EDUS301214-N RWEYQ-PTJU3 phase 208/230V, 60HzRWEYQ-PYDN3 phase460V, 60HzInstallation
EDUS301214-N Installation ManualInstallation of Outside Units 9parts other than those specified by Daikin are used, fire or explosion could result.• D
Installation Manual EDUS301214-N10 Installation of Outside Units3P153897-12X2. INTRODUCTIONThis installation manual concerns VRV inverters of the Daik
EDUS301214-N Installation ManualInstallation of Outside Units 113P153897-12X2-5 Technical specifications (1)(1)Refer to the engineering data book for
Installation Manual EDUS301214-N12 Installation of Outside Units3P153897-12X3. SELECTION OF LOCATIONThis unit does not have specifications for outdoor
EDUS301214-N Installation ManualInstallation of Outside Units 133P153897-12XWARNINGDo not install in the following locations.•Locations such as kitche
Installation Manual EDUS301214-N14 Installation of Outside Units3P153897-12X7. HANDLING OF THE BRAZED PLATE-TYPE HEAT EXCHANGERCAUTIONA brazed plate-t
EDUS301214-N Installation ManualInstallation of Outside Units 153P153897-12X[NOTES](1) The circle marks in the columns for corrosion or scale to devel
Installation Manual EDUS301214-N16 Installation of Outside Units3P153897-12X8-3 General• Make sure to connect the power supply wire to the power suppl
EDUS301214-N Installation ManualInstallation of Outside Units 173P153897-12X2. PC board (A1P)3. Mount an insulation sleeve.4. Connection of interlock
Installation Manual EDUS301214-N18 Installation of Outside Units3P153897-12XCAUTION¢Precautions when laying power supply wiring²Use round pressure ter
EDUS301214-NInstallation of Outside Units 1Installation ofOutside Units1. Center of Gravity ...
EDUS301214-N Installation ManualInstallation of Outside Units 193P153897-12X• Incorrect installation may cause breakage of outside unit.(Refer to figu
Installation Manual EDUS301214-N20 Installation of Outside Units3P153897-12X¢Cautions for installation of multiple outside units²1.The piping between
EDUS301214-N Installation ManualInstallation of Outside Units 213P153897-12X9-5 Example of connection In case of a system of switching between coolin
Installation Manual EDUS301214-N22 Installation of Outside Units3P153897-12X9-6 Air tight test and vacuum dryingThe units were checked for leaks by th
EDUS301214-N Installation ManualInstallation of Outside Units 233P153897-12X2.After the vacuum drying is finished, charge the additional refrigerant i
Installation Manual EDUS301214-N24 Installation of Outside Units3P153897-12X10. CHECKS AFTER INSTALLATIONWARNING• Never connect power supply wiring to
EDUS301214-N Installation ManualInstallation of Outside Units 253P153897-12X¢Cautions for check operation²• If the system is started within about 12 m
Installation Manual EDUS301214-N26 Installation of Outside Units3P153897-12XPay a special attention to the place, such as a basement, etc. where refri
EDUS301214-N Installation ManualInstallation of Outside Units 272.2 RWEYQ-PTJU (In case of manufacturing code: RWEYQ-PTJU9)3P153897-15T123figure 11245
Installation Manual EDUS301214-N28 Installation of Outside Units3P153897-15T1234567TO OUT/D UNIT TO OUT/D UNIT TO OUT/D UNITF1F2F1 F2F1 F2 F1 F2LOW NO
Center of Gravity EDUS301214-N2 Installation of Outside Units1. Center of GravityRWEYQ72PTJU / RWEYQ84PTJUUnit: in. (mm)RWEYQ72PYDN/RWEYQ84PYDNUnit: i
EDUS301214-N Installation ManualInstallation of Outside Units 293P153897-15T132AB[A-arrow view] [B-arrow view]figure 21figure 20figure 195431278911106
Installation Manual EDUS301214-N30 Installation of Outside Units3P153897-15Tfigure 251122334456[Heat pump system] [Heat recovery system]45321figure 24
EDUS301214-N Installation ManualInstallation of Outside Units 311. SAFETY CONSIDERATIONSRead these SAFETY CONSIDERATIONS for Installation carefullybef
Installation Manual EDUS301214-N32 Installation of Outside Unitsparts other than those specified by Daikin are used, fire or explosion could result.•
EDUS301214-N Installation ManualInstallation of Outside Units 332. INTRODUCTIONThis installation manual concerns VRV inverters of the Daikin RWEYQ-P s
Installation Manual EDUS301214-N34 Installation of Outside Units3P153897-15T2-5 Technical specifications (1)(1)Refer to the engineering data book for
EDUS301214-N Installation ManualInstallation of Outside Units 353P153897-15T3. SELECTION OF LOCATIONThis unit does not have specifications for outdoor
Installation Manual EDUS301214-N36 Installation of Outside Units3P153897-15TNOTE• If the unit is to be installed on a roof, check the strengt
EDUS301214-N Installation ManualInstallation of Outside Units 373P153897-15T7-3 Daily service and maintenance1.Management of water qualityThe plate ty
Installation Manual EDUS301214-N38 Installation of Outside Units3P153897-15T8. FIELD WIRINGNOTE• All field wiring and components must be installed by
EDUS301214-N Installation ManualInstallation of Outside Units 32. Installation Manual2.1 RWEYQ-PTJU/RWEYQ-PYDN3P153897-12X12 (PTJU)2 (PYDN)figure 1124
EDUS301214-N Installation ManualInstallation of Outside Units 393P153897-15TConnect the wire to the terminal block on PC board with care since too muc
Installation Manual EDUS301214-N40 Installation of Outside Units3P153897-15TField line connection:L1, L2, L3, phase of the power supply wiring should
EDUS301214-N Installation ManualInstallation of Outside Units 419. REFRIGERANT PIPINGCAUTIONAfter completing installation, be sure to open the valves.
