Strona 1 - J Series

Si18-201J Series[Applied Models]!!!!Super Multi Plus : Cooling Only !!!!Super Multi Plus : Heat PumpServiceManual

Strona 2 - Table of Contents i

Si18-201 Introductionix1. Introduction1.1 Safety CautionsCautions and Warnings"Be sure to read the following safety cautions before conducting re

Strona 3

Si18-201 Main FunctionsMain Functions 871.1.12 Mold Proof Air FilterFor FTK(X)25/35 J,FTK(X)50/60 H SeriesThe filter net is treated with mold resistin

Strona 4 - Table of Contents iii

Main Functions Si18-20188 Main Functions1.1.16 Automatic Operation (Heat Pump Only)Automatic Cooling/Heating FunctionWhen the AUTO mode is selected wi

Strona 5

Si18-201 Main FunctionsMain Functions 891.1.17 Night Set ModeWhen the OFF Timer is set, the New Night Set Circuit automatically activates.The Night Se

Strona 6 - Table of Contents v

Main Functions Si18-20190 Main Functions1.1.21 Intelligent EyeFor FTK(X)25/35 JSeries OnlyOutlineThe function that detects existence of humans in the

Strona 7

Si18-201 Main FunctionsMain Functions 91"Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes low and can

Strona 8 - Table of Contents vii

Main Functions Si18-20192 Main Functions1.1.23 Program Dry OperationBy the function of the microcomputer, program dry operation reduces the humidity k

Strona 9

Si18-201 Main FunctionsMain Functions 931.1.24 Cooling Monitoring FunctionMonitoring function is activated while cooling and program dry operation are

Strona 10 - 1. Introduction

Main Functions Si18-20194 Main Functions1.1.25 Freeze Protection FunctionWhen the indoor heat exchanger temperature falls below “A”°C in cooling or pr

Strona 11

Si18-201 Main FunctionsMain Functions 951.1.29 Air Flow Automatic (Auto Fan Speed)In cooling operation, if automatic airflow has been selected, the wi

Strona 12 - 1.1.3 Inspection after Repair

Main Functions Si18-20196 Main Functions1.1.31 Emergency Operation Function (ON/OFF Switch)The unit can be turned ON only by pressing ON/OFF operation

Strona 13 - 1.1.5 Using Icons List

Introduction Si18-201x1.1.2 Cautions Regarding Products after RepairCautionDo not repair the electrical components with wet hands.Working on the equip

Strona 14 - List of Function 1

Si18-201 Main FunctionsMain Functions 971.1.33 Filter Check Indicator"The filter check indicator located at the center of the unit will indicate

Strona 15 - 1. List of Function

Main Functions Si18-20198 Main Functions1.2 SkyAirThermostat ControlExisting cooling/heating preset temperature range has been changed.Draft Avoidance

Strona 16 - 1.2 Function List for China

Si18-201 Main FunctionsMain Functions 99Draft Avoidance Control 2When hot start is cancelled or when cold air prevention control is finished, if the f

Strona 17 - 1.3 Function List for Taiwan

Main Functions Si18-201100 Main Functions1.3 Cautions when SkyAir [Auto] [FAN] are used1.3.1 Heat Pump ModelThe Corresponding ModelsFHYC35 / 50 / 60 /

Strona 18 - 1.4 Function List for Europe

Si18-201Main Functions 101Part 5Part 5Part 5Part 5Main FunctionsMain FunctionsMain FunctionsMain FunctionsOutdoor Unit / BP UnitOutdoor Unit / BP Unit

Strona 19 - 6 List of Function

Si18-201102 Main Functions3.33 BP Unit Motorized Valve Control in High Discharge Pipe Temperature...

Strona 20

Si18-201 Refrigerant System and Function of Functional Parts of Outdoor UnitMain Functions 1031. Refrigerant System and Function of Functional Parts o

Strona 21 - 1.7 Function List for Europe

Refrigerant System and Function of Functional Parts of Outdoor Unit Si18-201104 Main Functions1.2 Major Functional Parts Compressor : JT100F-VDThe ap

Strona 22 - Specifications 9

Si18-201 Refrigerant System and Function of Functional Parts of Outdoor UnitMain Functions 105 EVT : Motorized valve in non-operating room BP unitIn

Strona 23 - 1. Specifications

Refrigerant System and Function of Functional Parts of Outdoor Unit Si18-201106 Main Functions1.3 Protective Devices, Thermistors, SensorsAHPSWhen the

Strona 24 - Indoor Unit

Si18-201 Introductionxi1.1.3 Inspection after RepairBe sure to use the specified cable to connect between the indoor and outdoor units. Make the conne

Strona 25

Si18-201 Protection DeviceMain Functions 1072. Protection Device2.1 Outdoor UnitRMX140JVMM1C Compressor JT100F-VD 3.3kW × 1 ScrollJ1HC Crankcase Heate

Strona 26

Protection Device Si18-201108 Main Functions2.2 BP UnitBPMK928B42, BPMK928B43FU1 ~ 4 FUSE (3EB82010-1) 250V 3.15AY1E(EVH)ElectronicExpansion ValveMa

Strona 27 - 1.1.2 Heat Pump

Si18-201 System controlMain Functions 1093. System control3.1 Outline of System ControlYESYESYESNONONOBP unitBP unitEVGEVLEVGEVLBP unitBP unitEVGEVG(M

Strona 28

System control Si18-201110 Main Functions3.2 Mode ConfigurationAir Conditioner Control ModeAir conditioner control modeDetermination of Normal Operati

Strona 29

Si18-201 System controlMain Functions 1113.3 Standby Control at Power ONPurpose of the FunctionTo initialize the motorized valve at power ON, to deter

Strona 30

System control Si18-201112 Main Functions3.4 Cooling / Heating Standby Operation at StartupPurpose of the FunctionTo prepare for the next startup afte

Strona 31 - 1.2 BP Units

Si18-201 System controlMain Functions 1133.5 Equalizing ControlPurpose of the FunctionTo provide equalizing control after a standby operation in order

Strona 32 - 1.3.1 Cooling Only

System control Si18-201114 Main FunctionsEqualizing Control in Heating4-way valve(Delay timer for OFF)Command frequencyOutdoor unit upper fanOutdoor u

Strona 33 - 6.0kW Class

Si18-201 System controlMain Functions 1153.6 Determination of Initial Frequency3.6.1 Determination of Operation FrequencyPurpose of the FunctionTo con

Strona 34 - 7.1kW Class

System control Si18-201116 Main Functions3.6.2 BP Unit Command Conversion1. ∆D (room temperature − temperature setting) signals from BP units are conv

Strona 35 - 3.5kW Class

Introduction Si18-201xii1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is de

Strona 36

Si18-201 System controlMain Functions 1173.6.3 Determination of Initial FrequencyInitial frequency setting (determination of initial operating frequen

Strona 37

System control Si18-201118 Main FunctionsDetermination of initial frequency for coolingInitial frequency FSR is determined based on the correction of

Strona 38

Si18-201 System controlMain Functions 119Determination of initial frequency for heatingInitial frequency FSR is determined based on the correction of

Strona 39 - 6.15kW Class · 7.7kW Class

System control Si18-201120 Main Functions3.7 Oil Return OperationPurpose of the FunctionTo collect refrigerating machine oil that adheres on the inter

Strona 40 - 60Hz 220-230V

Si18-201 System controlMain Functions 121Oil recovery operation in heating modeTOW1(150min)Cumulative heating timeCompressor operation frequencyCompre

Strona 41 - 1.3.2 Heat Pump

System control Si18-201122 Main Functions3.8 Defrost OperationOutline During heating operation, the outdoor heat exchanger intermediate temperature of

Strona 42

Si18-201 System controlMain Functions 1233.9 Pre-Equalization Standby OperationOutline In local air conditioner control mode and frequency fix mode, t

Strona 43 - 5.0kW Class · 6.0kW Class

System control Si18-201124 Main Functions3.10 Equalizing ControlOutline This function provides equalizing control after a standby operation in order t

Strona 44

Si18-201 System controlMain Functions 125Equalizing control in heatingStandbyoperation4-way valve(OFF delay timer)CommandfrequencyOutdoor unitlower fa

Strona 45

System control Si18-201126 Main Functions3.11 Capacity Control3.11.1 Outdoor Unit Motorized Valve Low Pressure (Cooling Capacity) ControlOutline This

Strona 46 - 6.0kW Class · 7.7kW Class

Si18-201List of Function 1Part 1Part 1Part 1Part 1List of FunctionList of FunctionList of FunctionList of Function1. List of Function...

