OUTDOOR UNIT RQYQ140P RXYQQ8T RXYQQ10T RXYQQ12T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ20T
Capacity range HP 5 8 10 12 14 16 18 20
Cooling capacity Nom. kW 14.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0
Heating capacity Nom. kW 16.0 25.0 31.5 37.5 45.0 50.0 56.0 63.0
Power input -
50Hz
Cooling Nom. kW 3.36 5.21 7.29 8.98 11.0 13.0 14.7 18.5
Heating Nom. kW 3.91 5.51 7.38 9.10 11.2 12.8 14.4 17.0
EER 4.17 4.30 3.84 3.73 3.64 3.46 3.40 3.03
ESEER
- 6.37 (2) / 7.53 (3) 5.67 (2) / 7.20 (3) 5.50 (2) / 6.96 (3) 5.31 (2) / 6.83 (3) 5.05 (2) / 6.50 (3) 4.97 (2) / 6.38 (3) 4.42 (2) / 5.67 (3)
COP
4.09
4.54 4.27 4.12 4.02 3.91 3.89 3.71
Maximum number of connectable indoor units 10 64 (1)
Indoor index
connection
Min. 62.5 100 125 150 175 200 225 250
Nom. 125 200 250 300 350 400 450 500
Max. 162.5 260 325 390 455 520 585 650
Dimensions Unit
HeightxWidthxDepth
mm 1,680x635x765 1,685x930x765 1,685x1,240x765
Weight Unit kg 175 187 194 305 314
Fan Air ow rate Cooling Nom. m³/min - 162 175 185 223 260 251 261
Sound power level Cooling Nom. dBA - 78 79 81 86 88
Sound pressure level
Cooling Nom. dBA 54 58 61 64 65 66
Operation range Cooling Min.~Max. °CDB -5~43
Heating Min.~Max. °CWB -20~15.5
Refrigerant Type R-410A
Piping
connections
Liquid OD mm 9.52 12.7 15.9
Gas OD mm 15.9 19.1 22.2 28.6
Total piping length
System Actual m 300
Power supply Phase/Frequency/Voltage Hz/V 3~/50/380-415 3N~/50/380-415
Current - 50Hz Maximum fuse amps (MFA) A 15 20 25 32 40 50
OUTDOOR UNIT RXYQQ22T RXYQQ24T RXYQQ26T RXYQQ28T RXYQQ30T RXYQQ32T RXYQQ34T RXYQQ36T
System Outdoor unit module 1 RXYQQ10T RXYQQ8T RXYQQ12T RXYQQ16T
Outdoor unit module 2 RXYQQ12T RXYQQ16T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ16T RXYQQ18T RXYQQ20T
Outdoor unit module 3 -
Capacity range HP 22 24 26 28 30 32 34 36
Cooling capacity Nom. kW 61.5 67.4 73.5 78.5 83.5 90.0 95.0 101.0
Heating capacity Nom. kW 69.0 75.0 82.5 87.5 93.5 100.0 106.0 113.0
Power input -
50Hz
Cooling Nom. kW 16.3 18.2 20.0 22.0 23.7 26.0 27.7 31.5
Heating Nom. kW 16.5 18.3 20.3 21.9 23.5 25.6 27.2 29.8
EER 3.77 3.70 3.68 3.57 3.52 3.46 3.43 3.21
ESEER
5.58 (2) / 7.07 (3) 5.42 (2) / 6.81 (3) 5.39 (2) / 6.89 (3) 5.23 (2) / 6.69 (3) 5.17 (2) / 6.60 (3) 5.05 (2) / 6.50 (3) 5.01 (2) / 6.44 (3) 4.68 (2) / 6.02 (3)
COP 4.18 4.10 4.06 4.00 3.98 3.91 3.90 3.79
Maximum number of connectable indoor units 64 (1)
Piping
connections
Liquid OD mm 15.9 19.1
Gas OD mm 28.6 34.9 41.3
Total piping length
System Actual m 300
Current - 50Hz Maximum fuse amps (MFA) A 63 80
OUTDOOR UNIT RXYQQ38T RXYQQ40T RXYQQ42T
System Outdoor unit module 1 RXYQQ8T RXYQQ10T RXYQQ10T
Outdoor unit module 2 RXYQQ10T RXYQQ12T RXYQQ16T
Outdoor unit module 3 RXYQQ20T RXYQQ18T RXYQQ16T
Capacity range HP 38 40 42
Cooling capacity Nom. kW 106.0 112.0 118.0
Heating capacity Nom. kW 120.0 125.0 132.0
Power input -
50Hz
Cooling Nom. kW 31.0 33.3
Heating Nom. kW 29.9 30.9 33.0
EER 3.42 3.61 3.54
ESEER 5.03 (2) / 6.36 (3) 5.29 (2) / 6.74 (3) 5.19 (2) / 6.65 (3)
COP 4.01 4.05 4.00
Maximum number of connectable indoor units 64 (1)
Piping
connections
Liquid OD mm 19.1
Gas OD mm 41.3
Total piping length
System Actual m 300
Current - 50Hz Maximum fuse amps (MFA) A 100
(1) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (2) The STANDARD ESEER value corresponds with normal
VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (3) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality (
variable refrigerant temperature control operation)
RXYQQ-TRQYQ140P