Installation Manual EDUS301214-N42 Installation of Outside Units3P153897-15TPrecautions when connecting pipes• See the following table for flare part
EDUS301214-N Installation ManualInstallation of Outside Units 433P153897-15T13 English9-5 Example of connection∗ In case of a system of switching betw
Installation Manual EDUS301214-N44 Installation of Outside Units3P153897-15T9-6 Air tight test and vacuum dryingThe units were checked for leaks by th
EDUS301214-N Installation ManualInstallation of Outside Units 453P153897-15T2.After the vacuum drying is finished, charge the additional refrigerant i
Installation Manual EDUS301214-N46 Installation of Outside Units3P153897-15T10. CHECKS AFTER INSTALLATIONWARNING• Never connect power supply wiring to
EDUS301214-N Installation ManualInstallation of Outside Units 473P153897-15T〈Cautions for check operation〉• If the system is started within about 12 m
Installation Manual EDUS301214-N48 Installation of Outside Units3P153897-15TPay a special attention to the place, such as a basement, etc. where refri
Installation Manual EDUS301214-N4 Installation of Outside Units3P153897-12XA B CF1 F1F2 F2 Q1 Q2F1 F2 F1 F2 F1 F2F1 F2 F1 F2 F1 F2F1 F2
EDUS301214-N Instructions for Antifreeze UsageInstallation of Outside Units 493. Instructions for Antifreeze Usage3P302356B5050― 50%― 50%― 50%
REFNET Pipe System EDUS301214-N50 Installation of Outside Units4. REFNET Pipe System4.1 Layout Example4.1.1 Heat Pump Series: Use of the particular b
EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 514.1.2 Heat Recovery SeriesUse of the particular branch fitting appropriate to each indi
REFNET Pipe System EDUS301214-N52 Installation of Outside Units4.2 Max. Refrigerant Piping Length4.2.1 Heat Pump SeriesNotes:1. Be sure to use a REFNE
EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 531. Equivalent Piping Length of Joints and Headers (Reference)* When the equivalent pipi
REFNET Pipe System EDUS301214-N54 Installation of Outside Units4.4 REFNET Joints and Headers4.4.1 REFNET JointsFor gas and liquid branch pipes Make s
EDUS301214-N REFNET Pipe SystemInstallation of Outside Units 55 When the number of indoor units to be connected to the branch pipes is less than the
REFNET Joint and Header EDUS301214-N56 Installation of Outside Units5. REFNET Joint and Header5.1 REFNET Joint (Branch Kit)KHRP26A22T9KHRP26A33T9KHRP2
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 57KHRP25A22T9KHRP25A33T9KHRP25M72TU9GAS SIDE JOINTLIQUID SIDE JOINTINSULATIONINSULAT
REFNET Joint and Header EDUS301214-N58 Installation of Outside UnitsKHRP25M73TU9KHRP26A22T9 / KHRP26A33T9C: 2P182411SUCTION GAS SIDE JOINTI. D. 1-3/8I
EDUS301214-N Installation ManualInstallation of Outside Units 53P153897-12X1234567TO OUT/D UNIT TO OUT/D UNIT TO OUT/D UNITF1F2F1 F2F1 F2 F1 F2LOW NOI
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 59C: 2P182411 φ 3/4φ 5/8φ 3/4φ 5/8φ 5/8φ 1/2φ 3/8φ 1/4φ 1/2φ 7/8φ 3/4φ 3/8φ 3/4φ 3/8
REFNET Joint and Header EDUS301214-N60 Installation of Outside UnitsKHRP25A22T9 / KHRP25A33T9C: 3P203737φ 3/4φ 3/8φ 7/8φ 1φ 3/4I.D φ 1/2I.D φ 7/8I.D φ
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 61C: 3P203737 φ 3/4φ 5/8φ 5/8φ 3/4φ 3/4φ 5/8φ 7/8φ 7/8φ 3/4φ 3/4φ 5/8φ 3/8φ 3/8φ 3/4
REFNET Joint and Header EDUS301214-N62 Installation of Outside UnitsKHRP25M72TU9 / KHRP25M73TU9 / KHRP26M72TU9 / KHRP26M73TU93P161697D
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 633P161697D 15º15º15º
REFNET Joint and Header EDUS301214-N64 Installation of Outside Units5.2 REFNET Header (Branch Kit)KHRP26M22H9KHRP26M33H9KHRP26M72H9KHRP26M73HU9C: D3K0
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 65KHRP25M33H9KHRP25M72H9KHRP25M73HU9SUCTION GAS SIDEI. D φ 3/4I. D φ 5/8I. D φ 1/2I.