Strona 47 - 1.4 Indoor Units (for China)

Si18-201 System controlMain Functions 1273.11.2 Outdoor Unit Motorized Valve High Pressure (Heating Capacity) ControlOutline This function opens the g

Strona 48

System control Si18-201128 Main Functions3.12 Peak Cut ControlOutline Based on the indoor heat exchanger intermediate temperature signal sent from the

Strona 49 - 50Hz 220V

Si18-201 System controlMain Functions 1293.13 Freeze-Up PreventionOutline According to the freeze prevention status sent from the BP unit, the compres

Strona 50 - Specifications 37

System control Si18-201130 Main Functions3.14 Gas Shortage MalfunctionOutline A gas shortage malfunction is detected by using electric current and by

Strona 51 - 1.4.2 Heat Pump

Si18-201 System controlMain Functions 1313.15 Discharge Pipe ControlOutline With the internal compressor temperature used as a substitute of the disch

Strona 52

System control Si18-201132 Main Functions3.16 Input Current Control3.16.1 Input Current Control IOutline The input current is detected by CT during co

Strona 53

Si18-201 System controlMain Functions 133Details The input current is used to control the upper limit of the operating frequency in order to maintain

Strona 54 - Specifications 41

System control Si18-201134 Main Functions3.16.2 Input Current Control II (High Pressure Control)Outline Based on the input current and input voltage,

Strona 55

Si18-201 System controlMain Functions 1353.17 Wet Protection Control IOutline When the outside air temperature is low, the lower limit of operating fr

Strona 56 - 1.5 Indoor Units (for Taiwan)

System control Si18-201136 Main Functions3.18 Electric Parts Cooling and Electric Parts / Fin Temperature ControlOutline This function cools the elect

Strona 57

List of Function Si18-2012 List of Function1. List of Function1.1 Function List for General★1! : for FLK, FLX50/60J★2– : for FLK, FLX50/60JDivisionInd

Strona 58

Si18-201 System controlMain Functions 1373.19 Differential Pressure ControlOutline This function sets an upper limit for the fan rotation speed accord

Strona 59 - 60Hz 220V

System control Si18-201138 Main Functions3.20 Year-Round Cooling-Only FunctionOutline This function turns off the compressor based on the conditions o

Strona 60 - Specifications 47

Si18-201 System controlMain Functions 1393.21 Nighttime Low Noise ControlPurpose of the FunctionThis function lowers the operating sound when the nois

Strona 61 - 1.5.2 Heat Pump

System control Si18-201140 Main Functions3.22 PI ControlOutline Based on the ∆D signal, MAXα of the command frequency is monitored every 20 seconds, a

Strona 62

Si18-201 System controlMain Functions 1413.23 Warm-Up FunctionOutline This function operates the inverter in a open-phase mode to warm up the compress

Strona 63 - 50 Specifications

System control Si18-201142 Main Functions3.24 Compressor Protection ControlPurpose of the FunctionThis function ensures appropriate compressor oil lev

Strona 64

Si18-201 System controlMain Functions 1433.25 Fan ControlPurpose of the FunctionThis function changes the fan rotation speed or stop the fan operation

Strona 65 - 1.6 Indoor Units (for Europe)

System control Si18-201144 Main FunctionsFan control in normal heating modeDue to outside air temperature DOA and output frequency FOUT, conditions 

Strona 66

Si18-201 System controlMain Functions 1453.26 Motorized Valve Control of Outdoor Unit3.26.1 Outline of Motorized Valve ControlOutline The EVL and EVG

Strona 67

System control Si18-201146 Main Functions3.26.2 Outdoor Unit Motorized Valve Opening RestrictionOutline This function restricts the opening degree of

Strona 68

Si18-201 List of FunctionList of Function 31.2 Function List for ChinaDivisionIndoor Unit / Outdoor UnitInverter (with Inverter Power Control)PAM cont

Strona 69

Si18-201 System controlMain Functions 1473. EVL (liquid pipe motorized valve) opening restrictionEVL (liquid pipe motorized valve)" ELV fully clo

Strona 70 - Floor Standing Type

System control Si18-201148 Main Functions3.26.3 Outdoor Unit Motorized Valve Control in Startup and During the Number of Operating Room Units ChangeOu

Strona 71 - 58 Specifications

Si18-201 System controlMain Functions 149"In case of KBPIW 1.5 ≤ FPIMN / initial frequencyWhen initial frequency is equal or smaller than FPIMN /

Strona 72

System control Si18-201150 Main Functions3.26.5 Outdoor Units Motorized Valve Control by Target Discharge Pipe TemperatureOutline This function adjust

Strona 73

Si18-201 System controlMain Functions 1513.27 Cooling Outdoor Unit SC ControlOutline This function controls the subcooling of the outdoor heat exchang

Strona 74

System control Si18-201152 Main Functions3.28 BP Unit Motorized Valve ControlPurpose of the FunctionThis function provides instructions regarding the

Strona 75

Si18-201 System controlMain Functions 1533.28.4 Full Closing of Motorized ValvesPurpose of the FunctionThe motorized valves are initialized when the p

Strona 76

System control Si18-201154 Main Functions3.28.6 Control Based on Relative Flow Rate InstructionPurpose of the FunctionThis function operates the motor

Strona 77

Si18-201 System controlMain Functions 1553.29 Gas Pipe Isothermal Control in Cooling OperationPurpose of the FunctionThis function ensures appropriate

Strona 78 - Printed Circuit Board (1)~(3)

System control Si18-201156 Main FunctionsThe motorized valve operating amount is determined based on deviation EGA between each room unit's gas p

Strona 79

List of Function Si18-2014 List of Function1.3 Function List for TaiwanDivisionIndoor Unit / Outdoor UnitInverter (with Inverter Power Control)PAM con

Strona 80

Si18-201 System controlMain Functions 1573.30 SH Control in Cooling OperationPurpose of the FunctionThis function ensures appropriate refrigerant dist

Strona 81

System control Si18-201158 Main FunctionsRegarding target superheated degree SH(Example) The following example is based on room A.When the sum of heat

Strona 82

Si18-201 System controlMain Functions 1593.31 SC Control in Heating OperationPurpose of the FunctionThis function ensures appropriate refrigerant dist

Strona 83

System control Si18-201160 Main FunctionsDetails The heat exchanger intermediate temperature and liquid pipe temperature are detected at every samplin

Strona 84

Si18-201 System controlMain Functions 1613.32 Heat Exchanger Isothermal Control in Heating OperationPurpose of the FunctionThis function ensures appro

Strona 85

System control Si18-201162 Main Functions3.33 BP Unit Motorized Valve Control in High Discharge Pipe TemperatureWhen the discharge pipe temperature ex

Strona 86 - 1.7 FHYC35~71KV Series

Si18-201 System controlMain Functions 1633.34 Inter-BP Units Heating Heat Exchanger Isothermal ControlPurpose of the FunctionThis function ensures app

Strona 87 - Printed Circuit

System control Si18-201164 Main Functions3.35 Inter-BP Units Gas Pipe Isothermal ControlPurpose of the FunctionThis function ensures appropriate refri

Strona 88 - 1.8 FDYM60FA, FDYM03FA Series

Si18-201 System controlMain Functions 1653.36 BP Unit Motorized Valve Control by Target Discharge Pipe TemperaturePurpose of the FunctionThis function

Strona 89

System control Si18-201166 Main Functions3.37 4-Way Valve Operation3.37.1 4-Way Valve Operation SecurityPurpose of the FunctionThis function ensures p

Strona 90 - Main Functions 77

Si18-201 List of FunctionList of Function 51.4 Function List for Europe★1! : for FLX50/60J★2– : for FLX50/60JDivisionIndoor Unit / Outdoor UnitInverte

Strona 91 - 1. Main Functions

Si18-201 System controlMain Functions 1673.38 JIS ModePurpose of the FunctionThis aims to minimize capacity deviations at the time the JIS mode is det

Strona 92 - 1.1.2 Wide-Angle Louvers

System control Si18-201168 Main Functions3.39 Pump Down OperationOutline When the Pump-down button is pressed, the following control is provided to co

Strona 93 - 80 Main Functions

Si18-201 System controlMain Functions 1693.40 Protection Control of SkyAir Indoor UnitsSkyAir Indoor Unit Peak-Cut ZoneThe zones for SkyAir indoor uni

Strona 94

System control Si18-201170 Main FunctionsMonitoring Function During SkyAir Indoor Unit Heating Thermostat OFFIn the case of SkyAir indoor units, the f

Strona 95 - 1.1.5 3 Step Flow

Si18-201Flow of Refrigerant 171Part 6Part 6Part 6Part 6Flow of RefrigerantFlow of RefrigerantFlow of RefrigerantFlow of Refrigerant1. Flow of Refriger

Strona 96 - Main Functions 83

Flow of Refrigerant Si18-201172 Flow of Refrigerant1. Flow of Refrigerant1.1 Flow of RefrigerantOperation ModeNo.Operating Status$: Fixed opening (ste

Strona 97 - (RL010) (RL010)

Si18-201 Flow of RefrigerantFlow of Refrigerant 1731.2 Standby Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(D

Strona 98 - 1.1.10 Washable Grille

Flow of Refrigerant Si18-201174 Flow of Refrigerant1.3 Equalizing Control (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(

Strona 99 - 86 Main Functions

Si18-201 Flow of RefrigerantFlow of Refrigerant 1751.4 Oil Return Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTO

Strona 100 - 1.1.15 Program Dry Function

Flow of Refrigerant Si18-201176 Flow of Refrigerant1.5 Low Outside Air Temperature CoolingTHERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTR

Strona 101 - 88 Main Functions

List of Function Si18-2016 List of Function1.5 Function List for Singapore, Malaysia, IndonesiaDivisionIndoor Unit / Outdoor UnitInverter (with Invert

Strona 102 - 1.1.20 Auto-Restart Function

Si18-201 Flow of RefrigerantFlow of Refrigerant 1771.6 All-Room Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(

Strona 103 - 1.1.21 Intelligent Eye

Flow of Refrigerant Si18-201178 Flow of Refrigerant1.7 Multi-Room Operation (No Surplus Refrigerant) (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMO

Strona 104 - Main Functions 91

Si18-201 Flow of RefrigerantFlow of Refrigerant 1791.8 Multi-Room Operation (Cooling) (with Surplus Refrigerant)THERMISTORLIQUID PIPEOUTDOOR UNITMOTOR

Strona 105 - 1.1.23 Program Dry Operation

Flow of Refrigerant Si18-201180 Flow of Refrigerant1.9 1-Room Operation — Indoor Unit with Large Capacity (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMO

Strona 106 - Main Functions 93

Si18-201 Flow of RefrigerantFlow of Refrigerant 1811.10 1-Room Operation — Indoor Unit with Small Capacity (2.5 kW) (Cooling)THERMISTORLIQUID PIPEOUTD

Strona 107 - 1.1.28 Auto-Swing of Flap(s)

Flow of Refrigerant Si18-201182 Flow of Refrigerant1.11 Standby Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(

