3
1
6
• VRV Systems • Indoor Unit
11
• Indoor Unit • Round flow cassette • FXFQ-A
6 Capacity tables
6 - 3 Capacity Correction Factor
FXFQ-A
3D079901
Capacity correction factor Te = 11°C
Indoor air
temperature
14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
FXFQ20A
TC 0.567 0.597 0.641 0.676 0.705 0.756 0.796
SHF 1.156 1.237 1.238 1.193 1.161 1.111 1.077
FXFQ25A
TC 0.567 0.597 0.641 0.676 0.705 0.756 0.796
SHF 1.156 1.237 1.238 1.193 1.161 1.111 1.077
FXFQ32A
TC 0.544 0.572 0.627 0.661 0.691 0.740 0.781
SHF 1.175 1.261 1.241 1.194 1.160 1.111 1.075
FXFQ40A
TC 0.551 0.580 0.630 0.664 0.693 0.742 0.782
SHF 1.165 1.248 1.238 1.193 1.160 1.112 1.076
FXFQ50A
TC 0.534 0.545 0.581 0.621 0.657 0.713 0.756
SHF 1.173 1.276 1.282 1.218 1.173 1.115 1.075
FXFQ63A
TC 0.535 0.547 0.581 0.623 0.659 0.715 0.756
SHF 1.168 1.270 1.282 1.217 1.171 1.114 1.076
FXFQ80A
TC 0.538 0.553 0.583 0.626 0.662 0.718 0.755
SHF 1.154 1.253 1.279 1.214 1.168 1.113 1.078
FXFQ100A
TC 0.542 0.561 0.590 0.633 0.669 0.720 0.756
SHF 1.140 1.235 1.268 1.206 1.162 1.116 1.093
FXFQ125A
TC 0.543 0.563 0.590 0.632 0.669 0.720 0.756
SHF 1.136 1.230 1.268 1.206 1.162 1.117 1.096