REFNET Joint and Header EDUS301214-N66 Installation of Outside UnitsKHRP26M22H9 / KHRP26M33H9 / KHRP26M72H9C: 3P113151C7/815/83/83/85/83/43/85/85/83/4
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 67C: 3P113151C 7/81 1-1/8
REFNET Joint and Header EDUS301214-N68 Installation of Outside UnitsKHRP25M33H9 / KHRP25M72H9C: 3P113623D
Installation Manual EDUS301214-N6 Installation of Outside Units3P153897-12X132AB[A-arrow view] [B-arrow view]figure 21figure 20figure 191278911105436&
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 69C: 3P113623D
REFNET Joint and Header EDUS301214-N70 Installation of Outside UnitsKHRP25M73HU9 / KHRP26M73HU93P185500
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 713P185500
REFNET Joint and Header EDUS301214-N72 Installation of Outside Units5.3 Outside Unit Multi Connection Piping KitBHFP22MA56UUnit (in.)Unit (in.)3D05475
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 73BHFP22MA84UUnit (in.)Unit (in.)3D054754Gas side joint3D054753Liquid side joint
REFNET Joint and Header EDUS301214-N74 Installation of Outside UnitsBHFP26MA56UUnit (in.)Unit (in.)3D054756Gas side joint3D054757Liquid side joint
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 75BHFP26MA56U, continuedUnit (in.)3D054755Gas side joint
REFNET Joint and Header EDUS301214-N76 Installation of Outside UnitsBHFP26MA84UUnit (in.)Unit (in.)3D054752Gas side joint3D054753Liquid side joint
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 77BHFP26MA84U, continuedUnit (in.)3D054751Gas side joint
REFNET Joint and Header EDUS301214-N78 Installation of Outside UnitsBHFP22MA56U / BHFP22MA84U, BHFP26MA56U / BHFP26MA84U1P185542
EDUS301214-N Installation ManualInstallation of Outside Units 73P153897-12Xfigure 251122334456[Heat pump system] [Heat recovery system]45321figure 241
EDUS301214-N REFNET Joint and HeaderInstallation of Outside Units 791P185542
Field Setting EDUS301214-N80 Installation of Outside Units6. Field Setting6.1 RWEYQ-PTJU/RWEYQ-PYDN2P190474H
EDUS301214-N Field SettingInstallation of Outside Units 812P190474H
Field Setting EDUS301214-N82 Installation of Outside Units2P190474H
EDUS301214-N Field SettingInstallation of Outside Units 832P190474H
Field Setting EDUS301214-N84 Installation of Outside Units2P190474H45% - 50%45% - 50%
EDUS301214-N Field SettingInstallation of Outside Units 852P190474H
Field Setting EDUS301214-N86 Installation of Outside Units3P190475C
EDUS301214-N Field SettingInstallation of Outside Units 876.2 RWEYQ-PTJU (In case of manufacturing code: RWEYQ-PTJU9)2P294487A
Field Setting EDUS301214-N88 Installation of Outside Units2P294487A
Installation Manual EDUS301214-N8 Installation of Outside Units1. SAFETY CONSIDERATIONSRead these SAFETY CONSIDERATIONS for Installation carefullybefo
EDUS301214-N Field SettingInstallation of Outside Units 892P294487A
Field Setting EDUS301214-N90 Installation of Outside Units2P294487A
EDUS301214-N Field SettingInstallation of Outside Units 912P294487A
Field Setting EDUS301214-N92 Installation of Outside Units2P294487A
EDUS301214-N Field SettingInstallation of Outside Units 933P190475C
© All rights reserved 03/13 FS1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are prod