Strona 108 - BLADE ANGLE

Si18-201 Flow of RefrigerantFlow of Refrigerant 1831.12 Equalizing Control (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR

Strona 109 - 1.1.32 Powerful Operation

Flow of Refrigerant Si18-201184 Flow of Refrigerant1.13 Oil Return Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUT

Strona 110 - 1.1.33 Filter Check Indicator

Si18-201 Flow of RefrigerantFlow of Refrigerant 1851.14 Defrost Operation THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(DEL)PROPE

Strona 111 - 1.2 SkyAir

Flow of Refrigerant Si18-201186 Flow of Refrigerant1.15 All-Room Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR

Strona 112 - Main Functions 99

Si18-201Table of Contents iSuper Multi PlusSuper Multi PlusSuper Multi PlusSuper Multi PlusJ SeriesJ SeriesJ SeriesJ Series!Heat PumpIndoor UnitFTX25J

Strona 113 - Cautions

Si18-201 List of FunctionList of Function 71.6 Function List for Australia★1! : for FLK, FLX50/60J★2– : for FLK, FLX50/60JDivisionIndoor Unit / Outdoo

Strona 114 - Main Functions 101

Si18-201 Flow of RefrigerantFlow of Refrigerant 1871.16 Multi-Room Operation (with non-Operating Room Unit) (Heating)THERMISTORLIQUID PIPEOUTDOOR UNIT

Strona 115 - 102 Main Functions

Flow of Refrigerant Si18-201188 Flow of Refrigerant1.17 Multi-Room Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUT

Strona 116 - Parts of Outdoor Unit

Si18-201 Flow of RefrigerantFlow of Refrigerant 1891.18 1-Room Operation — Indoor Unit with Large Capacity (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITM

Strona 117 - 1.2 Major Functional Parts

Flow of Refrigerant Si18-201190 Flow of Refrigerant1.19 1-Room Operation — Indoor Unit with Small Capacity (2.5 kW) (Heating)THERMISTORLIQUID PIPEOUTD

Strona 118 - Main Functions 105

Si18-201Operations 191Part 7Part 7Part 7Part 7OperationsOperationsOperationsOperations1. Remote Controller...

Strona 119 - 106 Main Functions

Remote Controller Si18-201192 Operations1. Remote Controller1.1 Wireless Remote Controller1.1.1 FTK, FTX25 / 35J ∗ARC423A3, ARC423A2 f

Strona 120 - 2. Protection Device

Si18-201 Remote ControllerOperations 1931.1.2 FVX25 / 35KZ

Strona 121 - 2.2 BP Unit

Remote Controller Si18-201194 Operations1.1.3 FTXD25 / 35KZ

Strona 122 - 3. System control

Si18-201 Remote ControllerOperations 1951.1.4 FTK, FTX50 / 60H

Strona 123 - 3.2 Mode Configuration

Remote Controller Si18-201196 Operations1.1.5 FTKD, FTXD50 / 60 / 71J

Strona 124 - Main Functions 111

List of Function Si18-2018 List of Function1.7 Function List for Europe★1! : for FLX50/60J★2– : for FLX50/60JDivisionIndoor Unit / Outdoor UnitInverte

Strona 125 - 112 Main Functions

Si18-201 Remote ControllerOperations 1971.1.6 FLK, FLX50 / 60JOpenthecover.CONAMPMAMPMPOWERFULMODEONCANCELOFFTEMPHOMELEAVESILENTFANSWINGTEMPON/OFFTran

Strona 126 - 3.5 Equalizing Control

Remote Controller Si18-201198 Operations1.1.7 CDK25 / 35 / 50 / 60HA, CDX25 / 35 / 50 / 60J∗ARC423A13, ARC423A14 for CDK25 / 35 / 50 / 60HAVEC, CDX25

Strona 127 - Equalizing Control in Heating

Si18-201 Remote ControllerOperations 1991.1.8 FLK, FLX25 / 35 / 50 / 60H∗ARC423A9, ARC423A10 for FLK25 / 35 / 50 / 60HVEC, FLX25 / 35 / 50 / 60HVECCON

Strona 128 - Main Functions 115

Remote Controller Si18-201200 Operations1.1.9 FHYC35 / 50 / 60 / 71K (Optional Accessory)BRC7C612WC

Strona 129

Si18-201 Remote ControllerOperations 201

Strona 130 - Main Functions 117

Remote Controller Si18-201202 Operations1.2 Wired Remote Controller1.2.1 FHYC35 / 50 / 60 / 71K (Optional Accessory)BRC1B61REMOTE CONTROLLER1.2.2 FDYM

Strona 131

Si18-201 Remote ControllerOperations 203

Strona 132

Remote Controller Si18-201204 Operations

Strona 133 - 3.7 Oil Return Operation

Si18-201Operating Test 205Part 8Part 8Part 8Part 8Operating TestOperating TestOperating TestOperating Test1. Operating Test ...

Strona 134 - Main Functions 121

Operating Test Si18-201206 Operating Test1. Operating Test1.1 Operating Test1OPERATING TEST*Check the connection status.Be sure to carry out initial s

Strona 135 - 3.8 Defrost Operation

Si18-201Specifications 9Part 2Part 2Part 2Part 2SpecificationsSpecificationsSpecificationsSpecifications1. Specifications...

Strona 136 - Main Functions 123

Si18-201 Operating TestOperating Test 207*ex.) : Connect indoor units (2 rooms) to BP1.Connect indoor units (3 rooms) to BP2.Connect indoor units (2 r

Strona 137 - 3.10 Equalizing Control

Operating Test Si18-201208 Operating Test1. Record the installation location of each BP unit in the centralized name plate attached to the front panel

Strona 138 - Equalizing control in heating

Si18-201 Operating TestOperating Test 2091.2 Test Operation SwitchTEST OPERATION SWITCH [SW7]Press the FORCED OPERATION SWITCH [SW7]Aftrer sellecting

Strona 139 - 3.11 Capacity Control

Operating Test Si18-201210 Operating Test1.3 Pump Down Operation Switch1. Close the liquid side stop valve of outdoor unit.2. Pump down3. Close the ga

Strona 140 - Main Functions 127

Si18-201 Operating TestOperating Test 2111.4 Record of the Installation PositionBe sure to enter the system unit installation position.1 SYSTEM LAYOUT

Strona 141 - 3.12 Peak Cut Control

Method of Field Set Si18-201212 Operating Test2. Method of Field Set2.1 Field SettingWired Remote ControllerNotes: (Field setting must be made from th

Strona 142 - Drooping zone

Si18-201 Method of Field SetOperating Test 213Wireless Remote ControllerNote: If optional accessories are mounted on the indoor unit, the indoor unit

Strona 143 - 3.14 Gas Shortage Malfunction

Method of Field Set Si18-201214 Operating Test2.1.2 Local Setting Mode No.Example To set the filter sign time to “filter contamination - heavy” for al

Strona 144 - 3.15 Discharge Pipe Control

Si18-201 Method of Field SetOperating Test 2153. When installing Sky Air simultaneous operation multi-unit, set to either “twin” or “triple.” Only whe

Strona 145 - 3.16 Input Current Control

Method of Field Set Si18-201216 Operating TestWireless Setting (Address and MAIN/SUB Setting)Explanation If several wireless remote controller units a

Strona 146

Specifications Si18-20110 Specifications1. Specifications1.1 Outdoor Units1.1.1 Cooling OnlyNotes:1.★ Refer to Engineering Data Book.2. The data ar

Strona 147 - 134 Main Functions

Si18-201 Method of Field SetOperating Test 217Setting the Address of Wireless Remote Controller (It is Factory Set to “1”) <Setting from the remote

Strona 148 - 3.17 Wet Protection Control I

Method of Field Set Si18-201218 Operating TestAfter Setting Stick the Unit No. label at decoration panel air discharge outlet as well as on the back o

Strona 149 - Temperature Control

Si18-201 Method of Field SetOperating Test 219Fan Speed Changeover when Thermostat is OFFBy setting to “Set Fan Speed,” you can switch the fan speed t

Strona 150 - Main Functions 137

Method of Field Set Si18-201220 Operating Test2.2 Group Number Setting for Central Remote Control"When controlled by a central remote controller

Strona 151

Si18-201 Method of Field SetOperating Test 2212.3 Interface Adaptor for Room Airconditioner <KRP928A1S>

Strona 152 - Main Functions 139

Method of Field Set Si18-201222 Operating TestNote: Setting of Centralized Controller<DCS301B61, DCS302B61, KRC72>Please refer to Operating Inst

Strona 153 - 3.22 PI Control

Si18-201 Method of Field SetOperating Test 2232.4 Precautions: For RMK140J / RMX140J Outdoor Unit UsersApplicable model seriesOutside air temperature

Strona 154 - 3.23 Warm-Up Function

Method of Field Set Si18-201224 Operating Test

Strona 155

Si18-201Service Diagnosis 225Part 9Part 9Part 9Part 9Service DiagnosisService DiagnosisService DiagnosisService Diagnosis1. Troubleshooting - Split Ty

Strona 156 - 3.25 Fan Control

Troubleshooting - Split Type Indoor Unit Si18-201226 Service Diagnosis1. Troubleshooting - Split Type Indoor Unit1.1 Troubleshooting with the Operatio

Strona 157 - 3.25.2 Fan OFF Delay Control

Si18-201 SpecificationsSpecifications 11Notes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.6

Strona 158 - EVG: Gas pipe motorized valve

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 227Troubleshooting with the LED IndicationThere are green and red LEDs on the PCB.

