EDUS301214-N
RWEYQ-PTJU
3 phase
208/230V, 60Hz
RWEYQ-PYDN
3 phase
460V, 60Hz
Installation
Przeglądanie stron 0
1 2 3 4 5 6 ... 94 95

Podsumowanie treści

Strona 1 - Installation

EDUS301214-N RWEYQ-PTJU3 phase 208/230V, 60HzRWEYQ-PYDN3 phase460V, 60HzInstallation

Strona 2 - Outside Units

EDUS301214-N Installation ManualInstallation of Outside Units 9parts other than those specified by Daikin are used, fire or explosion could result.• D

Strona 3 - 1. Center of Gravity

Installation Manual EDUS301214-N10 Installation of Outside Units3P153897-12X2. INTRODUCTIONThis installation manual concerns VRV inverters of the Daik

Strona 4 - 2. Installation Manual

EDUS301214-N Installation ManualInstallation of Outside Units 113P153897-12X2-5 Technical specifications (1)(1)Refer to the engineering data book for

Strona 5 - <RWEYQ-PTJU>

Installation Manual EDUS301214-N12 Installation of Outside Units3P153897-12X3. SELECTION OF LOCATIONThis unit does not have specifications for outdoor

Strona 6

EDUS301214-N Installation ManualInstallation of Outside Units 133P153897-12XWARNINGDo not install in the following locations.•Locations such as kitche

Strona 7

Installation Manual EDUS301214-N14 Installation of Outside Units3P153897-12X7. HANDLING OF THE BRAZED PLATE-TYPE HEAT EXCHANGERCAUTIONA brazed plate-t

Strona 8

EDUS301214-N Installation ManualInstallation of Outside Units 153P153897-12X[NOTES](1) The circle marks in the columns for corrosion or scale to devel

Strona 9

Installation Manual EDUS301214-N16 Installation of Outside Units3P153897-12X8-3 General• Make sure to connect the power supply wire to the power suppl

Strona 10

EDUS301214-N Installation ManualInstallation of Outside Units 173P153897-12X2. PC board (A1P)3. Mount an insulation sleeve.4. Connection of interlock

Strona 11 - 2. INTRODUCTION

Installation Manual EDUS301214-N18 Installation of Outside Units3P153897-12XCAUTION¢Precautions when laying power supply wiring²Use round pressure ter

Strona 12 - 2-6 Electrical specifications

EDUS301214-NInstallation of Outside Units 1Installation ofOutside Units1. Center of Gravity ...

Strona 13 - 3. SELECTION OF LOCATION

EDUS301214-N Installation ManualInstallation of Outside Units 193P153897-12X• Incorrect installation may cause breakage of outside unit.(Refer to figu

Strona 14 - 6. WATER PIPING WORK

Installation Manual EDUS301214-N20 Installation of Outside Units3P153897-12X¢Cautions for installation of multiple outside units²1.The piping between

Strona 15 - TYPE HEAT EXCHANGER

EDUS301214-N Installation ManualInstallation of Outside Units 213P153897-12X9-5 Example of connection In case of a system of switching between coolin

Strona 16 - 8. FIELD WIRING

Installation Manual EDUS301214-N22 Installation of Outside Units3P153897-12X9-6 Air tight test and vacuum dryingThe units were checked for leaks by th

Strona 17 - 8-3 General

EDUS301214-N Installation ManualInstallation of Outside Units 233P153897-12X2.After the vacuum drying is finished, charge the additional refrigerant i

Strona 18 - 3P153897-12X

Installation Manual EDUS301214-N24 Installation of Outside Units3P153897-12X10. CHECKS AFTER INSTALLATIONWARNING• Never connect power supply wiring to

Strona 19 - 9. REFRIGERANT PIPING

EDUS301214-N Installation ManualInstallation of Outside Units 253P153897-12X¢Cautions for check operation²• If the system is started within about 12 m

Strona 20 - 9-3 Pipe connection

Installation Manual EDUS301214-N26 Installation of Outside Units3P153897-12XPay a special attention to the place, such as a basement, etc. where refri

Strona 21

EDUS301214-N Installation ManualInstallation of Outside Units 272.2 RWEYQ-PTJU (In case of manufacturing code: RWEYQ-PTJU9)3P153897-15T123figure 11245

