System control Si18-201
168 Main Functions
3.39 Pump Down Operation
Outline When the Pump-down button is pressed, the following control is provided to collect refrigerant in
the receiver.
Details
4-way valve
Command frequency
Outdoor unit upper fan
Outdoor unit lower fan
EVP
EVL
EVG
Each room motorized valve
BP bypass motorized valve
ON
OFF
30 Hz
45Hz
775rpm
715rpm
450 pulses 450 pulses
0 pulse
0 pulse
450 pulses
450 pulses
450 pulses
450 pulses
0 pulse
Max. 3 min.
or
LP < 0.5 kg/cm²
1.5min
Max. 5 min.
or
LP < 1.5 kg /cm²
or
Suction superheat degree (SHS) > 10˚C
(M1052)