Strona 159

Troubleshooting - Split Type Indoor Unit Si18-201228 Service Diagnosis1.2 Service Check Function1.2.1 ARC423 Series (FTK(X)25/35J Series)In the ARC423

Strona 160 - Main Functions 147

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2291.2.2 ARC417 Series (FTK(X)50/60H Series)In the ARC417A series, the temperature

Strona 161 - 148 Main Functions

Troubleshooting - Split Type Indoor Unit Si18-201230 Service Diagnosis1.3 Code Indication on the Remote Controller1.3.1 Error Codes and Description of

Strona 162 - Temperature

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2311.4 Troubleshooting1.4.1 Indoor UnitsFTK(X)25/35 J Series - : Not used for troub

Strona 163

Troubleshooting - Split Type Indoor Unit Si18-201232 Service Diagnosis1.5 Troubleshooting Detail1.5.1 Faulty PCBRemote Controller DisplayA1Indoor Unit

Strona 164 - Main Functions 151

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2331.5.2 Operation Halt Due to the Freeze Protection FunctionRemote Controller Disp

Strona 165 - 152 Main Functions

Troubleshooting - Split Type Indoor Unit Si18-201234 Service DiagnosisTroubleshootingCheck No.8Refer to P.305NONONOCheck No. 8Indoor unit heat exchang

Strona 166 - Main Functions 153

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2351.5.3 Operation Halt Due to Fan Motor (AC Motor) or Related AbnormalityRemote Co

Strona 167 - 154 Main Functions

Troubleshooting - Split Type Indoor Unit Si18-201236 Service Diagnosis1.5.4 Operation Halt Due to Detection of Thermistor or Related AbnormalityRemote

Strona 168 - Main Functions 155

Specifications Si18-20112 SpecificationsNotes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.5

Strona 169

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2371.5.5 Faulty Indoor Unit PCBRemote Controller Display∗Indoor Unit LED DisplayA 4

Strona 170

Troubleshooting - Split Type Indoor Unit Si18-201238 Service Diagnosis1.5.6 Faulty Indoor Unit PCBRemote Controller Display∗Indoor Unit LED DisplayA 5

Strona 171 - 158 Main Functions

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2391.5.7 Faulty Power Supply or Indoor Unit PCB (For FTK(X)25/35J)Remote Controller

Strona 172 - Main Functions 159

Troubleshooting - Split Type Indoor Unit Si18-201240 Service Diagnosis1.5.8 Faulty Power Supply or Indoor Unit PCB (For FTK(X)50/60H, CDK(X)25~60H)Rem

Strona 173 - 160 Main Functions

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 241TroubleshootingCheck the varistor of the indoor unit PCB.Check the supply voltag

Strona 174 - Main Functions 161

Troubleshooting - Split Type Indoor Unit Si18-201242 Service DiagnosisTroubleshootingCheck No.16Refer to P.309Check the voltage of the transformer&apo

Strona 175

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 2431.5.9 Signal Transmission Error (Between Indoor and Outdoor Units)Remote Control

Strona 176 - Main Functions 163

Troubleshooting - Split Type Indoor Unit Si18-201244 Service Diagnosis1.5.10 Signal Transmission Error (Between Indoor Unit and Remote Controller)Remo

Strona 177 - 164 Main Functions

Si18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 245TroubleshootingCheck the indoor unit's LED A.Check the outdoor unit's

Strona 178 - Pipe Temperature

Troubleshooting - SkyAir Indoor Unit Si18-201246 Service Diagnosis2. Troubleshooting - SkyAir Indoor Unit2.1 The INSPECTION/TEST ButtonExplanation By

Strona 179 - 3.37 4-Way Valve Operation

Si18-201 SpecificationsSpecifications 13Notes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.5

Strona 180 - 3.38 JIS Mode

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2472.2 Self-Diagnosis by Wired Remote ControllerExplanation If operation stops due to m

Strona 181 - 3.39 Pump Down Operation

Troubleshooting - SkyAir Indoor Unit Si18-201248 Service Diagnosis2.3 Fault Diagnosis by Wireless Remote ControllerIf equipment stops due to a malfunc

Strona 182 - Main Functions 169

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 249

Strona 183 - 170 Main Functions

Troubleshooting - SkyAir Indoor Unit Si18-201250 Service Diagnosis2.4 Troubleshooting by LED on the Indoor Unit’sForeword Troubleshooting can be carri

Strona 184 - Flow of Refrigerant 171

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2512.5 Troubleshooting by Remote Controller Display / LED Display2.5.1 Explanation for

Strona 185 - 1. Flow of Refrigerant

Troubleshooting - SkyAir Indoor Unit Si18-201252 Service Diagnosis2.6 Troubleshooting Detail2.6.1 Failure of Indoor Unit PC BoardRemote Controller Dis

Strona 186 - Si18-201 Flow of Refrigerant

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2532.6.2 Malfunction of Drain Water Level System (Float Type) Remote Controller Display

Strona 187 - 174 Flow of Refrigerant

Troubleshooting - SkyAir Indoor Unit Si18-201254 Service DiagnosisTroubleshootingCautionBe sure to turn off power switch before connect or disconnect

Strona 188 - Flow of Refrigerant 175

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2552.6.3 Indoor Unit Fan Motor LockRemote Controller DisplayA6Applicable ModelsFHYCMeth

Strona 189 - 176 Flow of Refrigerant

Troubleshooting - SkyAir Indoor Unit Si18-201256 Service Diagnosis2.6.4 Swing Flap Motor Malfunction / LockRemote Controller DisplayA7Applicable Model

Strona 190 - Flow of Refrigerant 177

Specifications Si18-20114 Specifications1.1.2 Heat PumpNotes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shown in th

Strona 191 - (Cooling)

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2572.6.5 Failure of Capacity SettingRemote Controller DisplayAJApplicable ModelsFHYCMet

Strona 192 - Refrigerant)

Troubleshooting - SkyAir Indoor Unit Si18-201258 Service Diagnosis2.6.6 Malfunction of Heat Exchange Temperature Sensor System Remote Controller Displ

Strona 193

Si18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2592.6.7 Malfunction of Suction Air Temperature Sensor System Remote Controller Display

Strona 194 - (2.5 kW) (Cooling)

Troubleshooting - Outdoor Unit Related Si18-201260 Service Diagnosis3. Troubleshooting - Outdoor Unit Related3.1 The Unit Runs but Doesn’t Cool (Heat)

Strona 195 - 182 Flow of Refrigerant

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 261TroubleshootingHeatingOpen the stop valve.There is possibility of EVn malfunction.

Strona 196 - Flow of Refrigerant 183

Troubleshooting - Outdoor Unit Related Si18-201262 Service Diagnosis3.2 7 Seg. Display on the Outdoor P. C. BoardTROUBLE DAIGNOSIS <LED ON OUTDOOR

Strona 197 - 184 Flow of Refrigerant

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2633.3 Troubleshooting Detail3.3.1 High Pressure MalfunctionOutdoor Unit IndicationE3

Strona 198 - 1.14 Defrost Operation

Troubleshooting - Outdoor Unit Related Si18-201264 Service Diagnosis3.3.2 Compressor LockOutdoor Unit IndicationE6Method of Malfunction DetectionDetec

Strona 199 - 186 Flow of Refrigerant

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2653.3.3 Fan Lock / OvercurrentOutdoor Unit IndicationE7Method of Malfunction Detecti

Strona 200 - (Heating)

Troubleshooting - Outdoor Unit Related Si18-201266 Service Diagnosis3.3.4 Operation Halt Due to Detection of INV Input Current ErrorOutdoor Unit Indic

Strona 201 - 188 Flow of Refrigerant

Si18-201 SpecificationsSpecifications 15Notes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.6

Strona 202

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2673.3.5 Malfunction of Electronic Expansion ValveOutdoor Unit IndicationE9Method of

Strona 203 - (2.5 kW) (Heating)

Troubleshooting - Outdoor Unit Related Si18-201268 Service Diagnosis3.3.6 Operation Halt Due to Discharge Pipe Temperature ControlOutdoor Unit Indicat

Strona 204 - Operations 191

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2693.3.7 LP Drop ErrorOutdoor Unit IndicationFCMethod of Malfunction DetectionWhen th

Strona 205 - 1. Remote Controller

Troubleshooting - Outdoor Unit Related Si18-201270 Service Diagnosis3.3.8 Malfunction of High Pressure Switch SystemOutdoor Unit IndicationH3Method of

Strona 206 - 1.1.2 FVX25 / 35KZ

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2713.3.9 Operation Halt Due to Faulty Position Detection SensorOutdoor Unit Indicatio

Strona 207 - 1.1.3 FTXD25 / 35KZ

Troubleshooting - Outdoor Unit Related Si18-201272 Service Diagnosis3.3.10 Fan Position Detection ErrorOutdoor Unit IndicationH7Method of Malfunction

Strona 208 - 1.1.4 FTK, FTX50 / 60H

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2733.3.11 Operation Halt Due to Detection of CT ErrorOutdoor Unit IndicationH8Method

Strona 209 - 1.1.5 FTKD, FTXD50 / 60 / 71J

Troubleshooting - Outdoor Unit Related Si18-201274 Service Diagnosis3.3.12 Faulty Outside Air ThermistorOutdoor Unit IndicationH9Method of Malfunction

Strona 210 - 1.1.6 FLK, FLX50 / 60J

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2753.3.13 Faulty Discharge ThermistorOutdoor Unit IndicationJ3Method of Malfunction D

Strona 211 - 198 Operations

Troubleshooting - Outdoor Unit Related Si18-201276 Service Diagnosis3.3.14 Faulty of Suction ThermistorOutdoor Unit IndicationJ5Method of Malfunction

Strona 212 - Operations 199

Specifications Si18-20116 SpecificationsNotes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.50Hz

Strona 213 - BRC7C612WC

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2773.3.15 Faulty heat exchanger thermistorOutdoor Unit IndicationJ6Method of Malfunct

Strona 214 - Operations 201

Troubleshooting - Outdoor Unit Related Si18-201278 Service Diagnosis3.3.16 Faulty of Liquid Pipe ThermistorOutdoor Unit IndicationJ7Method of Malfunct

Strona 215 - 1.2 Wired Remote Controller

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2793.3.17 Faulty BP Liquid Pipe ThermistorOutdoor Unit IndicationJ8Method of Malfunct

Strona 216 - Operations 203

Troubleshooting - Outdoor Unit Related Si18-201280 Service Diagnosis3.3.18 Faulty BP Gas Pipe ThermistorOutdoor Unit IndicationJ9Method of Malfunction

Strona 217 - 204 Operations

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2813.3.19 Abnormal LP ErrorOutdoor Unit IndicationJCMethod of Malfunction Detection1.

