INSTALLATION MANUALEnglishFrançaisEspañolSPLIT SYSTEM Air ConditionersMODELSRZQ18PVJURZQ24PVJURZQ30PVJURead these instructions carefully before instal
9 English(Flux has an extremely negative effect on refrigerant piping systems. For instance, if chlorine based fl ux is used, it will cause pipe corro
English 10Refrigerant piping work procedure6-4 The fi eld piping can be connected in three directions.Piping coverScrew for front panelScrew for pip
11 English NOTERefrigerant cannot be charged until fi eld wiring has been • completed.Refrigerant may only be charged after performing the air-tight t
English 12Valve capService portField piping connection partValve stemSilicon sealant(Take care not to generate cavity.)<Liquid line><Gas lin
13 EnglishConnection example of whole system wiring7-1 PowerRemote controller Indoor unitGroundPowerGroundOutdoor unit16V208-230V208-230V16VEarth lea
English 14How to Insulation tube.Use the insulation tube large to cover the power supply • wiring.Use the insulation tube small to cover the transmis
15 EnglishPiping size and heat insulation:5. Refer to “6-1 Selection of piping material”, “6-5 Heat insulation of the piping”.Check of stop valve:6.
English 16<Cautions on check operation>If the air conditioner is started within about 12 minutes after • the power of the indoor/outdoor unit i
17 EnglishWhen nothing is displayed in the remote controllerThere might be a problem with the connection or transmis-• sion between the indoor unit a
3PA60114-14U EM08A096 (0902)HT00_CV_3PA60114-14U.indd 200_CV_3PA60114-14U.indd 2 1/26/2009 4:54:55 PM1/26/2009 4:54:55 PM
SPLIT SYSTEM Air Conditioners Installation manual1 EnglishCONTENTS1. SAFETY CONSIDERATIONS ... 12. INTRODUCTI
English 2When wiring the power supply and connecting the •remote controller wiring and transmission wiring, posi-tion the wires so that the terminal
3 English NOTEInstall the indoor and outdoor units, power supply •wiring and transmission wiring at least 3.5ft. away from televisions or radios in
English 4BEFORE INSTALLATION3. 〈Bringing-in〉Bring in the outdoor unit slowly by holding the lugs provided on the left and right sides as shown in the
5 English DANGERDo not install unit in an area where fl ammable materials are • present due to risk of explosion resulting in serious injury or death.
English 6When an obstruction is present also in the upward area •When one outdoor unit is installed individually(1) 20 or less20 or more40 or moreWhe
7 English<Pattern 2>When an obstruction on the air outlet side is lower than the outdoor unit (There is no restriction in the height of obstruc
English 8When an obstruction is present on the air inlet side(2) 4Z12 or more NOTEOnly two outdoor units can be stacked.1. About 4 in. is required as