P250363-2B EM09A034A (1011)FS
1 EnglishVRV SYSTEM Inverter Air Conditioners Installation manualCONTENTS1. SAFETY CONSIDERATIONS ... 12. BEF
English 2It is recommended to install a ground fault circuit inter-• rupter if one is not already available. This helps prevent electrical shocks or
3 EnglishBEFORE INSTALLATION2. WARNINGEntrust installation to the place of purchase or a qualifi ed • serviceman. Improper installation could lead to
English 4Where piping between indoor and outdoor units is • possible within the allowable limit. (Refer to the installa-tion manual for the outdoor u
5 EnglishTable 1Model A B C D E F G H I12 · 18 type46-3/42217-1/219-1/21014-1/211-15/1617-1/817-15/1624 · 30 · 36 · 42 · 48 · 54 type53-1/424 20 22 1
English 6REFRIGERANT PIPING WORK5. 〈Observe the requirements listed below for refrigerant piping sizes.〉Liquid Gas12 · 18 type 1/4 in. 1/2 in.24 · 30
7 English CAUTIONBe sure to insulate any fi eld piping all the way to the piping •connection inside the unit. Any exposed piping may cause condensati
English 8To keep the piping from becoming clogged with dirt, • avoid bends where possible and install so that traps can be cleaned.At least 4 in.Air