Strona 218 - Operating Test 205

Troubleshooting - Outdoor Unit Related Si18-201282 Service Diagnosis3.3.20 Rise in BOX TemperatureOutdoor Unit IndicationL3Method of Malfunction Detec

Strona 219 - 1. Operating Test

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2833.3.21 Abnormal Rise in Fin TemperatureOutdoor Unit IndicationL4Method of Malfunct

Strona 220

Troubleshooting - Outdoor Unit Related Si18-201284 Service Diagnosis3.3.22 Operation Halt Due to Detection of Output OvercurrentOutdoor Unit Indicatio

Strona 221 - INITIALIZE SETTING

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 285TroubleshootingCheck No.1Refer to P.300Check No.2Refer to P.300Check No.6Refer to

Strona 222 - 1.2 Test Operation Switch

Troubleshooting - Outdoor Unit Related Si18-201286 Service Diagnosis3.3.23 Integrated Input Current StopOutdoor Unit IndicationL7Method of Malfunction

Strona 223 - (Low Pressure) indicator

Si18-201ii Table of ContentsNOTICE : Special specificationsModel RMK140JAVM has the following different specifications from the others. Take the impor

Strona 224 - 1 SYSTEM LAYOUT

Si18-201 SpecificationsSpecifications 17Notes:1.★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.5

Strona 225 - 2. Method of Field Set

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2873.3.24 Electronic ThermalOutdoor Unit IndicationL8Method of Malfunction DetectionE

Strona 226 - Operating Test 213

Troubleshooting - Outdoor Unit Related Si18-201288 Service Diagnosis3.3.25 Stall PreventionOutdoor Unit IndicationL9Method of Malfunction DetectionSta

Strona 227 - 2.1.2 Local Setting Mode No

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2893.3.26 Transmission Error between MicrocomputersOutdoor Unit IndicationLCMethod of

Strona 228

Troubleshooting - Outdoor Unit Related Si18-201290 Service Diagnosis3.3.27 Overvoltage, Low VoltageOutdoor Unit IndicationU2Method of Malfunction Dete

Strona 229

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2913.3.28 Transmission Error between Outdoor Unit and BP UnitOutdoor Unit IndicationU

Strona 230

Troubleshooting - Outdoor Unit Related Si18-201292 Service DiagnosisTroubleshootingCheck No.14Refer to P.308NOCould be outside causes other than error

Strona 231

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2933.3.29 Transmission Error between Indoor Unit and BP UnitOutdoor Unit IndicationU6

Strona 232 - 02 Set Fan Speed

Troubleshooting - Outdoor Unit Related Si18-201294 Service Diagnosis3.3.30 Transmission Error of DC FanOutdoor Unit IndicationU7Method of Malfunction

Strona 233 - 220 Operating Test

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2953.3.31 Operation Halt Due to Detection of Gas ShortageOutdoor Unit IndicationU0Met

Strona 234 - <KRP928A1S>

Troubleshooting - Outdoor Unit Related Si18-201296 Service DiagnosisTroubleshootingCheck No.3Refer to P.301CT CheckRefer to P.273NOCorrect connection

Strona 235 - 222 Operating Test

Specifications Si18-20118 Specifications1.2 BP UnitsNote:1. BP or Indoor Unit Max. Height - BP or Indoor Unit Min. Height → Max. 15m.Set up BP and IU

Strona 236 - 2P042644-17G

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2973.3.32 System MalfunctionOutdoor Unit IndicationUHMethod of Malfunction DetectionC

Strona 237 - 224 Operating Test

Troubleshooting - Outdoor Unit Related Si18-201298 Service Diagnosis3.3.33 Faulty BOX Thermistor MalfunctionOutdoor Unit IndicationP3Method of Malfunc

Strona 238 - Service Diagnosis 225

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2993.3.34 Faulty Fin ThermistorOutdoor Unit IndicationP4Method of Malfunction Detecti

Strona 239 - Air outlet

Troubleshooting - Outdoor Unit Related Si18-201300 Service Diagnosis3.4 How to Check3.4.1 Installation Condition CheckCheck No.13.4.2 Discharge Pressu

Strona 240 - Service Diagnosis 227

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 3013.4.3 Electronic Expansion Valve CheckCheck No.3 Conduct the followings to check t

Strona 241 - 1.2 Service Check Function

Troubleshooting - Outdoor Unit Related Si18-201302 Service Diagnosis3.4.5 Internal Wiring Check (1)Check No.5 Check the wiring at the sections marked

Strona 242

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 3033.4.6 Power Transistor Check (Capacitor Voltage Check)Check No.6 Power Transistor

Strona 243

Troubleshooting - Outdoor Unit Related Si18-201304 Service Diagnosis3.4.7 Power Transistor Output CheckCheck No.7 Measure the output current and volta

Strona 244 - 1.4 Troubleshooting

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 3053.4.8 Thermistor Resistance CheckCheck No.8 Remove the connectors of the thermisto

Strona 245 - 1.5 Troubleshooting Detail

Troubleshooting - Outdoor Unit Related Si18-201306 Service Diagnosis3.4.9 Inverter Units Refrigerant System CheckCheck No.93.4.10 Inverter Units Input

Strona 246 - Service Diagnosis 233

Si18-201 SpecificationsSpecifications 191.3 Indoor Units (for General)1.3.1 Cooling Only" Wall Mounted Type★Refer to Engineering Data Book"2

Strona 247 - Refer to P.305

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 3073.4.11 Electrolytic Capacitor Capacity CheckCheck No.113.4.12 Voltage Check when S

Strona 248 - Service Diagnosis 235

Troubleshooting - Outdoor Unit Related Si18-201308 Service Diagnosis3.4.13 Power Supply Waveforms CheckCheck No.13 Measure the power supply waveform b

Strona 249 - C4, C5, C9, CA

Si18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 3093.4.15 Inverter Units Hall IC CheckCheck No.15 1. Check the connector connection.2

Strona 250 - 1.5.5 Faulty Indoor Unit PCB

BP Unit Trouble Diagnosis Si18-201310 Service Diagnosis4. BP Unit Trouble Diagnosis4.1 PCB Parts Layout4.2 LED On Branch Provider Unit (Diagnosis LEDs

Strona 251 - 1.5.6 Faulty Indoor Unit PCB

Si18-201Removal Procedure 311Part 10Part 10Part 10Part 10Removal ProcedureRemoval ProcedureRemoval ProcedureRemoval Procedure1. For BPMK928B42 · 43 ..

Strona 252 - Service Diagnosis 239

For BPMK928B42 · 43 Si18-201312 Removal Procedure1. For BPMK928B42 · 431.1 Installation of Indoor UnitProcedure Warning Be sure to turn off all p

Strona 253 - CDK(X)25~60H)

Si18-201 For BPMK928B42 · 43Removal Procedure 3131.2 Opening of Electrical Box Cover and Removal of PCB MountProcedure Warning Be sure to turn of

Strona 254

For BPMK928B42 · 43 Si18-201314 Removal Procedure2. Removing the PCB"The PCB is treated for moisture resistance. Replace the PCB and its mount to

Strona 255 - Refer to P.309

Si18-201 For BPMK928B42 · 43Removal Procedure 3151.3 Removal of Motorized ValveProcedure Warning Be sure to turn off all power supplies before di

Strona 256 - Service Diagnosis 243

For BPMK928B42 · 43 Si18-201316 Removal Procedure4. Dismounting the motorized valve"Before taking this procedure, make sure there is no refrigera

Strona 257 - Controller)

Specifications Si18-20120 Specifications★ Refer to Engineering Data Book. "5.0kW Class50Hz 220-230-240V / 60Hz 220-230VModel FTKD50JVE FTKD50JVEA

Strona 258

Si18-201 For BPMK928B42 · 43Removal Procedure 3174Heat up the brazed sections of the motorized valve. Using pliers or the like, disconnect the valve.R

Strona 259 - 246 Service Diagnosis

For BPMK928B42 · 43 Si18-201318 Removal Procedure1.4 Removal of ThermistorProcedure Warning Be sure to turn off all power supplies before disasse

Strona 260 - Service Diagnosis 247

Si18-201 For BPMK928B42 · 43Removal Procedure 3193Insert the new thermistor terminal to the thermistor connector."Align the thermistor terminal w

Strona 261 - 248 Service Diagnosis

Outdoor Unit Si18-201320 Removal Procedure2. Outdoor Unit2.1 Removal of Outer PanelsProcedure Warning Be sure to wait 10 minutes or more after tu

Strona 262 - Service Diagnosis 249

Si18-201 Outdoor UnitRemoval Procedure 3212.2 Removal of PCB and Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turning

Strona 263

Outdoor Unit Si18-201322 Removal Procedure4. Disconnecting the compressor leads"Handle the sound insulation with enough care. It may damage the p

Strona 264 - 2.5.1 Explanation for Symbols

Si18-201 Outdoor UnitRemoval Procedure 3235. Detaching the electrical box1Remove the screws from the electrical box.2Lift the electrical box off the

Strona 265 - 2.6 Troubleshooting Detail

Outdoor Unit Si18-201324 Removal Procedure3Disconnect the two relay connectors on the side.4Remove the two lock screws from the front section.5Slide t