Strona 22 - 9-5 Example of connection

Installation Manual EDUS301214-N28 Installation of Outside Units3P153897-15T1234567TO OUT/D UNIT TO OUT/D UNIT TO OUT/D UNITF1F2F1 F2F1 F2 F1 F2LOW NO

Strona 23 - Charge with the tank upright

Center of Gravity EDUS301214-N2 Installation of Outside Units1. Center of GravityRWEYQ72PTJU / RWEYQ84PTJUUnit: in. (mm)RWEYQ72PYDN/RWEYQ84PYDNUnit: i

Strona 24

EDUS301214-N Installation ManualInstallation of Outside Units 293P153897-15T132AB[A-arrow view] [B-arrow view]figure 21figure 20figure 195431278911106

Strona 25 - 11. TEST RUN

Installation Manual EDUS301214-N30 Installation of Outside Units3P153897-15Tfigure 251122334456[Heat pump system] [Heat recovery system]45321figure 24

Strona 26

EDUS301214-N Installation ManualInstallation of Outside Units 311. SAFETY CONSIDERATIONSRead these SAFETY CONSIDERATIONS for Installation carefullybef

Strona 27

Installation Manual EDUS301214-N32 Installation of Outside Unitsparts other than those specified by Daikin are used, fire or explosion could result.•

Strona 28 - 3P153897-15T

EDUS301214-N Installation ManualInstallation of Outside Units 332. INTRODUCTIONThis installation manual concerns VRV inverters of the Daikin RWEYQ-P s

Strona 29 - F1 F2 F1 F2

Installation Manual EDUS301214-N34 Installation of Outside Units3P153897-15T2-5 Technical specifications (1)(1)Refer to the engineering data book for

Strona 30

EDUS301214-N Installation ManualInstallation of Outside Units 353P153897-15T3. SELECTION OF LOCATIONThis unit does not have specifications for outdoor

Strona 31

Installation Manual EDUS301214-N36 Installation of Outside Units3P153897-15TNOTE• If the unit is to be installed on a roof, check the strengt

Strona 32 - 1. SAFETY CONSIDERATIONS

EDUS301214-N Installation ManualInstallation of Outside Units 373P153897-15T7-3 Daily service and maintenance1.Management of water qualityThe plate ty

Strona 33

Installation Manual EDUS301214-N38 Installation of Outside Units3P153897-15T8. FIELD WIRINGNOTE• All field wiring and components must be installed by

Strona 34

EDUS301214-N Installation ManualInstallation of Outside Units 32. Installation Manual2.1 RWEYQ-PTJU/RWEYQ-PYDN3P153897-12X12 (PTJU)2 (PYDN)figure 1124

Strona 35

EDUS301214-N Installation ManualInstallation of Outside Units 393P153897-15TConnect the wire to the terminal block on PC board with care since too muc

Strona 36

Installation Manual EDUS301214-N40 Installation of Outside Units3P153897-15TField line connection:L1, L2, L3, phase of the power supply wiring should

Strona 37

EDUS301214-N Installation ManualInstallation of Outside Units 419. REFRIGERANT PIPINGCAUTIONAfter completing installation, be sure to open the valves.

Strona 38

Installation Manual EDUS301214-N42 Installation of Outside Units3P153897-15TPrecautions when connecting pipes• See the following table for flare part

Strona 39

EDUS301214-N Installation ManualInstallation of Outside Units 433P153897-15T13 English9-5 Example of connection∗ In case of a system of switching betw

Strona 40

Installation Manual EDUS301214-N44 Installation of Outside Units3P153897-15T9-6 Air tight test and vacuum dryingThe units were checked for leaks by th

Strona 41

EDUS301214-N Installation ManualInstallation of Outside Units 453P153897-15T2.After the vacuum drying is finished, charge the additional refrigerant i

Strona 42

Installation Manual EDUS301214-N46 Installation of Outside Units3P153897-15T10. CHECKS AFTER INSTALLATIONWARNING• Never connect power supply wiring to

Strona 43

EDUS301214-N Installation ManualInstallation of Outside Units 473P153897-15T〈Cautions for check operation〉• If the system is started within about 12 m

Strona 44

Installation Manual EDUS301214-N48 Installation of Outside Units3P153897-15TPay a special attention to the place, such as a basement, etc. where refri

Strona 45

Installation Manual EDUS301214-N4 Installation of Outside Units3P153897-12XA B CF1 F1F2 F2 Q1 Q2F1 F2 F1 F2 F1 F2F1 F2 F1 F2 F1 F2F1 F2

