System control Si18-201
160 Main Functions
Details The heat exchanger intermediate temperature and liquid pipe temperature are detected at every
sampling time of 60 sec of the heating SC control.
The range of target SC : 3°C
≤
SC1
≤
8°C
The motorized valve of operating room unit is operated to obtain the target SC.
Target SC > Current SC : Evr closed
Target SC < Current SC : Evr opened
0
1
2
3
4
5
6
7
8
9
10
0 50 100 150
Capacity supply QCOMP (%)
Target SC
(M1050)