Strona 266 - Service Diagnosis 253

Si18-201 Outdoor UnitRemoval Procedure 3257. Detaching the filter PCB1The filter PCB is located as shown at right.2Disconnect all the connectors and r

Strona 267

Outdoor Unit Si18-201326 Removal Procedure8. Detaching the control PCB1The control PCB is located as shown at right.2The setting and self-diagnostic P

Strona 268 - Service Diagnosis 255

Si18-201 SpecificationsSpecifications 21★ Refer to Engineering Data Book. "7.1kW Class50Hz 220-230-240V / 60Hz 220-230VModel FTKD71JVE FTKD71JVEA

Strona 269 - 256 Service Diagnosis

Si18-201 Outdoor UnitRemoval Procedure 3275Remove the five locking card spacers and detach the control PCB."The back of the PCB has silicone comp

Strona 270 - Service Diagnosis 257

Outdoor Unit Si18-201328 Removal Procedure11.Detaching the fan control PCB1The fan control PCB is located as shown at right.Remove the four locking ca

Strona 271

Si18-201 Outdoor UnitRemoval Procedure 3292.3 Removal of Propeller Fans and Fan MotorsProcedure Warning Be sure to wait 10 minutes or more after

Strona 272

Outdoor Unit Si18-201330 Removal Procedure2. Dismounting the fan motors"In disconnecting the connectors, do not pull the leads, but hold the conn

Strona 273 - 260 Service Diagnosis

Si18-201 Outdoor UnitRemoval Procedure 3312.4 Removal of ThermistorProcedure Warning Be sure to wait 10 minutes or more after turning off all pow

Strona 274

Outdoor Unit Si18-201332 Removal Procedure2.5 Removal of Motorized ValveProcedure Warning Be sure to wait 10 minutes or more after turning off al

Strona 275 - 7 seg. display

Si18-201 Outdoor UnitRemoval Procedure 3334Disconnect the earth wire.WarningIf refrigerant gas leaks during the job, ventilate the room. (Bear in mind

Strona 276 - 3.3 Troubleshooting Detail

Outdoor Unit Si18-201334 Removal Procedure2.6 Removal of Sound InsulationProcedure Warning Be sure to wait 10 minutes or more after turning off a

Strona 277 - 3.3.2 Compressor Lock

Si18-201 Outdoor UnitRemoval Procedure 3353Draw out the sound insulation cover from the bottom of the compressor.4Undo the two points of the sound ins

Strona 278 - 3.3.3 Fan Lock / Overcurrent

Outdoor Unit Si18-201336 Removal Procedure2.7 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after turning off all pow

Strona 279 - 266 Service Diagnosis

Specifications Si18-20122 Specifications" Duct Connected Type★Refer to Engineering Data Book."2.5kW Class50Hz 220-230-240V / 60Hz 220-230VMo

Strona 280 - Service Diagnosis 267

Si18-201 Outdoor UnitRemoval Procedure 3373Remove the three lock nuts from the compressor.4Remove the three lock bolts from the compressor."This

Strona 281 - 268 Service Diagnosis

Outdoor Unit Si18-201338 Removal Procedure2.8 Removal of 4-way ValveProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Strona 282 - 3.3.7 LP Drop Error

Si18-201 Outdoor UnitRemoval Procedure 3393Remove the lock screw from the piping assembly.4Disconnect the pipes form the accumulator (at points A and

Strona 283 - 270 Service Diagnosis

Outdoor Unit Si18-201340 Removal Procedure7Cut off the compressor's discharge pipe (at point L) with the pipe cutter.8Disconnect the 4-way valve

Strona 284 - Service Diagnosis 271

Si18-201 Outdoor UnitRemoval Procedure 3412. Disconnecting the 4-way valve1Remove the screw.2Get rid of the brazing at points A, B, C and D. Disconnec

Strona 285 - 272 Service Diagnosis

Indoor Unit Si18-201342 Removal Procedure3. Indoor Unit3.1 Refer following table for indoor unit removal procedureModel Number Service Manual PageFTK2

Strona 286 - Service Diagnosis 273

Si18-201Caution Before Operation 343Part 11Part 11Part 11Part 11Cautions before OperationCautions before OperationCautions before OperationCautions be

Strona 287

Installation Si18-201344 Caution Before Operation1. Installation1.1 Outdoor Unit1 INSTALLATION PROCEDURE1. Carrying-in• Take care not to let your hand

Strona 288

Si18-201 InstallationCaution Before Operation 345(C) Where there are obstacles on both suction and discharge sides: Pattern 1 Where the obstacles o

Strona 289

Installation Si18-201346 Caution Before Operation1.2 BP UnitINSTALLATIONThree-sided view (product dimensions and attachment bolt pitch)• This unit may

Strona 290

Si18-201 SpecificationsSpecifications 23★Refer to Engineering Data Book."5.0kW Class50Hz 220-230-240V / 60Hz 220-230VModel CDK50HAVE CDK50HAVEARa

Strona 291

Si18-201 InstallationCaution Before Operation 347Hanging bolt (M10 or M8)Six-sided nut (M10 or M8)Hanger metal 7Hanger metal 7Screws 8Screws 8

Strona 292

Wiring Si18-201348 Caution Before Operation2. Wiring2.1 Outdoor UnitELECTRIC WIRING CONNECTION1. Connection electric wire treatment ( CAUTION)Followin

Strona 293

Si18-201 WiringCaution Before Operation 3492. BP unit connection priorityWhen connecting to the BP unit, always start the connection with BP1 of the t

Strona 294 - 3.3.19 Abnormal LP Error

Wiring Si18-201350 Caution Before Operation2.2 BP Unit• Connect refrigerant pipes and connection wires to the appropriate ports marked with matching

Strona 295 - 282 Service Diagnosis

Si18-201 WiringCaution Before Operation 351(5) Follow the instruction on the wiring nameplate to connect the connection wires for indoor/outdoor units

Strona 296 - Service Diagnosis 283

Wiring Si18-201352 Caution Before Operation2.3 Outdoor Unit Rotary Switch Setting* RAM View MonitorRSW1 RSW2 Remarks Unit0 0 Latest (status) error cod

Strona 297 - 284 Service Diagnosis

Si18-201 WiringCaution Before Operation 353RSW1 RSW2 Remarks Unit4 1 Current BP 1 Room-A gas pipe temperature Temp. offset 40h4 2 Current BP 1 Room-B

Strona 298 - Service Diagnosis 285

Others Si18-201354 Caution Before Operation3. Others3.1 Explanation for FTK(X)25/35J Series3.1.1 Test Run from the Remote Controller (For Heat Pump Mo

Strona 299 - 286 Service Diagnosis

Si18-201 OthersCaution Before Operation 3553.1.2 Method of Operating Air Conditioners Individually (When Two Units are Installed in One Room) For Cool

Strona 300 - 3.3.24 Electronic Thermal

Others Si18-201356 Caution Before Operation3.1.5 Adjusting the Angle of the Intelligent-eye Sensor"Once installation of the indoor unit is comple

Strona 301 - 3.3.25 Stall Prevention

Specifications Si18-20124 Specifications" Floor/Ceiling Suspended Dual Type★Refer to Engineering Data Book."2.5kW Class50Hz 220-230-240V / 6

Strona 302 - Service Diagnosis 289

Si18-201 OthersCaution Before Operation 3573.2 Explanation for FTK(X)50/60H and CDK(X)25~60H Series3.2.1 Test Run from the Remote Controller (For Heat

Strona 303 - 290 Service Diagnosis

Others Si18-201358 Caution Before Operation3.2.3 Centralized Control (For KRC72, KRP411A1S and KRP410A11S)For an explanation on usage, see the option

Strona 304 - Service Diagnosis 291

Si18-201Appendix 359Part 12Part 12Part 12Part 12AppendixAppendixAppendixAppendix1. Piping Diagrams...

Strona 305 - Refer to P.308

Piping Diagrams Si18-201360 Appendix1. Piping Diagrams1.1 Outdoor UnitsRMK140JVMC9 (8) / RMK140JVMT9 / RMK140JZVMARMK140JAVMTHERMISTORLIQUID PIPEOUTDO

Strona 306 - Service Diagnosis 293

Si18-201 Piping DiagramsAppendix 361RMX140JVMC9 (8) / RMX140JVMT9 / RMX140JVMB / RMX140JZVMBTHERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDIS

Strona 307 - 294 Service Diagnosis

Piping Diagrams Si18-201362 Appendix1.2 BP UnitsBPMK928B42BPMK928B43REFRIGERANT FLOWOUTDOOR UNITOUTDOOR UNIT(19.1CuT)(9.5CuT)COOLINGHEATINGEXPANSION V

Strona 308 - Service Diagnosis 295

Si18-201 Piping DiagramsAppendix 3631.3 Indoor UnitsFTK25 / 35JVE (A) 9, FTX25 / 35JVEA9, FTK25 / 35JVEC, FTX25 / 35JVEC, FTK25 / 35JAVET, FTX25 / 35J

Strona 309 - Refer to P.273

Piping Diagrams Si18-201364 AppendixFTXD50 / 60 / 71JVEA (9) , FTXD50 / 60 / 71JVET, FTXD50 / 60 / 71JV1BCDK25 / 35 / 50 / 60HAVE (A) , CDK25 / 35 / 5

Strona 310 - 3.3.32 System Malfunction

Si18-201 Piping DiagramsAppendix 365CDX25 / 35 / 50 / 60HAVEA, CDX25 / 35 / 50 / 60HAVEC, CDX25 / 35 / 50 / 60HAV1NB,CDX25 / 35 / 50 / 60JV1NB, CDX 25

Strona 311 - 298 Service Diagnosis

Piping Diagrams Si18-201366 AppendixFLK50 / 60JVEA (9)FLX25 / 35HVEA , FLX25 / 35 / 50 / 60HVEC, FLX25 / 35 / 50 / 60HVET,FLX25 / 35HV1NBREFRIGERANT F