Strona 46

EDUS301214-N Instructions for Antifreeze UsageInstallation of Outside Units 493. Instructions for Antifreeze Usage3P302356B5050― 50%― 50%― 50%

Strona 47

REFNET Pipe System EDUS301214-N50 Installation of Outside Units4. REFNET Pipe System4.1 Layout Example4.1.1 Heat Pump Series: Use of the particular b

Strona 48

EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 514.1.2 Heat Recovery SeriesUse of the particular branch fitting appropriate to each indi

Strona 49

REFNET Pipe System EDUS301214-N52 Installation of Outside Units4.2 Max. Refrigerant Piping Length4.2.1 Heat Pump SeriesNotes:1. Be sure to use a REFNE

Strona 50 - 3P302356B

EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 531. Equivalent Piping Length of Joints and Headers (Reference)* When the equivalent pipi

Strona 51 - 4. REFNET Pipe System

REFNET Pipe System EDUS301214-N54 Installation of Outside Units4.4 REFNET Joints and Headers4.4.1 REFNET JointsFor gas and liquid branch pipes Make s

Strona 52 - 4.1.2 Heat Recovery Series

EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 55 When the number of indoor units to be connected to the branch pipes is less than the

Strona 53 - 4.2.1 Heat Pump Series

REFNET Joint and Header EDUS301214-N56 Installation of Outside Units5. REFNET Joint and Header5.1 REFNET Joint (Branch Kit)KHRP26A22T9KHRP26A33T9KHRP2

Strona 54 - 4.3.2 Heat Recovery Series

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 57KHRP25A22T9KHRP25A33T9KHRP25M72TU9GAS SIDE JOINTLIQUID SIDE JOINTINSULATIONINSULAT

Strona 55 - 4.4.2 REFNET Headers

REFNET Joint and Header EDUS301214-N58 Installation of Outside UnitsKHRP25M73TU9KHRP26A22T9 / KHRP26A33T9C: 2P182411SUCTION GAS SIDE JOINTI. D. 1-3/8I

Strona 56

EDUS301214-N Installation ManualInstallation of Outside Units 53P153897-12X1234567TO OUT/D UNIT TO OUT/D UNIT TO OUT/D UNITF1F2F1 F2F1 F2 F1 F2LOW NOI

Strona 57 - 5. REFNET Joint and Header

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 59C: 2P182411 φ 3/4φ 5/8φ 3/4φ 5/8φ 5/8φ 1/2φ 3/8φ 1/4φ 1/2φ 7/8φ 3/4φ 3/8φ 3/4φ 3/8

Strona 58 - KHRP25M72TU9

REFNET Joint and Header EDUS301214-N60 Installation of Outside UnitsKHRP25A22T9 / KHRP25A33T9C: 3P203737φ 3/4φ 3/8φ 7/8φ 1φ 3/4I.D φ 1/2I.D φ 7/8I.D φ

Strona 59 - KHRP26A22T9 / KHRP26A33T9

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 61C: 3P203737 φ 3/4φ 5/8φ 5/8φ 3/4φ 3/4φ 5/8φ 7/8φ 7/8φ 3/4φ 3/4φ 5/8φ 3/8φ 3/8φ 3/4

Strona 60 - C: 2P182411

REFNET Joint and Header EDUS301214-N62 Installation of Outside UnitsKHRP25M72TU9 / KHRP25M73TU9 / KHRP26M72TU9 / KHRP26M73TU93P161697D

Strona 61 - KHRP25A22T9 / KHRP25A33T9

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 633P161697D 15º15º15º

Strona 62 - C: 3P203737

REFNET Joint and Header EDUS301214-N64 Installation of Outside Units5.2 REFNET Header (Branch Kit)KHRP26M22H9KHRP26M33H9KHRP26M72H9KHRP26M73HU9C: D3K0

Strona 63 - 3P161697D

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 65KHRP25M33H9KHRP25M72H9KHRP25M73HU9SUCTION GAS SIDEI. D φ 3/4I. D φ 5/8I. D φ 1/2I.

Strona 64

REFNET Joint and Header EDUS301214-N66 Installation of Outside UnitsKHRP26M22H9 / KHRP26M33H9 / KHRP26M72H9C: 3P113151C7/815/83/83/85/83/43/85/85/83/4

Strona 65 - Unit (in.)

