• Indoor Unit • Round flow cassette • FXFQ-A
1
6
• VRV Systems • Indoor Unit
10
6 Capacity tables
6 - 3 Capacity Correction Factor
FXFQ-A
3D079901
Capacity correction factor Te = 9°C
Indoor air
temperature
14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
FXFQ20A
TC 0.696 0.741 0.794 0.813 0.831 0.861 0.884
SHF 1.156 1.151 1.107 1.091 1.077 1.053 1.037
FXFQ25A
TC 0.696 0.741 0.794 0.813 0.831 0.861 0.884
SHF 1.156 1.151 1.107 1.091 1.077 1.053 1.037
FXFQ32A
TC 0.673 0.728 0.784 0.803 0.820 0.851 0.874
SHF 1.175 1.155 1.107 1.091 1.077 1.052 1.036
FXFQ40A
TC 0.681 0.732 0.786 0.805 0.821 0.852 0.875
SHF 1.165 1.152 1.106 1.090 1.077 1.053 1.036
FXFQ50A
TC 0.662 0.692 0.755 0.779 0.800 0.834 0.858
SHF 1.173 1.183 1.121 1.096 1.079 1.054 1.035
FXFQ63A
TC 0.664 0.693 0.756 0.781 0.803 0.834 0.858
SHF 1.168 1.182 1.121 1.095 1.078 1.054 1.035
FXFQ80A
TC 0.670 0.693 0.756 0.784 0.807 0.834 0.858
SHF 1.154 1.181 1.120 1.093 1.075 1.055 1.036
FXFQ100A
TC 0.678 0.697 0.763 0.790 0.810 0.834 0.858
SHF 1.140 1.174 1.115 1.089 1.073 1.060 1.048
FXFQ125A
TC 0.680 0.697 0.763 0.790 0.810 0.834 0.858
SHF 1.136 1.175 1.115 1.089 1.072 1.061 1.049