Strona 312 - 3.3.34 Faulty Fin Thermistor

Si18-201 SpecificationsSpecifications 25★Refer to Engineering Data Book."5.0kW Class50Hz 220-230-240V / 60Hz 220-230VModel FLK50HVE FLK50JVEA9Rat

Strona 313 - 3.4 How to Check

Si18-201 Piping DiagramsAppendix 367FLX50 / 60JVEA (9) , FLX50 / 60JV1B FHYC35 / 50 / 60 / 71KVE9, FHYC35 / 50 / 60 / 71KV1C9, FDYM60 / 03FAV1 (C) , F

Strona 314 - Service Diagnosis 301

Piping Diagrams Si18-201368 AppendixFTK50 / 60HVEC, FTX50 / 60HVECFTXD25 / 35KZV1BHEAT EXCHANGERON HEAT EXCH.ON LIQUID PIPEFAN MOTORCROSS FLOW FANINDO

Strona 315 - 302 Service Diagnosis

Si18-201 Piping DiagramsAppendix 369FVX25 / 35KZV1BFVX(K)35 12.7CuTFVX(K)25 9.5CuTFIELD PIPINGFIELD PIPING(6.4CuT)REFRIGERANT FLOWINDOOR UNIT7.9CuTCRO

Strona 316

Wiring Diagrams Si18-201370 Appendix2. Wiring Diagrams2.1 Outdoor UnitsRMK140JVMC9 (8)RMX140JVMC9 (8)NACPHPSPMLED2~LED4PCB1~PCB4ACNM1CC900~C927C1RLH1P

Strona 317 - 2 second 5 second

Si18-201 Wiring DiagramsAppendix 371RMK140JVMT9RMX140JVMT9OIS15 :SOLID STATE RELAYN :NEUTRALM1F,M2F :FAN MOTORM1C :COMPRESSOR MOTORLED2~LED4 :7 SEGMEN

Strona 318

Wiring Diagrams Si18-201372 AppendixRMK140JAVMRMX140JVMB, RMX140JZVMBN : NEUTRALACP : CONNECTORHPS : HIGH PRESSURE SWPM : POWER MODULELED2~LED4 : 7 SE

Strona 319 - 306 Service Diagnosis

Si18-201 Wiring DiagramsAppendix 373RMK140JZVMANACPHPSPMLED2~PCB1~ACNM1CC900~C1RLH1P~L900~CT900~FG1~F1UOIS15H102~M1F,M2FL1R,L2RBPPOWERBPBP222333111FIE

Strona 320 - Check No.12

Wiring Diagrams Si18-201374 Appendix2.2 BP UnitsBPMK928B42BPMK928B4312TO INDOOR UNITSPCB :PRINTED CIRCUIT BOARDFU1~3 :FUSEH1P~H6P:PILOT LAMPR1T~R4T :T

Strona 321 - 308 Service Diagnosis

Si18-201 Wiring DiagramsAppendix 3752.3 Indoor Units2.3.1 Cooling OnlyFTK25 / 35JVE (A) 9, FTK25 / 35JAVETFTK25 / 35JVECTURNED OFF AND THEN BACKTHE MA

Strona 322 - Service Diagnosis 309

Wiring Diagrams Si18-201376 AppendixFTKD50 / 60 / 71JVE (A) (9) , FTKD50 / 60 / 71JVETFTK50 / 60HVECRECEIVERSIGNALLEDH1PPCB3PCB4S1WCONTROLLERLEDH2PWIR

Strona 323 - 4. BP Unit Trouble Diagnosis

Specifications Si18-20126 Specifications" Ceiling Mounted Cassette Type (SkyAir)★Refer to Engineering Data Book."3.75kW Class · 5.2kW Class5

Strona 324 - Removal Procedure 311

Si18-201 Wiring DiagramsAppendix 377CDK25 / 35 / 50 / 60HAVE (A) , CDK25 / 35 / 50 / 60HAVETCDK25 / 35 / 50 / 60HAVECRECEIVERSIGNALLEDPCB2H1PCONTROLLE

Strona 325 - 1. For BPMK928B42 · 43

Wiring Diagrams Si18-201378 AppendixFLK25 / 35 / 50 / 60HVE (A) , FLK25 / 35 / 50 / 60HVETFLK25 / 35 / 50 / 60HVECSIGNALRECEIVERLEDH1PPCB4PCB3CONTROLL

Strona 326

Si18-201 Wiring DiagramsAppendix 379FLK50 / 60JVEA (9)SIGNALRECEIVERLEDH1PPCB4PCB3CONTROLLERWIRELESSLEDH2PS1WREMOTELEDH3PR1TS31t˚S27S25S24S26R2TS32t˚S

Strona 327

Wiring Diagrams Si18-201380 AppendixFHYC35 / 50 / 60 / 71KVE9 3D005668C

Strona 328

Si18-201 Wiring DiagramsAppendix 381FHYC35 / 50 / 60 / 71KV1C9

Strona 329

Wiring Diagrams Si18-201382 AppendixFDYM60 / 03FAV1FDYM60 / 03FAVAL C : 3D019816D(OPTION)

Strona 330 - Step Procedure Points

Si18-201 Wiring DiagramsAppendix 383FDYM60 / 03FAV1C

Strona 331 - 1.4 Removal of Thermistor

Wiring Diagrams Si18-201384 Appendix2.3.2 Heat PumpFTX25 / 35JVEA9, FTX25 / 35JAVET, FTX25 / 35JAV1NB, FTXD25 / 35KZV1BFTXD50 / 60 / 71JVEA (9) , FTXD

Strona 332 - Removal Procedure 319

Si18-201 Wiring DiagramsAppendix 385CDX25 / 35 / 50 / 60HAVEA, CDX25 / 35 / 50 / 60HAV1NB, CDX25 / 35 / 50 / 60JV1NBFLX25 / 35HVEA, FLX25 / 35 / 50 /

Strona 333 - 2. Outdoor Unit

Wiring Diagrams Si18-201386 AppendixFLX50 / 60JVEA (9) , FLX50 / 60JV1BFTX25 / 35JVECSIGNALRECEIVERLEDH1PPCB4PCB3CONTROLLERLEDH2PS1WWIRELESSREMOTELEDH

Strona 334

Si18-201Table of Contents iii1. Introduction ...ix1.1 Safety

Strona 335

Si18-201 SpecificationsSpecifications 27"""" Duct Connected Type (SkyAir)★Refer to Engineering Data Book."6.15kW Class · 7.7k

Strona 336

Si18-201 Wiring DiagramsAppendix 387FTX50 / 60HVECCDX25 / 35 / 50 / 60HAVEC, CDX25 / 35JVECRECEIVERSIGNALH1PLEDPCB3PCB4S1WCONTROLLERLEDH2PWIRELESSREMO

Strona 337

Wiring Diagrams Si18-201388 AppendixFLX25 / 35 / 50 / 60HVECFVX25 / 35KZV1BRECEIVERSIGNALH1PLEDPCB4PCB3H2PLEDS7WWIRELESSREMOTECONTROLLERH3PLEDR1TS31t˚

Strona 338

Si18-201Index iIndexIndexIndexIndexSymbols* ...237, 238, 239, 240Numerics3 Step Flow ...

Strona 339

Si18-201ii IndexFaulty Outside Air Thermistor ...274Faulty PCB ...

Strona 340

Si18-201Index iiiOperation Halt Due to Detection of Thermistor or Related Abnormality ...236Operation Halt Due to D

Strona 341 - 328 Removal Procedure

Si18-201iv IndexTroubleshooting with the LED Indication ...227Troubleshooting with the Operation Lamp ...226UU0 ...

Strona 342

Si18-201Drawings & Flow Charts vDrawings & Flow ChartsDrawings & Flow ChartsDrawings & Flow ChartsDrawings & Flow ChartsNumerics1-

Strona 343

Si18-201vi Drawings & Flow ChartsFHYC35~71KV SeriesPrinted Circuit Board ...74Field SettingWired Remote Contro

Strona 344 - 2.4 Removal of Thermistor

Si18-201Drawings & Flow Charts viiOperation Halt Due to the Freeze Protection Function ...233Outdoor Unit Moto

Strona 345

Si18-201viii Drawings & Flow ChartsTroubleshooting with the LED Indication ...227UUsing the remote controller for trial operation ...

Strona 346 - Removal Procedure 333

Specifications Si18-20128 Specifications1.3.2 Heat Pump"""" Wall Mounted Type★ Refer to Engineering Data Book."2.5kW Class ·

Strona 347

Head office:Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,Kita-ku, Osaka, 530-8323 JapanTokyo office:Shinjuku Sumitomo Bldg., 6-1 Nishi-Shinjuku2-c

Strona 348

Si18-201 SpecificationsSpecifications 29★ Refer to Engineering Data Book."7.1kW Class50Hz 220-230-240V / 60Hz 220-230VModelFTXD71JVEACooling Heat

Strona 349 - 2.7 Removal of Compressor

Specifications Si18-20130 Specifications" Duct Connected Type★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz 220-230-240V / 6

Strona 350

Si18-201 SpecificationsSpecifications 31" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz

Strona 351 - 2.8 Removal of 4-way Valve

Specifications Si18-20132 Specifications" Ceiling Mounted Cassette Type (SkyAir)★Refer to Engineering Data Book."3.75kW Class · 5.2kW Class5

Strona 352

Si18-201 SpecificationsSpecifications 33" Duct Connected Type (SkyAir)★Refer to Engineering Data Book."6.0kW Class · 7.7kW Class50Hz 220-230

Strona 353 - 340 Removal Procedure

Specifications Si18-20134 Specifications1.4 Indoor Units (for China)1.4.1 Cooling Only" Wall Mounted Type★Refer to Engineering Data Book.50Hz 220