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 67C: 3P113151C 7/81 1-1/8

Strona 66 - KHRP25M73HU9

REFNET Joint and Header EDUS301214-N68 Installation of Outside UnitsKHRP25M33H9 / KHRP25M72H9C: 3P113623D

Strona 67

Installation Manual EDUS301214-N6 Installation of Outside Units3P153897-12X132AB[A-arrow view] [B-arrow view]figure 21figure 20figure 191278911105436&

Strona 68 - 1 1-1/8

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 69C: 3P113623D

Strona 69 - KHRP25M33H9 / KHRP25M72H9

REFNET Joint and Header EDUS301214-N70 Installation of Outside UnitsKHRP25M73HU9 / KHRP26M73HU93P185500

Strona 70 - C: 3P113623D

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 713P185500

Strona 71 - KHRP25M73HU9 / KHRP26M73HU9

REFNET Joint and Header EDUS301214-N72 Installation of Outside Units5.3 Outside Unit Multi Connection Piping KitBHFP22MA56UUnit (in.)Unit (in.)3D05475

Strona 72 - 3P185500

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 73BHFP22MA84UUnit (in.)Unit (in.)3D054754Gas side joint3D054753Liquid side joint

Strona 73 - BHFP22MA56U

REFNET Joint and Header EDUS301214-N74 Installation of Outside UnitsBHFP26MA56UUnit (in.)Unit (in.)3D054756Gas side joint3D054757Liquid side joint

Strona 74 - 3D054753

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 75BHFP26MA56U, continuedUnit (in.)3D054755Gas side joint

Strona 75 - BHFP26MA56U

REFNET Joint and Header EDUS301214-N76 Installation of Outside UnitsBHFP26MA84UUnit (in.)Unit (in.)3D054752Gas side joint3D054753Liquid side joint

Strona 76 - 3D054755

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 77BHFP26MA84U, continuedUnit (in.)3D054751Gas side joint

Strona 77 - 3D054752

REFNET Joint and Header EDUS301214-N78 Installation of Outside UnitsBHFP22MA56U / BHFP22MA84U, BHFP26MA56U / BHFP26MA84U1P185542

Strona 78 - BHFP26MA84U, continued

EDUS301214-N Installation ManualInstallation of Outside Units 73P153897-12Xfigure 251122334456[Heat pump system] [Heat recovery system]45321figure 241

Strona 79 - 1P185542

EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 791P185542

Strona 80

Field Setting EDUS301214-N80 Installation of Outside Units6. Field Setting6.1 RWEYQ-PTJU/RWEYQ-PYDN2P190474H

Strona 81 - 6. Field Setting

EDUS301214-N Field SettingInstallation of Outside Units 812P190474H

Strona 82 - EDUS301214-N Field Setting

Field Setting EDUS301214-N82 Installation of Outside Units2P190474H

Strona 83 - Field Setting EDUS301214-N

EDUS301214-N Field SettingInstallation of Outside Units 832P190474H

Strona 84

Field Setting EDUS301214-N84 Installation of Outside Units2P190474H45% - 50%45% - 50%

Strona 85 - 45% - 50%

EDUS301214-N Field SettingInstallation of Outside Units 852P190474H

Strona 86

Field Setting EDUS301214-N86 Installation of Outside Units3P190475C

Strona 87

EDUS301214-N Field SettingInstallation of Outside Units 876.2 RWEYQ-PTJU (In case of manufacturing code: RWEYQ-PTJU9)2P294487A

Strona 88

Field Setting EDUS301214-N88 Installation of Outside Units2P294487A

Strona 89

Installation Manual EDUS301214-N8 Installation of Outside Units1. SAFETY CONSIDERATIONSRead these SAFETY CONSIDERATIONS for Installation carefullybefo

Strona 90

EDUS301214-N Field SettingInstallation of Outside Units 892P294487A

Strona 91

Field Setting EDUS301214-N90 Installation of Outside Units2P294487A

Strona 92

EDUS301214-N Field SettingInstallation of Outside Units 912P294487A

Strona 93

Field Setting EDUS301214-N92 Installation of Outside Units2P294487A

Strona 94

EDUS301214-N Field SettingInstallation of Outside Units 933P190475C

Strona 95 - Cautions on product corrosion

© All rights reserved 03/13 FS1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are prod