9. FIELD SETTING
(1) Make sure the service lids are closed on the indoor and outdoor units.
(2) Field setting must be made from the remote controller in accordance with the installation condi-
tion.
Setting can be made by changing the Mode No., FIRST CODE NO., and SECOND CODE NO..
For setting and operation, refer to the FIELD SETTING in the installation manual of the remote controller.
9-1 SETTING AIR FILTER SIGN
Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air fil-
ters.
Change the SECOND CODE NO. according to Table 5 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to 01 for air filter contamination-light)
Ta bl e 5
9-2 SETTING AIR FLOW RATE INCREASE MODE
It is possible to raise set air flow (HIGH and LOW) from the field. Change the SECOND CODE NO. as
shown in Table 6 to suit your needs.
(SECOND CODE NO. is factory set to 01 for standard.)
Ta bl e 6
When using wireless remote controllers
When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.
9-3 SETTING INDOOR UNIT NUMBER OF SIMULTANEOUS OPERATION SYSTEM
When using in simultaneous operation system mode, change the SECOND CODE NO. as shown in
Ta bl e 7 .
(SECOND CODE NO. is factory set to 01 for pair system.)
Ta bl e 7
When using in simultaneous operation system mode, refer to Simultaneous Operation System Individ-
ual Setting section to set master and slave units separately.
When using wireless remote controllers
When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.
Setting
Spacing time of display air
filter sigh
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Air filter
contamination-light
Approx. 200 hrs.
10 (20) 0
01
Air filter
contamination-heavy
Approx. 100 hrs. 02
Setting Mode No. FIRST CODE NO. SECOND CODE NO.
Standard
13(23) 0
01
A little increase 02
Increase 03
Setting Mode No. FIRST CODE NO. SECOND CODE NO.
Pair system (1 unit)
11 (21) 0
01
Simultaneous operation
system (2-unit)
02
Simultaneous operation
system (3-unit)
03
01_EN_3P083811-3T.fm Page 17 Friday, September 3, 2004 10:17 AM