Strona 354

Si18-201 SpecificationsSpecifications 35" Duct Connected Type★Refer to Engineering Data Book.50Hz 220VModel CDK25HAVEC CDK35HAVECRating Capacity

Strona 355 - 3. Indoor Unit

Specifications Si18-20136 Specifications" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book.50Hz 220VModel FLK25HVEC FLK35HVECRa

Strona 356 - Caution Before Operation 343

Si18-201iv Table of ContentsPart 5 Main Functions Outdoor Unit / BP Unit... 1011. Refrigerant System and Function of Functional

Strona 357 - 1. Installation

Si18-201 SpecificationsSpecifications 37" Ceiling Mounted Cassette Type (SkyAir)"""" Duct Connected Type (SkyAir)★Refer to En

Strona 358 - Caution Before Operation 345

Specifications Si18-20138 Specifications1.4.2 Heat Pump"""" Wall Mounted Type★Refer to Engineering Data Book.50Hz 220VModelFTX25JV

Strona 359 - INSTALLATION

Si18-201 SpecificationsSpecifications 39" Duct Connected Type★Refer to Engineering Data Book.50Hz 220VModelCDX25HAVEC CDX35HAVECCooling Heating C

Strona 360 - INSTALLATION OF THE MAIN UNIT

Specifications Si18-20140 Specifications" Duct Connected Type★Refer to Engineering Data Book.50Hz 220VModelCDX25JVEC CDX35JVECCooling Heating Coo

Strona 361 - 2. Wiring

Si18-201 SpecificationsSpecifications 41" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book.50Hz 220VModelFLX25HVEC FLX35HVECCo

Strona 362 - 1, 2, and 3 all match

Specifications Si18-20142 Specifications" Ceiling Mounted Cassette Type (SkyAir)" Duct Connected Type (SkyAir)★Refer to Engineering Data Boo

Strona 363 - CONNECTING THE WIRING

Si18-201 SpecificationsSpecifications 431.5 Indoor Units (for Taiwan)1.5.1 Cooling Only" Wall Mounted Type★Refer to Engineering Data Book. "

Strona 364 - Operating Test

Specifications Si18-20144 Specifications★Refer to Engineering Data Book."7.1kW Class60Hz 220VModel FTKD71JVETRating Capacity kW 7.1Front Panel Co

Strona 365 - 352 Caution Before Operation

Si18-201 SpecificationsSpecifications 45" Duct Connected Type★Refer to Engineering Data Book.60Hz 220VModel CDK25HAVET CDK35HAVETRating Capacity

Strona 366 - Caution Before Operation 353

Specifications Si18-20146 Specifications" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book.60Hz 220VModel FLK25HVET FLK35HVETRa

Strona 367 - 3. Others

Si18-201Table of Contents v3.38 JIS Mode ...1673.39 Pump Do

Strona 368

Si18-201 SpecificationsSpecifications 47" Ceiling Mounted Cassette Type (SkyAir)"""" Duct Connected Type (SkyAir)★Refer to En

Strona 369 - 356 Caution Before Operation

Specifications Si18-20148 Specifications1.5.2 Heat Pump"""" Wall Mounted Type★Refer to Engineering Data Book."2.5kW Class · 3

Strona 370

Si18-201 SpecificationsSpecifications 49★Refer to Engineering Data Book."7.1kW Class60Hz 220VModelFTXD71JVETCooling HeatingRating Capacity kW 7.1

Strona 371

Specifications Si18-20150 Specifications" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book.60Hz 220VModelFLX25HVET FLX35HVETCo

Strona 372 - Appendix 359

Si18-201 SpecificationsSpecifications 51" Ceiling Mounted Cassette Type (SkyAir)" Duct Connected Type (SkyAir)★Refer to Engineering Data Boo

Strona 373 - 1. Piping Diagrams

Specifications Si18-20152 Specifications1.6 Indoor Units (for Europe)1.6.1 Heat Pump" Wall Mounted Type★Refer to Engineering Data Book."2.5k

Strona 374 - Appendix 361

Si18-201 SpecificationsSpecifications 53★Refer to Engineering Data Book."5.0kW Class · 6.0kW Class50Hz 230VModelFTXD50JV1B FTXD60JV1BCooling Heat

Strona 375

Specifications Si18-20154 Specifications" Duct Connected Type★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz 230VModelCDX25HA

Strona 376 - INDOOR UNIT

Si18-201 SpecificationsSpecifications 55★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz 230VModelCDX25JV1NB CDX35JV1NBCooling Heat

Strona 377

Specifications Si18-20156 Specifications" Floor / Ceiling Suspended Dual Type★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz

Strona 378

Si18-201vi Table of Contents1.3 Code Indication on the Remote Controller ...2301.4 Troubleshooting...

Strona 379

Si18-201 SpecificationsSpecifications 57" Floor Standing Type★Refer to Engineering Data Book."2.5kW Class · 3.5kW Class50Hz 230VModelFVX25KZ

Strona 380

Specifications Si18-20158 Specifications

Strona 381

Si18-201Printed Circuit Board Connector Wiring Diagram and Name 59Part 3Part 3Part 3Part 3Printed Circuit BoardPrinted Circuit BoardPrinted Circuit Bo

Strona 382

Printed Circuit Board Connector Wiring Diagram and Name Si18-20160 Printed Circuit Board Connector Wiring Diagram and Name1. Printed Circuit Board Con

Strona 383 - 3D024908C

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 611.2 Outdoor Unit RMK (X) 140

Strona 384 - Appendix 371

Printed Circuit Board Connector Wiring Diagram and Name Si18-20162 Printed Circuit Board Connector Wiring Diagram and NameOther DesignationsPrinted Ci

Strona 385 - 372 Appendix

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 63Printed Circuit Board (2)(Fi

Strona 386 - RMK140JZVMA

Printed Circuit Board Connector Wiring Diagram and Name Si18-20164 Printed Circuit Board Connector Wiring Diagram and Name1.3 FTK25 / 35J Series, FTX2

Strona 387 - 2.2 BP Units

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 65Printed Circuit Board (1)~(3

Strona 388 - 2.3 Indoor Units

Printed Circuit Board Connector Wiring Diagram and Name Si18-20166 Printed Circuit Board Connector Wiring Diagram and Name1.4 FTK50~60HV Series, FTKD5

Strona 389 - 376 Appendix

Si18-201Table of Contents viiPart 12Appendix...3591. Piping Diagrams...

Strona 390 - CDK25 / 35 / 50 / 60HAVEC

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 67Printed Circuit Board (2)(Po

Strona 391 - 378 Appendix

Printed Circuit Board Connector Wiring Diagram and Name Si18-20168 Printed Circuit Board Connector Wiring Diagram and Name1.5 CDX25~60HAV Series, CDK2

Strona 392 - Appendix 379

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 69Printed Circuit Board (1)~(3

Strona 393 - 3D005668C

Printed Circuit Board Connector Wiring Diagram and Name Si18-20170 Printed Circuit Board Connector Wiring Diagram and Name1.6 FLK25~60HV Series, FLX25

Strona 394 - FHYC35 / 50 / 60 / 71KV1C9

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 71Printed Circuit Board (1)(Co

Strona 395 - (OPTION)

Printed Circuit Board Connector Wiring Diagram and Name Si18-20172 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board (3)(Di

Strona 396 - FDYM60 / 03FAV1C

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 731.7 FHYC35~71KV SeriesCoolin

Strona 397 - 3D020026E

Printed Circuit Board Connector Wiring Diagram and Name Si18-20174 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board

Strona 398 - Appendix 385

Si18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 751.8 FDYM60FA, FDYM03FA Serie

Strona 399 - 386 Appendix

Printed Circuit Board Connector Wiring Diagram and Name Si18-20176 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board

Strona 400 - Appendix 387

Si18-201viii Table of Contents

Strona 401 - 388 Appendix

Si18-201Main Functions 77Part 4Part 4Part 4Part 4Main FunctionsMain FunctionsMain FunctionsMain FunctionsIndoor UnitIndoor UnitIndoor UnitIndoor Unit1

Strona 402 - IndexIndex

Main Functions Si18-20178 Main Functions1. Main Functions1.1 Main Functions in Split Type1.1.1 Power-Airflow Flap & DiffuserFor FTK, FTX50/60 H Se

Strona 403

Si18-201 Main FunctionsMain Functions 79Temperature Distribution< Conditions >Outside temperature: 7ºCDB, thermostat setting: 23ºC, air flow set

Strona 404 - Index iii

Main Functions Si18-20180 Main FunctionsFlap Angle During HeatingDuring CoolingCapable of sending air to the center of a room even if it is installed

Strona 405

Si18-201 Main FunctionsMain Functions 81Cooling, Dry, Operation (For Cooling Only Model)Cooling, Dry, Heating Operation (For Heat Pump Model)Note: Not

Strona 406 - Drawings & Flow Charts

Main Functions Si18-20182 Main Functions1.1.4 Wide Angle Flaps, Louvers and Auto-SwingFor FTK(X)25/35J Series OnlyOutline of the ActionIt can be comma

Strona 407

Si18-201 Main FunctionsMain Functions 83Heating (In The Case of Swing-OFF Start)Heating (In The Case of Swing-ON Start)Note: The flaps remain in the p

Strona 408

Main Functions Si18-20184 Main Functions1.1.6 Fan Speed Control for Indoor UnitsFor FTK(X)25/35J, FTK(X)50/60 H SeriesControl ModeThe airflow rate can

Strona 409

Si18-201 Main FunctionsMain Functions 851.1.7 ON/OFF Button on Indoor UnitFor FTK, FTX50/60 H Series OnlyAn ON/OFF switch is provided on the front pan

Strona 410 - Printed in Japan 10/2002 AK

Main Functions Si18-20186 Main FunctionsClean the Front Grille."You may wipe it with a soft cloth soaked in water."Only neutral detergent ma